The ABB TotalFlow entry on the Ignition Edge IIoT page is an entitlement, not a download: the driver is a third-party Cirrus Link module that reached beta after that listing was written. It runs on Ignition Edge and standard Ignition, polls G2 late, G3, G4 and G5 flow computers, and needs MQTT Transmission to publish, because the G5 has no native MQTT client.
Both paths make the edge device open the connection as a client. MQTT is TCP plus a broker — one address at the publisher, TLS on 8883, a unique client ID per client, topic-based delivery — while a direct tcp out to tcp in link is faster to build but pins the publisher to each consumer's address and port. Build direct TCP for one fixed pair; build the broker for anything that grows.
Move a machine from Python control to an IPC with a PLC runtime when it needs a guaranteed reaction faster than roughly 10 ms, synchronized motion, or a controls layer others can maintain: the runtime then owns outputs and axes, and Python stays as a client over ADS, OPC UA or shared memory. Count the field I/O, the runtime licence and the commissioning hours before committing.
Stop Node-RED, run npm install with the path to the vendor's package from the Node-RED user directory, restart, and confirm the package name on the Manage palette's Nodes tab. A bare copy into node_modules skips dependency installation and is the usual cause of a node that never appears.
The runtime rejects the container's merged overlay2 path when it resolves through a symlink or against a mount that was not live when the daemon started. Set data-root in /etc/docker/daemon.json, stop the daemon, rsync the old tree to the card, and reboot so the SD card mounts before Docker starts.
The malformed packet line is the broker's disconnect notice: Mosquitto received bytes from that client that do not decode as MQTT and closed that connection. It is a broker-side message, not a controller diagnostic. Make every client ID unique, correlate the line with the controller's Success, Error and Error Code status tags at the same attempt, then capture from the enable-bit trigger and decode the CONNECT before assigning a cause.
Groups of tags can freeze between an Ignition MQTT edge node and the cloud server while the connection stays up, then recover on their own after hours. No fixed version is proven: an in-place module upgrade above 4.0.6 reproduced the same behavior during an active incident, so capture evidence while it happens and monitor past the 29-day recurrence.
When a CODESYS MQTT client crashes only after the program sets xEnable, and not when you force the same variable, the fault is in the code path around the call — most often an allocation sized for a PC runtime that an embedded controller cannot serve. Isolate the flag in its own task, add implicit check POUs, size every declaration for the target, and call the client block unconditionally each cycle.
MQTT forwards your payload bytes unchanged, so a quoted "868.9640" is a JSON string and an analog point rejects it. Either publish a real JSON number at the source, or convert the text in a receiver that parses it, as Geo SCADA 2023's Text JSON driver did in the reported case. Confirm with one controlled test that changes only the quotation marks.
A success status and an Explorer table prove only that the Flux stream produced rows; mqtt.to() fails silently, so isolate the fault hop by hop. Confirm the row entering the sink has balance, the four peak columns and the type tag, test TCP to the broker from the database's own runtime, publish with the real credentials, and keep a subscriber on the exact topic.
A vendor statement that secure MQTT is on the roadmap is not a capability you can design around. Treat MQTT over TLS as confirmed only when the released firmware documentation names it for your controller and firmware version, including certificate handling and client authentication. Until then, put a separate edge PC or gateway between the controller and the TLS-protected broker and keep the controller's link plain inside the plant network.
A Modbus and MQTT Node-RED flow set idles in the low hundreds of MB of RAM, so CPU rarely decides the purchase. Choose DIN-rail hardware on 24 VDC input, eMMC endurance and mounting, and pick x86-64 only if something besides Node-RED will ever run on the box.
Responsibility follows who administers the infrastructure, not the direction the data travels. Company A keeps its receiving PI environment and its boundary, Company B keeps its source servers and its boundary, and the connector host belongs to whichever organization runs it. Every firewall rule across a boundary is approved by the organization that owns that boundary.