Troubleshooting
Fix SLSping no reply to AVEVA Historian 2023 status tags
Short answer
Historian 2023 still serves status tags to a remote InTouch node over SuiteLink through the legacy Historian I/O Server, so SLSping should answer. Do not copy the 2020 aahiosvrsvc.exe hotfix into a 2023 install. The reported fix was enabling System Monitor Manager, permitting non-encrypted communication as a temporary diagnostic, then rebooting the InTouch client node.
On this page
Historian 2023 still serves status tags to a remote InTouch node over SuiteLink through the legacy Historian I/O Server, and slsping <historian node name> aahiosvrsvc should answer from that client. When it stays silent, leave the 2020 fix behind: copying aahiosvrsvc.exe from a Historian 2020 hotfix into a 2023 installation is not supported, and no 2023 hotfix was identified for this symptom. The fix reported for this exact fault was enabling System Monitor Manager, permitting non-encrypted communication as a temporary diagnostic, then rebooting the InTouch node; reboots before those changes had restored nothing. Test the path in layers from the client, read the SMC logs on both nodes, and change one setting at a time.
Test the path in three layers #
A status tag crosses four things before it reaches the InTouch window: name resolution, the network route, the SuiteLink endpoint that the legacy Historian I/O Server hosts, and the connection settings at both ends. Test them in that order, from the InTouch client, and write down every result:
- Standard ping to the Historian node,
ping <historian node name>, using the same node name the SuiteLink test uses. slsping <machine name> <Communication Driver name>, the documented driver form, which for the Historian I/O Server readsslsping <historian node name> aahiosvrsvc.- The SMC log on both nodes, read while the failure is present.
aahiosvrsvc is the SuiteLink name of the legacy Historian I/O Server. A reply proves the endpoint answers; no reply while ping passes proves the fault sits between the host and that endpoint, which is where every remaining check lives.
What each result tells you #
| From the InTouch client | Meaning | Commit to this next step |
|---|---|---|
| Standard ping fails | Name resolution, routing or access fault | Fix name resolution or the route, then repeat both tests; nothing above this layer matters yet |
| Ping replies, SLSping silent | Host reachable, SuiteLink endpoint not answering | Work the endpoint: service state, firewall, System Monitor Manager, encryption, SMS membership |
| SLSping replies, tag still unavailable | Endpoint healthy | The fault is the tag binding or client configuration, not the connection |
Read the table as a decision, not a menu: only the row that matches your two results gets worked, and everything above it stays fixed. A passing SLSping is not proof the tag is valid, because the command tests the endpoint rather than the binding, so the third row sends you to the tag name and the client log, not back to the network. When the losing end is the client's data connection rather than the status endpoint, start instead with Fix InTouch 2023 Test Connection failure to Historian.
Check the endpoint before changing settings #
Work these in order, because each is a known cause of a silent endpoint and each takes a minute:
- The SuiteLink service is running on the Historian node.
- The firewall allows the port the SuiteLink service listens on between the two nodes.
- Neither node has its network classified as Public, since profile-based rules can block application traffic while ping still passes.
- Where System Management Server manages the nodes, both belong to the same SMS, and the logger shows the connection attempt rather than a silent drop.
Enable System Monitor Manager, then restart the client #
The reported resolution, in order:
- System Monitor Manager was enabled on the affected node; it had not been running.
- Non-encrypted communication was allowed.
- The InTouch node was rebooted, and the status tags returned.
Reboots of both nodes before those changes had restored nothing, so the restart on its own carried no fix; it applied the setting change. The working rule: after enabling System Monitor Manager or changing the encryption setting, restart the InTouch node and retest before concluding anything else.
Allowing non-encrypted communication strips protection from that SuiteLink path, so run it only as an authorized, temporary diagnostic. The permanent state is the encryption configuration your security policy approves on both nodes; if the connection only works with encryption relaxed, that mismatch is the finding, not the fix.
