ABB TotalFlow module for Ignition: what exists today

Edge computing and IIoT Published 5 min read

Short answer

The ABB TotalFlow entry on the Ignition Edge IIoT page is an entitlement, not a download: the driver is a third-party Cirrus Link module that reached beta after that listing was written. It runs on Ignition Edge and standard Ignition, polls G2 late, G3, G4 and G5 flow computers, and needs MQTT Transmission to publish, because the G5 has no native MQTT client.

On this page
  1. What the Edge IIoT listing actually means
  2. Where the driver runs, and what it polls
  3. The MQTT path and poll loading
  4. Working the data path for one G5 flow computer on Ignition Edge
  5. Verifying the path after install
  6. One caution for beta code on measurement points
  7. Questions asked

The ABB TotalFlow entry on the Ignition Edge IIoT page is an entitlement, not a published download. That page, in the Ignition 8.0 user manual, lists the modules the Edge IIoT license activates — and when it was written, the TotalFlow driver was a third-party Cirrus Link module still in development; it reached beta afterward. What exists is a device driver that runs on an Ignition gateway, polls the flow computer, and hands the values to MQTT Transmission for publishing. The G5 has no native MQTT client, so the flow computer never talks to a broker itself: the gateway is the MQTT edge, and the unit stays a polled device.

What the Edge IIoT listing actually means #

The Edge IIoT page of the Ignition 8.0 manual names four modules the license activates: MQTT Transmission, Opto22 SNAP PAC driver, Emerson ROC driver and ABB TotalFlow. A name on that list is an entitlement — the license covers it once the module is installed — not proof that a module file has been published. At the time of that listing the TotalFlow module had not shipped; it went to beta afterward.

Third-party modules for Ignition are distributed as module files from their vendor and listed by name on the third-party modules page of the Ignition downloads site, scoped to the gateway version — the documented listing carries 8.1.43. Treat the vendor's release notes and that listing, not the Edge IIoT page, as the record of what is downloadable today, and confirm the current build with the vendor's sales team before you plan a deployment around it.

The module is sold the way other third-party Ignition modules are: a licensed module with an optional annual support contract. Note also that later editions of the manual list a different Edge IIoT module set — the 8.1 page names MQTT Transmission, Opto22 SNAP PAC Driver and Remote Tag Provider — so the controlling list for your site is the one for the gateway version you run.

Where the driver runs, and what it polls #

The module is a device driver on an Ignition gateway, and it runs on both Ignition Edge and standard Ignition installations — do not buy an Edge license just to get the driver. The driver polls the TotalFlow unit over its configured connection, and the values surface as tags in the gateway's tag browser.

The protocol implementation targets four hardware variants: G2 late, G3, G4 and G5. The vendor's own statement at release was that not every hardware version had been tested, and early G2 units sit outside the list. For a fleet, that means each unit is identified by hardware variant and firmware before the driver is counted on.

Placement follows the comms path. An Ignition Edge gateway at the site — usually a fanless mini PC in the cabinet beside the flow computer — needs no always-up link to the outside. Standard Ignition at a central server works when a comms path to the unit is reachable from there.

The MQTT path and poll loading #

MQTT Transmission publishes the polled tags upstream to your broker, which makes this the same pattern as bridging OPC UA PLC data to MQTT with an edge PC: one gateway owns the device protocol and republishes over MQTT.

Polling is the load that matters. Each poll cycle occupies the flow computer's communication port and, on remote low-power sites, its power budget. Set the poll interval from the fastest change you need to see, not from what the gateway can issue. When the broker link drops, MQTT store and forward backfill after a connection outage is the behavior to plan for, because the driver keeps polling while the publisher waits to deliver.

Working the data path for one G5 flow computer on Ignition Edge #

Inputs, each from the documented record:

  • Modules the Edge IIoT license activates (8.0 manual page): 4 — MQTT Transmission, Opto22 SNAP PAC driver, Emerson ROC driver, ABB TotalFlow.
  • Hardware variants the driver's protocol implementation covers (vendor statement): 4 — G2 late, G3, G4, G5.
  • Native MQTT clients in a G5 flow computer (vendor confirmation): 0.
  • Gateway platforms that can run the module: 2 — Ignition Edge and standard Ignition.

