IMD SolutionComputing LibraryShop main store

Troubleshooting

Fixing AVEVA Historian VSS writer 0x800423f4 backup failures

Edge computing and IIoT Published 4 min read

Short answer

Windows VSS error 0x800423f4 means a writer reported a non-retryable error. Identify the failing writer and operation, then check AVEVA knowledge article 000112336 if the Historian storage writer failed on 2023 R2 SP1 P02, P03 or P04. Verify a backup and isolated restore covering the SQL Runtime database and history blocks.

On this page
  1. Identify the writer that rejected the backup operation
  2. Check the installed release against the hotfix record
  3. Verify the backup and its restore
  4. Questions asked

Start with the named writer in the failed backup job. Windows reports 0x800423f4 when a VSS writer returns VSS_E_WRITERERROR_NONRETRYABLE. If the logs name HistorianWriter under aahStorage.exe, check the Historian build and its storage logs before selecting a fix. On AVEVA Historian 2023 R2 SP1 P02, P03 or P04, knowledge article 000112336 is the place to check whether hotfix HF-IMS4497189 applies.

Identify the writer that rejected the backup operation #

  1. Run vssadmin list writers from an elevated Windows prompt as soon as practical after the failure. Record the writer name, instance ID, state and last error, along with the backup job's timestamp. Check every HistorianWriter instance that the job is intended to protect.
  2. Match the job timestamp and writer instance to the Windows Application log. Capture the named operation. In the reported Historian case, the storage writer rejected a Freeze event. The same HRESULT can appear for other VSS writers and other events.
  3. Check the AVEVA Operations Control Management Console logs around the same window. Determine which configured storage location each error affects. Main storage and Auto Summary had separate entries in the reported case. Confirm whether ingestion continued and whether known values reached storage afterward.
  4. Match the backup job's component and volume selections to the configured history locations. The SQL Server writer has a separate result. Its successful freeze and thaw confirm its own participation. Continue checking the Historian writers and the configured backup set.

Microsoft's Writer Errors and Vetoes describes when a backup requester can proceed after a writer veto. A completed job may still report a component exclusion or a fallback mode. Read the component outcome before treating the backup as application-consistent.

If the logs also show a Runtime database query error after an upgrade, trace that SQL request separately and correlate its timestamp before assigning it to the VSS failure.

Check the installed release against the hotfix record #

The public AVEVA discussion identifies HF-IMS4497189 for the regression described in AVEVA knowledge article 000112336. The reported scope is Historian 2023 R2 SP1 P02, P03 and P04. The regression concerns aahStorage.exe hanging while VSS backup is enabled, with warnings in the OCMC log. The error code alone leaves the underlying cause open.

Compare the installed Historian release, service pack and patch label with the current support record. Consult the vendor's directions for the exact build or a later patch. If the hotfix applies, use the AVEVA support package and follow its maintenance, prerequisite and restart instructions. Before the maintenance window, confirm your existing recoverable backups and the plan for data arriving during the interruption.

If the error recurs, retain the backup job status, Windows event details, writer listing, OCMC entries and installed package version. Check for coincident storage or intake errors and verify which components the requester included. The evidence supports troubleshooting for that release and configuration.

Verify the backup and its restore #

Check What to record
Before the job Confirm the relevant writers are present and record their current state. Identify the SQL Runtime backup and the history storage locations in scope.
During and after a controlled job Check the backup product's component report for successful VSS participation by the intended Historian writers. Confirm there was no fallback or omitted component for the intended history data, and verify ingestion resumed.
On an isolated restore system Follow the version-specific AVEVA procedure for restoring the SQL Runtime database and history blocks. Verify tags and representative values on both sides of the backup window using known timestamps. Record the newest recoverable data and the time the restore took.

The AVEVA Historian Server Administrator Guides document separate procedures for the Runtime database and history blocks. The documented VSS-aware path can capture local history blocks while Historian runs. The guide calls for shutting down Historian to restore history blocks and warns against copying the current block without a VSS-aware utility. If an alternate storage location is on a network share, the Historian host's VSS-aware backup does not cover that share. Document how it is protected and test its restore separately.

Questions asked

Does 0x800423f4 identify AVEVA Historian as the cause?

The result identifies a non-retryable VSS writer error. Find the writer name, instance and operation in the failed job and Windows Application log. SQL Server and the Historian storage writer report their outcomes separately.

How can I confirm whether HF-IMS4497189 applies?

Record the installed Historian release, service pack and patch level. Check AVEVA knowledge article 000112336 and the package notes for applicability, prerequisites and any superseding patch. The reported release range is 2023 R2 SP1 P02 through P04.

Does disabling Auto Summary cover a failure in Main storage?

Check the Main writer and its log entries independently. Auto Summary and Main can both report errors. A clean result for one writer leaves the other writer's result to verify.

Can I copy an active history block if the VSS writer fails?

AVEVA directs administrators to use a VSS-aware backup for the current history block. Until consistent coverage is restored, record the gap and use the backup procedure AVEVA supports for the affected configuration.

What should I verify in a restore test?

Follow the matching Historian administration guide on an isolated system. Verify the restored Runtime database, tag definitions and history blocks. Query known values and timestamps across the backup window, including the storage locations and partitions the policy covers.

Corrections

  • : Clarified VSS writer identification, hotfix applicability and restore verification for Historian backups.

Keep reading

  • Troubleshooting

    Citect SCADA connector to Historian shows disconnected

    A "Disconnected" destination status means the Citect SCADA Connector has no session to Historian and is buffering samples to local disk. SMC tag-discovery and write entries prove the connector's stages, not that values were archived. Stop the connector, verify the destination instance, services and write authorization, reconnect once, and close only when a query returns a sample and the buffer drains.

    Edge computing and IIoT

  • Troubleshooting

    Fixing a historian device shortcut that will not appear

    A ping, an open web page and an online programming session prove IP reachability, not a working data path. When the historian drops a device shortcut, the RSLinx Enterprise tree usually holds the gateway interface instead of the controller behind it. Stop browsing and the related services, delete the interface entry, define the SLC 5/03 manually under ENI Devices at the same IP address, point a fresh shortcut at the controller icon, restart, and confirm with a live item read.

    Edge computing and IIoT

  • Troubleshooting

    Historian tagnames showing a ? prefix mean hidden spaces

    A ? prefix on a tagname in an aahDBDump export marks a hidden space-type character in the stored name, not a corrupt tag or lost history. Find every affected tag with a CHARINDEX query on dbo.Tag in the Runtime database, then rename them with the aahTagRename utility (TN Hist235), which preserves history and needs Historian stopped and disabled under store-and-forward protection.

    Edge computing and IIoT