Short answer

Start with the historian your SCADA host already licenses; add a separate engine only when an external consumer (enterprise rollup, SSRS-style reporting, cloud analytics) demands one. Keep cross-vendor history on OPC-HDA, move real-time cross-vendor data onto an MQTT bridge instead of OPC-DA COM, and benchmark anything above the reported 10,000-tag field ceiling before committing.

On this page
  1. The decision by situation
  2. What operators actually judge
  3. Real-time cross-vendor data: skip OPC-DA COM
  4. History cross-vendor: OPC-HDA
  5. Sizing: run the record math before you license
  6. Where the cloud fits
  7. Choosing the host hardware
  8. The decision, again
  9. Questions asked

Use the historian your SCADA host already owns. Add a separate historian engine only when a named consumer outside the SCADA screens forces it: an enterprise rollup, a reporting tool that needs SQL access, or a cloud analytics layer. When the data has to cross between two platforms, keep history on OPC-HDA and move real-time onto an MQTT bridge; the OPC-DA COM route between SCADA and an enterprise historian is the link that breaks in the field. For scale, the reported field ceiling on the add-on engine is 10,000 tags across six reported installs; anything above that needs a load test before you commit to it.

The decision by situation #

Situation Decision Why
One SCADA host, no historian yet Use the SCADA host's own historian No bridge, no extra licenses, trends are native to the screens
Add-on engine wanted for analysis, up to 10,000 tags Acceptable if it integrates both ways through a module Six reported installs with no issues; 10,000 tags is the largest reported
1,000,000+ tags No add-on engine without a load test No reported installed result at that scale
Enterprise historian already holds the plant history Keep it; read history over OPC-HDA OPC-HDA ran for years in the field with only occasional service restarts
Real-time values needed across platforms Custom bridge publishing to an MQTT broker Replaces the fragile OPC-DA COM link and the JDBC path that does not scale
Multi-site or enterprise view needed On-premise historian at each site, summaries to the central or cloud layer Operator screens must not depend on a WAN link

What operators actually judge #

An operator judges a historian by three things: the trend loads, the live values stay good, and the report matches the trend. A historian bolted onto the SCADA host as one platform answers all three with one license and one tag database. A separate engine can answer them too, but only if the integration carries data in both directions so SCADA screens and scripts keep reading history as if it were local.

That two-way flow is the test for any add-on. If the module only pushes data out, the SCADA side loses native trending and every screen or script that called the local history API has to change.

Real-time cross-vendor data: skip OPC-DA COM #

Three routes exist for pulling live values from an enterprise historian into a PC-based SCADA host, and the field evidence ranks them clearly:

  • OPC-DA COM connection: worked, then broke frequently; after a historian-side update it stopped and threw errors in the SCADA host. Do not use it for production real-time.
  • Direct database (JDBC-style) connection: works at small tag counts but is not feasible at scale.
  • A custom service that reads the tags and publishes them to an MQTT broker, which the SCADA host subscribes to: the preferred route when the enterprise historian stays.

The reason OPC-DA fails is structural. COM/DCOM ties the connection to the operating system and component versions on both ends simultaneously, so one vendor-side upgrade breaks it with no change on the SCADA side. The MQTT bridge shares only a broker and a topic structure; the price is that you own and maintain the publisher service. If your plant already runs MQTT, the same pattern extends outward — the same reasoning behind connecting on-premise OPC UA and SQL servers to a cloud historian architecture, described in article:connect-on-premise-opc-ua-and-sql-servers-to-a-cloud-pi-system.

History cross-vendor: OPC-HDA #

History is the easier direction. An OPC-HDA connection for historical data ran for years in the field with no issues except the occasional restart of the historian's HDA service. Build that into the design as a monitored service, not a set-and-forget component. The mechanics of reading that history into a SCADA host are covered step by step in article:read-proficy-historian-opc-hda-tags-into-ignition.

Sizing: run the record math before you license #

Historian storage scales on records, not tags. A worked example for a mid-size site:

  • 5,000 logged tags, averaging one stored change per minute (deadband-limited).
  • Records per day: 5,000 × 1,440 minutes = 7,200,000 records per day.
  • Records per year: 7,200,000 × 365 ≈ 2.63 billion records.
  • At roughly 50 bytes per stored record (value, timestamp, quality, compression overhead): 2.63 × 10⁹ × 50 B ≈ 131 GB per year.

