The ABB TotalFlow entry on the Ignition Edge IIoT page is an entitlement, not a download: the driver is a third-party Cirrus Link module that reached beta after that listing was written. It runs on Ignition Edge and standard Ignition, polls G2 late, G3, G4 and G5 flow computers, and needs MQTT Transmission to publish, because the G5 has no native MQTT client.
The port-in-use error means the AutoStart instance already owns port 1880, so keep autostart on and do not launch a second instance. From your PC, open the editor at the gateway's own interface address, for example 192.168.200.1:1880 on the X1P2 link, never 127.0.0.1:1880, which points at the PC itself.
A Node-RED editor that stops at the header, sidebar and loading animation while the dashboard at /ui still serves fresh values is a browser fault, not a runtime fault. Test the editor in a second browser or clean profile, read the console and network errors, then update or repair that browser. Reinstalling Node-RED or Node.js cannot fix it, because the failing component never touches the server.
Ping proves only that small ICMP packets cross the VPN. Intermittent PLC programming access comes from three causes: a firewall rule that never allows the programming session, a missing return route or gateway on the PLC, or a tunnel MTU below 1500 bytes that drops full-size packets. Test the port, read the router log, then fix the first cause that fails.
A firewall label is not the device's name; it is text the firewall took from a named address object, a DNS lookup, a DHCP lease, its discovery inventory or the management display. Identify which source the page in front of you reads, change the name through that source's owner, and verify with fresh traffic. On an Industrial Edge appliance the device-side hostname changes through the documented configuration path, never a generic OS rename command.
The PCS 7 V10 SP2 hardware requirements page names five IPCs for the OS server role, but the compatibility matrix releases Windows Server 2025 only for the RW-/RS-528A and RW-/RS-548A families. The two documents answer different questions, and the matrix decides the operating system.
A yellow power LED with a restart loop means the board is powered but never completes startup. Decide at the BIOS screen: if setup opens, the fault is late in the boot chain; if it does not open after cleaning and swapping power module, RAM and disk, the chassis has failed and the disk moves to a replacement.
The SENDDATA timer handler publishes only when MQTT STATUS returns 5, and the script never calls MQTT CONNECT again after a failure, so one LSTERR 28 at startup or any later drop silences every following cycle. Trace STATUS on each cycle, add a controlled reconnect to the connect label, and move the SUBSCRIBE loop after CONNECT.
A CPU peak from an InfluxDB container that repeats on a fixed schedule and survives stopping Node-RED and Grafana is scheduled work, not client load. Suspect the tasks defined around the container first — health checks, metrics scrapes, backups — then prove the cause by stopping the InfluxDB container alone and running a two-way test; fix the task you find, or move the historian stack to a dedicated box.
Build one groov View page and one Node-RED flow: eight Data Store tags drive two five-row file lists, an API key with groov Manage permission drives the unmount call, and operators work from a single page after a one-time setup. Move means select, wait for the indication, Refresh; safe removal means Unmount, Refresh, and pull the drive only when the USB filenames disappear.
The hourly offline cycle comes from the router's Max outgoing call duration, which defaults to 60 minutes and closes the Talk2M session on schedule even though the internet link itself is fine. Set it to 0 for an unlimited session, or to a longer site-approved value, then confirm the fix with separate WAN and gateway tests.
Yes: 1,000 Modbus tags at a one-minute interval is 16.7 values per second and fits Node-RED writing to SQL Server, provided reads are grouped per device and each poll-plus-insert cycle finishes well inside the logging window. The budget below puts a grouped design at about 3.5 seconds per cycle and a per-tag design at 51 seconds, which ten device timeouts push past the deadline.
On an Ewon Flexy with firmware 14.x or later, a BASIC script reads the MQTT link state with the MQTT Status command: a returned 5 means the connection is operational and any other value means it is not. The firmware owns disconnection and reconnection, so the script only monitors and logs, and you investigate the internet path when the broker never comes back on its own.