Rule in words: with zero MQTT clients in the flow computer, the path needs exactly one gateway running exactly two modules — the TotalFlow driver to poll the unit and MQTT Transmission to publish its tags. Everything else the license activates sits idle on this path.

Arithmetic:

  • 4 activated modules − 2 doing this work = 2 idle: the Opto22 SNAP PAC and Emerson ROC drivers stay activated but unused.
  • The G5 is 1 of the 4 covered variants, so the unit is inside the protocol scope, with the vendor's untested-hardware caveat until the release build.
  • 0 native MQTT clients in the unit = 0 broker-only options, so 1 site holding TotalFlow units needs 1 gateway.

Result: one Ignition Edge gateway at the site, running 2 of the 4 activated modules, polls the G5 and publishes its tags; nothing else in the activated set participates.

Decision: any site with one or more TotalFlow units needs exactly one gateway, because the units contribute zero MQTT clients and no broker-only path exists. Edge belongs at the site when no always-up central link is available; standard Ignition centrally when one is.

Verifying the path after install #

  • The gateway's module page shows the TotalFlow module installed and running.
  • The device connection reads connected and holds across several poll cycles, not just the first.
  • Compare one flow, one pressure and one temperature value in the tag browser against the flow computer's local display at the same moment. A fixed offset or scaling error is a mapping or units problem, not a comms fault.
  • Subscribe to the broker from a separate client and confirm the published values update at the poll rate.

One caution for beta code on measurement points #

The module reached beta after the Edge IIoT listing, and the vendor had not tested every hardware version within the four supported variants. Running beta code on custody-transfer measurement points is a decision to document, not a default: keep the established measurement record in place until a release build is validated against the unit's own totals.

Questions asked

Does the Ignition Edge IIoT license include the TotalFlow module, or is it a separate purchase?

Both, in sequence: the Edge IIoT listing says the license activates the module, but third-party Ignition modules are sold by their vendor. This one is a licensed module with an optional annual support contract. Ask the vendor's sales team whether licensing is per gateway or per device, because that difference decides the cost across a multi-site fleet, and the answer belongs in the written quote, not in an assumption.

One of my flow computers is an early G2. Is it supported?

The protocol implementation targets G2 late, G3, G4 and G5, so early G2 hardware sits outside the documented scope, and the vendor had not tested every hardware version even within those four variants. Get written confirmation naming your exact hardware and firmware before you count on the driver covering that unit.

The driver connects but the tags read bad quality. Is that comms or configuration?

Check quality before the link. A connection that stays up while tags read bad quality points to a protocol or configuration fault, such as addressing, mapping or units. A connection that drops intermittently points to the comms path or to port loading from other pollers. Read tag quality first, then the connection status history, and you will know which side to work.

What should I send when the module will not install or the device will not connect?

Five items: module version, Ignition gateway version, the flow computer's hardware variant, its firmware, and gateway logs spanning the failing poll cycles. Open the case with the module vendor and include the gateway vendor when the fault is in module loading rather than the driver itself. With those items support can reproduce the fault without a round of questions first.

Keep reading

  • Comparison

    Getting Wonderware Historian data into Ignition Edge for MQTT

    Yes — Ignition Edge can publish this data as MQTT Sparkplug, but through two separate routes. Live values come from the existing DAServer acquisition layer behind a DA-to-UA gateway, because Edge's OPC client is UA-only. History and aggregates come from SQL queries against the Historian Runtime database, using its documented stored procedures.

    Edge computing and IIoT

  • How-to

    Bridging OPC UA PLC data to MQTT with an edge PC

    Keep the OPC UA server on the PLC side and give MQTT publishing its own role on a separate edge PC that acts as the OPC UA client and MQTT publisher. Commission the two links independently — first a verified tag read, then a verified subscriber message — and only then widen the tag set.

    Edge computing and IIoT

  • Troubleshooting

    Trace an edge gateway MQTT connection failure to Azure Event Grid

    A desktop MQTT client that connects and publishes with thumbprint authentication clears only that endpoint, certificate and permission combination on that host. When the gateway fails against the same Event Grid namespace, test four stages in order on the gateway itself: network path and DNS to TCP 8883, the TLS handshake with both certificate directions and the clock, the CONNECT identity, and publish authorization on the exact topic. The first stage that fails names the fix.

    Edge computing and IIoT