Two things move that number hard. The logging trigger — deadband and change-only logging versus fixed-interval logging — can swing the records-per-tag figure by an order of magnitude in either direction, and retention or replication multiplies the footprint. If you log on scan instead of change, redo the math at your scan rate. The same discipline applies before any historian choice; the scale-and-support framework in article:plant-historian-selection-by-scale-and-support-needs walks that inventory.

Where the cloud fits #

Cloud services offer connectivity, storage, asset modeling and visualization, which overlaps what an on-premise SCADA host already does. The layered design that works is not either-or: keep the site historian on-premise for operator trends and alarms, and send summary data upward for the enterprise view. The vendor guidance for multi-site systems points the same way — keep site data local, send summaries to the center. Before anything leaves the site, decide which tags may leave; the tag-exposure control described in article:expose-only-approved-ignition-tags-to-an-external-historian is the gate to put on that flow.

On-premise cloud hardware only enters when a requirement forces specific cloud services to run physically at the site. At that point you are comparing two complete site stacks, and both need sizing and costing.

Choosing the host hardware #

The historian is a disk-bound service that should run on its own machine, sized for write throughput and retention rather than raw CPU. When the existing SCADA host is aging or the historian outgrows it, put the historian on a dedicated box — a fanless industrial mini PC in the cabinet does this job for most site installations.

The decision, again #

  1. No historian yet, one site: the SCADA host's built-in historian. Done.
  2. Analysis or reporting gap, under 10,000 tags: an add-on engine that integrates both ways is field-proven at that scale.
  3. 1,000,000+ tags: run a load test first; no installed result exists at that scale for the add-on engine.
  4. Enterprise historian already in place: keep it, read history over OPC-HDA, and move real-time to an MQTT bridge.
  5. Multi-site: local historian per site, summaries upward, tag exposure gated.

Questions asked

Why avoid OPC-DA for cross-vendor real-time data?

OPC-DA rides on COM/DCOM, so the connection depends on the operating system and component versions on both machines at once. One vendor-side update can break it with no change on the SCADA side, which is exactly what the field reports show. An MQTT bridge shares only a broker and a topic structure, so it survives version changes on either end. The cost is that you own and maintain the bridge service.

How much storage does a site historian need per year?

Estimate records, not tags. Multiply tags by average records per minute by 1,440 minutes per day by 365 days, then multiply by your bytes per record. For 5,000 tags logging one change per minute at roughly 50 bytes per record, that is about 131 GB per year. Change rate, deadband behavior, buffering and retention move that figure, so size from your own logging trigger settings.

When does a cloud historian layer make sense?

When you serve multiple sites or an enterprise dashboard rather than one machine. Keep operator-facing trends and alarms on the on-premise historian so the screen never depends on a WAN link, and send summary data to the central or cloud system for rollup.

Keep reading

  • Selection guide

    Plant historian selection by scale and support needs

    Pick the tier first: a control-room or automation-vendor historian for one site's process trends, an enterprise platform only when several sites share one operational history, and a self-built time-series stack only when your team owns connectors, dashboards, backups and upgrades. Size by stored events per second — the sum of each tag group's tags times its stored events per second — times retention, never by tag count alone.

    Edge computing and IIoT

  • How-to

    Connecting InTouch HMI tags to Wonderware Historian by version

    The installed InTouch release decides the path: on 2020 R2 or newer, configure the Historian connection inside InTouch and enable its store-and-forward; on earlier releases, let Historian's IDAS collector read the running InTouch application. Verify with one stored value before expanding the tag set.

    Edge computing and IIoT

  • Selection guide

    GeoSCADA Data Tables or an external SQL database

    Keep the records in native Data Tables while each retained table stays within the documented 100 MB maximum and writes are infrequent, exporting and trimming what you keep. Move to an external SQL database with ODBC linked tables when growth, business data ownership, or several SCADA systems needing one source of truth dominates, and call that database from client scripts or a separate service, never from logic.