AVEVA Historian Flex licensing and redundancy credits explained

Edge computing and IIoT Published 4 min read

Short answer

Standard and Advanced editions of AVEVA Historian license the second redundant node under Flex, and that node consumes no additional Flex credits. Edge/Local and Historian Starter do not include the redundancy license. The entitlement covers the license side only; the failover path still has to be configured and proven for the installed release.

On this page
  1. Which editions carry the second node
  2. Why the partner adds zero credits
  3. Partner or independent second server
  4. What the entitlement does not configure
  5. Proving the pair before you rely on it
  6. Questions asked

Yes — for two of the four editions. AVEVA Historian Standard and Advanced include the license for a second redundant node, and that node draws no additional Flex credits. Edge/Local and Historian Starter do not include it, so a partner node on those editions needs licensing resolved first. Flex is the subscription program the credits sit under; the edition inside the entitlement is what decides whether the redundant partner is part of the purchase. The entitlement answers the licensing question only — the failover path still has to be configured and proven on your installed release before anyone counts on it.

Which editions carry the second node #

Read the edition from the purchased entitlement and from the license details of the installed deployment — not from the fact that a second server exists in the rack. An installed application is not evidence that its operating role is licensed.

Edition Redundant second node Effect on the Flex credit pool
Standard Included No additional credits
Advanced Included No additional credits
Edge/Local Not included Partner must be licensed before commissioning
Historian Starter Not included Partner must be licensed before commissioning

The decision at this step: on Standard or Advanced, build the pair now, because the entitlement already covers it. On Edge/Local or Starter, resolve the licensing through AVEVA's licensing channel before you configure anything — the entitlement gap does not clear on a reboot.

Why the partner adds zero credits #

The redundancy entitlement travels with the edition. The credit pool is charged for the primary historian deployment, and the partner runs under the same entitlement because its job is to preserve that one history service through a node failure, not to add capacity. That is also the boundary of the answer: it is not a blanket exemption for any second historian in the organization.

Worked example — illustrative, because credit amounts come from your own entitlement statement, not from a universal rate table. Suppose your records show the primary historian deployment charged 100 Flex credits:

  • Redundant partner for that service: 100 + 0 = 100 credits. Total unchanged.
  • Second standalone historian for a different line: 100 + 100 = 200 credits. Full charge for a new deployment.

The arithmetic is trivial; the engineering decision is which of those two lines your second server belongs to.

Partner or independent second server #

Decide by role, not by server count. Record which primary the second node protects, which data sources feed that service, and which clients retrieve history from it. A node mirroring the primary's collection for the same consumers is a partner. A node with its own sources and its own consumers is a separate historian and is charged as one — for instance, a second server that exists to push replicated data toward a PI System is an independent workload with version requirements for Historian-to-PI replication of its own, not a redundant partner.

That record doubles as the commissioning boundary: it tells the team which workload the failover test must preserve, instead of relying on the label "second server".

What the entitlement does not configure #

Installation is not activation. Putting Historian on a second machine does not create the redundant relationship. For the installed release, the pair is configured in the historian configuration reached through OCMC — on the primary node you define the backup — and collection and retrieval follow that architecture, not the license file. Redundancy at the connector layer, where a Citect or Plant SCADA connector chooses between two historians, is a separate decision: it is covered under how Connector redundancy options work.

Commissioning a secondary on an edition that does not carry the entitlement produces an immediate, visible licensing fault rather than a silent gap — a secondary running in demo mode with a license tag violation is the symptom that tells you the edition, not the installer, decides.

Proving the pair before you rely on it #

A correct license does not mean a working failover. Treat collection continuity and client retrieval continuity as separate acceptance items: a partner can preserve data while a misconfigured client cannot read it, and a client can keep reaching a node that has stopped receiving fresh samples.

  1. Clear licensing first: confirm status on both nodes and resolve any reported fault.
  2. Confirm network access between both nodes and every data source the documented architecture needs.
  3. Configure the pair and the collection paths per the release's redundancy procedure.
  4. Point each history client at the documented retrieval arrangement.
  5. Interrupt the primary in a controlled way, during an agreed window with the recovery procedure at hand — that window is when you want to learn the pair does not switch over, not the night the primary actually fails. Measure the transition; do not assume a failover time.
  6. Verify a known tag shows current timestamps and readable history through the intended client on the surviving node.

Watch the known failure modes while you test: output writes stopping on a secondary after failover is one that license state will not explain. When both continuity checks pass, the original question is fully answered: the pair is licensed, and it works.

Questions asked

Is License Server redundancy the same entitlement?

No, it is a different layer. License Server redundancy means two nodes run the License Server and License Manager components, configured from License Manager on the primary node, so license checks survive the loss of one machine. Historian redundancy is the data-service pair described above. A plant that cannot tolerate either loss runs both, and each is set up separately.

Both of our historians collect the same tags in parallel. Is that one license or two?

If both nodes collect the same sources for the same service and the same clients, that is the redundant-pair role, and on Standard or Advanced the partner adds no credits whether it stands by or logs in parallel. If each node collects its own sources for its own consumers, they are two historians regardless of what the servers are called, and each is charged. Decide by role, not by count.

We commissioned the secondary before checking the edition. How do we recover?

Resolve the entitlement through AVEVA's licensing channel first: Standard and Advanced carry the partner, Edge/Local and Starter do not. Then confirm the edition on the renewed entitlement, re-check the secondary's license state until the demo-mode fault clears, and only after that run the failover test. Testing failover on a node still in demo mode proves nothing about production behavior.

At renewal, will the partner node start consuming Flex credits?

Not while the entitlement's edition still includes redundancy. The inclusion follows the edition term by term, so at each renewal read the edition in the entitlement records and the license details of the installed deployment rather than carrying last term's assumption forward. If the edition is unchanged, the partner's zero-credit treatment is unchanged.

Keep reading

  • Explainer

    AVEVA Historian Connector redundancy options explained

    AVEVA Historian Connector v3.1 does not manage failover between redundant Historians. For collection redundancy, run two Connectors, each writing to its own Historian, with configurations you keep identical by procedure; use Historian partner and client failover only to cover temporary access loss.

    Edge computing and IIoT

  • Explainer

    AVEVA Historian to PI replication version requirements

    Replication from AVEVA Historian to AVEVA PI needs the 2023 release of Historian or later and PI Web API v1.16.0 or later on the destination. The two version numbers never need to match, and there is no direct requirement on the PI Archive version. Historian-to-Historian replication instead requires the destination to be the same version or newer than the source.

    Edge computing and IIoT

  • Troubleshooting

    Citect SCADA connector to Historian shows disconnected

    A "Disconnected" destination status means the Citect SCADA Connector has no session to Historian and is buffering samples to local disk. SMC tag-discovery and write entries prove the connector's stages, not that values were archived. Stop the connector, verify the destination instance, services and write authorization, reconnect once, and close only when a query returns a sample and the buffer drains.

    Edge computing and IIoT