Leave the 2020 hotfix out of 2023 #
A hotfix built for one version is not supported on a newer installation, so the aahiosvrsvc.exe replacement that cleared the symptom under Historian 2020 does not carry into 2023: it can leave mismatched binaries behind and it repairs nothing here. Do not chase the driver changes either. 2023 R2, not the 2023 release, introduced a PCS driver as an additional runtime retrieval path for Historian data, and the legacy I/O Server endpoint it sits beside still answers SuiteLink.
Worked case: SLSping silent after a 2020 to 2023 upgrade #
Inputs, each from the reported case:
- Historian upgraded from 2020 to 2023, version 2023 rather than 2023 R2.
- A remote InTouch node reads Historian status tags; it worked under 2020.
slsping <historian node name> aahiosvrsvcreturns no reply from that client.- Under 2020 the same symptom had been cleared by replacing
aahiosvrsvc.exefrom a hotfix, which is ruled out on 2023.
Rule in words: the read needs name resolution, then host reachability, then a listening endpoint, then compatible settings at both ends. The first failing layer is the fault; one layer changes at a time, and the pair of tests is re-run after each change.
- Standard ping by node name: it passes, so resolution and routing stand.
slsping <machine name> aahiosvrsvc: still no reply, so the endpoint layer holds the fault and the binaries stay untouched.- Endpoint checks: SuiteLink service running, firewall port open, network profile not Public, SMS membership matched.
- Settings: System Monitor Manager enabled, non-encrypted communication permitted for the test, SMC logs read on both nodes for the connection attempt.
- Restart the InTouch node.
Result: after steps 4 and 5 the status tags returned on the client. The restarts tried before step 4 had changed nothing, which is why the order is settings first, restart second.
Decision: ping passing while SLSping stays silent means work the endpoint settings and never the executables. SLSping answering while the tag still reads bad means the binding is the fault, not the connection. Either way, the 2020 hotfix stays out of the 2023 installation.
Confirm the fix holds #
- Retest standard ping and SLSping from the InTouch client; both pass, or the fault is not closed.
- Confirm the tag value updates and that the tag points at the intended Historian status item.
- Read the SMC log on both nodes after the change; the connection attempt should show success with no new failures.
- Confirm firewall and encryption are back at the approved policy, because the relaxed setting was diagnostic only.
- If the no-reply returns, capture the exact SLSping output, the standard ping result and the SMC log from both nodes while the failure is present; those artifacts, not the screen value, carry the next diagnosis.
Once SuiteLink carries values reliably, what the client can read back over it follows its own rules; see Write calculated tags to AVEVA Historian readable via SuiteLink.
Questions asked
Do I still need the aahiosvrsvc.exe hotfix in Historian 2023?
No. Applying a hotfix built for an older version onto a newer installation is not supported, and no 2023 hotfix was identified for this symptom. The 2023 fix is configuration: System Monitor Manager enabled, encryption matched to policy, then a client restart. Keep the 2020 executable out of the 2023 binaries folder.
Does the 2023 R2 PCS driver change how SLSping reaches aahiosvrsvc?
No. The PCS driver arrived in 2023 R2 as an additional runtime retrieval path for Historian data. If you find it while working through settings, that is the R2 addition, not the cause: the legacy Historian I/O Server and its SuiteLink endpoint remain, so it does not explain a no-reply result.
What evidence do I capture if the no-reply comes back?
Capture the exact SLSping output including whether it timed out or errored, the standard ping result from the same client, and the SMC log from both nodes, all while the failure is present. A stale screen value identifies no layer; those artifacts do.
Can non-encrypted SuiteLink stay enabled once the tags work?
No. Treat it as an authorized, temporary diagnostic and restore the encryption your security policy requires on both nodes. If the path only works with encryption relaxed, that mismatch is the finding; the same rule applies to any protocol left unencrypted after a test.