IMD Solution Computing Library
Plant-floor computing, explained.
Practical answers for the engineers who specify, install and maintain industrial PCs, edge devices and the software that runs on them.
Read the latest articlesLatest articles
Troubleshooting
LatestFailed to load node catalog: check the gateway and DNS first
The error means the Node-RED editor on the edge computer could not download the catalog from nodered.org. It is almost always a missing default gateway or DNS entry on the edge computer's internet-facing interface, not a firewall rule, because the edge computer is not a router between its two ports.
Explainer
When to split tag history into separate historian databases
Keep the ten tags in one historian unless their groups truly need different retention periods; that policy difference is the only sound reason to split history into separate databases. Query speed is not: a historian query reads the tags and time range requested, not whole files, so smaller stores make trends no faster and a cross-group trend may read several stores. Fix storage growth with deadbands first.
Selection guide
PCS 7 V6.0 on Windows 2000: picking replacement IPC hardware
Do not stand up Windows 2000 under VMware on an IPC 547E as a replacement for a PCS 7 V6.0 station: that combination is not a documented compatible path. Check the exact hardware, operating system, release and S7-400 interface in the vendor compatibility tool, keep V6.0 only on listed native hardware you can still obtain, and otherwise migrate the operating system and PCS 7 together in one coordinated step.
Selection guide
Historian alternative for PLC batch tracking records
Simple batch tracking needs one row per completed batch, not a tag historian. Size the choice with batches per day, retention and concurrent viewers: memory-card logging covers CSV-only jobs, a PC acquisition package adds web viewing and export with no report code, and a companion PC writing to SQL Server Express hands reporting to a database owner — the storage math is megabytes either way.
Troubleshooting
Why Windows IoT LTSC 2021 reads PLC data slower than 2019
A different DLL build identifies a version difference, not a proven cause. Freeze the workload across both partitions, log monotonic timestamps around every read beside the PLC watchdog counter, capture traffic on each partition, and change one inventoried variable at a time: driver, link settings, power management, security software. The watchdog arithmetic decides whether the lost time sits between reads or inside single calls, and each outcome has its own next step.
Troubleshooting
Reading default historian data in SQL Server the supported way
Attaching a SQL Server DSN to the SystemHistorian tag does store the historian's tables in SQL Server, but they are keyed to internal tag IDs, not tag names. Keep the default historian as the store and read the data through the REST SQLQuery endpoint, building an ID-to-name lookup from the Parms tables and paging large ranges in blocks of about ten thousand records.
Troubleshooting
Why an edge VM drops pings from some VLANs after boot
When an edge virtual device answers pings during early boot and then goes unreachable from only some VLANs, suspect a Docker address overlap: the host's container networks reserve 172.16.0.0/12 by default. A corporate subnet inside that range loses its return path once the container bridges come up. Verify the overlap, then move the Docker pool to an unused range through the documented CLI onboarding method.
Troubleshooting
Why S7 nodes disappear from the Node-RED palette
Installing an S7 package such as node-red-contrib-s7 can break another package's startup registration, which empties its node types out of the Node-RED palette; the flows and the S7-1200 are untouched. Compare the installed-package list and startup log against your baseline, reinstall the missing package through the deployment's supported method, restart and hard-refresh, then set the S7-1200's PUT/GET permission, rack and slot, and a non-optimized test block.
How-to
Bidirectional Sparkplug B writes on a CODESYS controller
Version V1.3.0.0 of the CODESYS SparkplugB library makes the controller a bidirectional edge node only after both directions are proven: telemetry from EoN to host through the broker, then NCMD and DCMD writes from the Primary SCADA node into a write handler that changes the process value. Broker receipt is delivery, not acceptance.
Troubleshooting
Why historian data goes missing and reappears the next day
Data that reappears by the next morning was never lost: it reached the affected Historian late and was committed to history with its original timestamps. Anchor the gap start to the logger's block-creation entry, clear the source side with the second Historian on the same OI Server, then set the registry value documented in AVEVA support article 000041658 on the affected server and verify across two block switches.
Troubleshooting
Why MQTT Engine still feeds old tags after a broker stops
Old values keep reaching the screens because MQTT Engine buffers and processes each Edge node's messages in order, so a birth-message flood drains through the tags even after the broker is stopped. Measure the queue with Enable Latency Check and Message Processing Latency, fix the flooding node first, and restart the module only to clear what the fixed cause already built.
Troubleshooting
Why slash aliases in tag historian query return zero rows
The script access pattern is correct: getCoreResults() and getRowCount() are the documented calls for reading a Tag Historian Query from a Script data source. The zero row count comes from the query, not the method. Replace every slash in the Data Key Alias with an underscore, leave the historian tag path untouched, and read row zero only after the row count is greater than zero.