Selection guide
IPC BX-39A as the successor to the IPC 427E
Short answer
The IPC BX-39A is the officially designated successor to the IPC 427E, and the name change reflects a revised Siemens computer naming scheme rather than a missing 427G. Successor status identifies the product to evaluate; acceptance still rests on comparing the machine's order-specific configuration against the successor's datasheet.

On this page
Yes, the IPC BX-39A is the official successor to the IPC 427E: Siemens' delivery release names it as the replacement, and the odd-looking designation reflects a revised naming scheme, not a missing generation. If you maintain a 427E-based station, evaluate the BX-39A now, and approve the swap only after comparing the installed order-specific configuration against the successor's documented data.
Is there an official successor to the IPC 427E? #
Yes. Siemens' delivery release for the SIMATIC IPC BX-39A states that the device, with a new Intel processor architecture, will replace the SIMATIC IPC 427E. The designated successor is therefore the product to evaluate, not a placeholder while waiting for another model.
The confusion is understandable: other members of the Box PC family have already received a generation designation containing "G", so an engineer scanning the catalog expects the next letter in the sequence for this line. Siemens has instead begun revising its computer designations so that size, performance class and intended application are visible in the name. The new designation is that revised scheme in action, not a break in the succession.
Will there be an IPC 427G to wait for? #
No published Siemens product information announces an IPC 427G, so do not plan a migration around one. Where an engineer would commit: treat the designated successor as the successor and start the evaluation now.
The identity of the successor and the existence of a future product are separate questions. A proposed follow-up model becomes a procurement option only when Siemens publishes applicable product information for it. Postponing the assessment of the designated successor because its name breaks the expected letter sequence only delays the replacement project.
Does the similar enclosure shape mean it drops straight in? #
No. Similar geometry is not proof of installation compatibility; successor status and drop-in compatibility are separate decisions. Successor status identifies the product to evaluate, while acceptance rests on the machine's order-specific configuration.
A product-family designation identifies a platform, not every configuration sold under it. The order number on the equipment identification label identifies the purchased configuration: interfaces, memory, storage, operating system and accessories. That number, not the enclosure silhouette, is the starting point for the comparison.
The documented dimensions illustrate why the check matters. The BX-39A base device with two expansion slots measures 262 x 133 x 63 mm (W × H × D), and 262 x 133 x 114 mm in the deeper variant. Compare both against the dimensioned drawing of your installed 427E, including connector positions and cooling clearance, before approving the mounting.
One practical help: Siemens has changed over to new mounting kits for the IPC 427E that also support the designated successor, and only the new kits are marketed. If your 427E carries one of the current kits, the mounting bracket can carry over; an older kit needs replacing with the new one.
Which documented data do I compare against? #
The delivery release and the operating instructions document up to 32 GB RAM, an Intel processor architecture new to this class, and a PCIe x4 expansion slot (mechanical x8) to Revision 4.0 with cards up to 175 mm long. Match each figure against what the installed machine actually uses.
Build the comparison in this order:
- Record the installed configuration of the 427E: order number, operating-system edition and version, application versions, installed drivers, storage arrangement, network settings, interface assignments and any expansion hardware.
- Obtain the configuration documents for the proposed unit from Siemens product documentation and the quotation, so the comparison runs against the order you would actually place.
- Compare physical installation: the dimensions above, mounting kit, orientation, connector positions, cable access and cooling clearances.
- Compare interfaces and electrical supply: every required network, serial or fieldbus connection must have a documented destination on the new device.
- Plan software and licensing: confirm the application supports the new processor generation and operating system, and use only manufacturer-supported installation, restore and license-transfer procedures.
- Classify each difference as compatible, requiring an engineered change, or blocking acceptance. A missing interface is a design issue, not something to bridge with an unverified adapter.
The front-panel LEDs help at commissioning: the new box has four, Power, Run/Stop, Error and Maintenance, and their states are documented in the manual. Where a software controller will run on it, the installed Windows 11 build can matter; the write-up on why the S7-1508S V31.1 won't install on this box PC under Windows 11 covers that case.
How do I prove the replacement before the machine runs on it? #
Test in a maintenance window or on a representative bench setup, and treat a successful boot as proof of nothing more than the computer starting. The acceptance record is what stands behind the swap.
Run four checks:
- Hardware inventory: delivered processor, memory (up to 32 GB is the documented maximum, not the shipped amount), storage and interfaces match the approved order.
- Operating system and drivers: required devices recognized, drivers loaded, no unresolved device errors.
- Communication: each connection to controllers and supervisory systems reaches its peer and carries live data without persistent faults.
- Application: normal startup, representative workload, shutdown and restart, with licenses valid and configuration persisting.
Back up projects, configuration files and recoverable system data first, and keep a recovery path that does not depend on the new computer booting. The same configuration-matching discipline applies when choosing a box PC replacement for hardware-bound software, and the broader hardware decision for a legacy system is covered in picking replacement IPC hardware for PCS 7 V6.0 on Windows 2000.
What is the decision for each case? #
Commit to the designated successor, and let the configuration comparison decide the rest.
| Case | Decision |
|---|---|
| Standard 427E installation, current mounting kit, supported OS | Approve the replacement; the new kit carries over and the interfaces compare cleanly |
| 427E with expansion card | Verify card length against the 175 mm PCIe limit and the Revision 4.0 slot before approving |
| Application tied to a specific OS build or driver | Treat as an engineered change: confirm support on the new platform before ordering |
| Waiting for an IPC 427G | Do not wait; no such product is published and the BX-39A is the designated replacement |
Where the comparison closes and the unit is being specified as a compact box computer in the cabinet, choose it as an industrial mini PC class of device from the hardware range.
Questions asked
Will there be an IPC 427G?
No published information announces an IPC 427G. Siemens revised its computer designations so that size, performance class and intended use show in the name, which is why the 427E's successor carries the BX-39A designation instead of an incremented generation letter.
How much RAM does the IPC BX-39A support?
The delivery release for the designated successor documents up to 32 GB RAM. Verify the actually ordered memory against the datasheet for your order number, because the supported maximum is not the amount every configuration ships with.
Is the IPC BX-39A larger than the IPC 427E?
With two expansion slots fitted, the base device measures 262 x 133 x 63 mm, or 262 x 133 x 114 mm in the deeper variant. Compare these figures with the dimensioned drawings of your installed 427E before assuming the similar enclosure shape means identical mounting.
What should I record from the old IPC 427E before ordering?
Record the order number from the equipment label, the operating-system edition and version, application versions, drivers, storage layout, network settings and any expansion hardware added after delivery. The order number identifies the purchased configuration and is the starting point for the datasheet comparison.