IMD Solution Computing Library
Plant-floor computing, explained.
Practical answers for the engineers who specify, install and maintain industrial PCs, edge devices and the software that runs on them.
Read the latest articlesLatest articles
Troubleshooting
LatestWhy oversized history blocks spike historian RAM at merge
Merge crashes on 15 to 20 GB history blocks are an input-volume problem, not a memory problem. Measure which of three causes fills the blocks — corrupted block sets, alarm and event bloat, or store-and-forward replay into old intervals — then fix that source. Adding RAM only moves the crash threshold; recalculated blocks stay small once the true cause is removed.
Explainer
PI AF SDK: the native path from a C# application to PI
No driver joins two OPC UA clients, so KEPServerEX needs no new driver for this. Read PI Data Archive and PI Asset Framework from C# through PI AF SDK, which needs the server-side PSA license. Any new values must flow through a real OPC UA server endpoint that a licensed PI OPC UA interface or connector collects from.
Comparison
WinCC CAS versus SIMATIC IT Historian: which archive fits
WinCC CAS is the long-term archive inside one WinCC system: it stores process values, messages and batch data from OS servers and SIMATIC BATCH. SIMATIC IT Historian is a plant-level historian that aggregates raw, compressed, validated and aggregated data from heterogeneous sources and adds KPI calculation and reporting. Choose CAS for a single WinCC installation; choose the Historian when you must consolidate several systems or serve validated, user-facing reports.
Troubleshooting
Edge gateway cloud connected but PLC variables missing
A Connected cloud status proves only the gateway-to-hub link. When the metric node tree shows only Sys, data and downstream and the driver list lacks the PLCnext data source, discovery between controller and gateway failed, not the cloud link. Run the controller-side checks, escalate through the gateway application's Contact Support channel with the evidence list, and accept the fix only when a changed test value reaches the hub.
Troubleshooting
Aggregation Matrix report fails when tag count rises
The failing report is the bigger aggregate workload even though it covers a shorter time range: report size follows tags times intervals, not the date span. The error name identifies the database function that was executing, not the cause. Capture the complete SQL message and test one report setting at a time.
Explainer
Node-RED IO data MQTT setup: keep publish and control separate
An IO-over-MQTT setup on an edge PC has three separate boundaries: the IO service that publishes values, the MQTT path that carries them, and the control path back to the device. Seeing values in Node-RED proves only the receive direction; you verify control at the device itself, and you troubleshoot from the first boundary where data stops.
Explainer
Why Node-RED in Docker cannot run a Windows shutdown script
A Node-RED exec node in a Docker container launches processes inside Linux, so a Windows .bat file can never execute from it. Route the shutdown request through Windows OpenSSH with a restricted management account, and transfer ownership of the whole stop sequence to Windows before the Node-RED container exits.
Troubleshooting
Failed to load node catalog: check the gateway and DNS first
The error means the Node-RED editor on the edge computer could not download the catalog from nodered.org. It is almost always a missing default gateway or DNS entry on the edge computer's internet-facing interface, not a firewall rule, because the edge computer is not a router between its two ports.
Explainer
When to split tag history into separate historian databases
Keep the ten tags in one historian unless their groups truly need different retention periods; that policy difference is the only sound reason to split history into separate databases. Query speed is not: a historian query reads the tags and time range requested, not whole files, so smaller stores make trends no faster and a cross-group trend may read several stores. Fix storage growth with deadbands first.
Selection guide
PCS 7 V6.0 on Windows 2000: picking replacement IPC hardware
Do not stand up Windows 2000 under VMware on an IPC 547E as a replacement for a PCS 7 V6.0 station: that combination is not a documented compatible path. Check the exact hardware, operating system, release and S7-400 interface in the vendor compatibility tool, keep V6.0 only on listed native hardware you can still obtain, and otherwise migrate the operating system and PCS 7 together in one coordinated step.
Selection guide
Historian alternative for PLC batch tracking records
Simple batch tracking needs one row per completed batch, not a tag historian. Size the choice with batches per day, retention and concurrent viewers: memory-card logging covers CSV-only jobs, a PC acquisition package adds web viewing and export with no report code, and a companion PC writing to SQL Server Express hands reporting to a database owner — the storage math is megabytes either way.
Troubleshooting
Why Windows IoT LTSC 2021 reads PLC data slower than 2019
A different DLL build identifies a version difference, not a proven cause. Freeze the workload across both partitions, log monotonic timestamps around every read beside the PLC watchdog counter, capture traffic on each partition, and change one inventoried variable at a time: driver, link settings, power management, security software. The watchdog arithmetic decides whether the lost time sits between reads or inside single calls, and each outcome has its own next step.