How-to
Migrating WinCC 7.0 SP3 to 7.5: the two-hop path
Short answer
A WinCC 7.0 SP3 project cannot be migrated straight to 7.5: the 7.5 migrator does not accept that source version. It goes to 7.3 first, then to 7.5, and because 7.3 is discontinued its installation media comes from a support request with the vendor's Technical Support. Run both hops on a copy and keep the original project and the old IPC as the rollback.
On this page
- Why 7.5 refuses 7.0 SP3 as a source
- Inventory the installed software
- Request the discontinued 7.3 media
- Back up the project and freeze the original
- Run the first hop from 7.0 SP3 to 7.3
- Prepare the replacement and move the licenses
- Run the second hop and verify end to end
- The decision for each case
- Questions asked
A WinCC 7.0 SP3 project reaches version 7.5 in two hops, not one: 7.0 SP3 to 7.3, then 7.3 to 7.5. The project migrator built into 7.5 does not accept 7.0 SP3 as a source, the 7.3 migrator does accept 7.0 SP3, and the 7.5 migrator accepts 7.3. The catch is that WinCC 7.3 is discontinued, so its installation media comes through a support request with Siemens Technical Support instead of a normal download. The sequence below runs every hop on a copy of the project, leaves the production original untouched as the rollback image, and ends with a verified 7.5 runtime on the replacement machine, an IPC547J in the example followed here.
Why 7.5 refuses 7.0 SP3 as a source #
Each WinCC V7 release changes the project database structure and runtime components, so the migrator of a given release accepts only defined source versions. The Siemens migration documentation for 7.3 lists 7.0 SP3 as an accepted source; the documentation for 7.5 lists 7.3, not 7.0 SP3. Migration is also a one-way conversion: it rewrites the project, and no path leads back from 7.5 to 7.0.
| Hop | Source project | Target | Accepted-source basis |
|---|---|---|---|
| 1 | WinCC 7.0 SP3 | WinCC 7.3 | 7.3 migration documentation lists 7.0 SP3 |
| 2 | WinCC 7.3 | WinCC 7.5 | 7.5 migration documentation lists 7.3 |
Read both statements against the exact service-pack and update level in your inventory. If the installed 7.0 SP3 level is not accepted as it stands, install the required update on the old IPC first; the hop itself does not change.
Inventory the installed software #
The replacement has to reproduce every option, driver and add-on, so record them before any media is requested.
- Open the "Installed software" shortcut in the Start menu if the IPC image has one. Otherwise open Programs and Features (
appwiz.cpl); every installed component and its version is listed there. - On an operating system that has PowerShell, export the list instead of transcribing it.
C:\inventory.csvis an example output path; pick your own.
Get-ItemProperty HKLM:\Software\Microsoft\Windows\CurrentVersion\Uninstall\*, HKLM:\Software\Wow6432Node\Microsoft\Windows\CurrentVersion\Uninstall\* | Where-Object DisplayName | Select-Object DisplayName, DisplayVersion, Publisher | Sort-Object DisplayName | Export-Csv C:\inventory.csv -NoTypeInformation
DisplayName, DisplayVersion and Publisher are the registry property names the uninstall entries carry; the two Uninstall keys cover the 64-bit and 32-bit installer records.
- On an OS without PowerShell, screenshot Programs and Features sorted by name.
Check: the WinCC entry reads at the 7.0 SP3 level, every WinCC option, communication channel and other Siemens package the project depends on is present, and no entry is missing its version string. That list is the bill of materials for the whole migration.
Request the discontinued 7.3 media #
- Open a support request with Siemens Technical Support for the WinCC 7.3 installation media, stating it is needed as a migration hop from 7.0 SP3 toward 7.5.
- Attach the inventory, the installed version and service-pack level, the target hardware (an IPC547J here), the final target version 7.5, and the license situation, so support can confirm the hop is covered.
- While the request is open, read the 7.3 release notes for the operating systems it supports and compare them with the OS planned for the replacement. If 7.3 does not support that OS, the first hop runs on a separate staging machine whose OS it does support, and only the migrated project folder moves to the replacement.
Check: the received media identifies itself as WinCC 7.3 and offers every option the inventory lists.
Back up the project and freeze the original #
- Close WinCC on the old IPC.
- Copy the entire project folder, archives included, to external storage.
That copy is the rollback image and is never opened by a newer WinCC. Migration happens to working copies only: the migrator rewrites whatever project it is pointed at, and there is no downgrade back to 7.0.
Run the first hop from 7.0 SP3 to 7.3 #
- Install WinCC 7.3 and the inventoried options on the staging machine.
- Copy the project there and run the project migration on that copy.
- Open the migrated project, recompile it and read the migration log.
Check: the project opens in the 7.3 editor; tag count, picture count and archive configuration match the 7.0 SP3 original; the compile finishes without errors; every logged warning maps to a known feature change, not to a missing object or driver. Anything missing is fixed here, on the staging machine; it will not improve in the second hop.
Prepare the replacement and move the licenses #
- Install WinCC 7.5 on the replacement machine, when the old unit is being retired rather than repaired that can be an industrial box PC taking over the old IPC's place in the cabinet, with the same option set the inventory recorded.
- Move the licenses before the old drive is wiped or the machine scrapped: WinCC licenses are held on a storage drive and managed with the Automation License Manager, so transfer them from the old IPC to the replacement while both still exist.
- Read the license terms for the 7.5 target to confirm the existing licenses cover it, and ask Technical Support whether an upgrade license is required.
Check: the Automation License Manager on the replacement lists every required WinCC license on its local drive.
Run the second hop and verify end to end #
Copy the migrated 7.3 project to the replacement, a copy again, with the 7.3 original kept with the rollback material, and run the migration to 7.5. Then verify, in this order:
- Software parity. Export Programs and Features on the replacement with the same command, to
C:\inventory-new.csvfor example, and compare it with the old export. Worked example with illustrative numbers: the old file has 58 rows, of which 49 carry other publishers and 9 carry the vendor's name (58 - 49 = 9): the WinCC entry, two options and six communication channels. The replacement, filtered the same way, must also return 9 rows, each at the 7.5 level; 8 rows means one channel was never installed. - Project integrity. Open the 7.5 project and compile: zero errors, and object counts equal to the original. If the 7.0 SP3 project had 1,240 tags and 96 pictures, the migrated project shows 1,240 tags and 96 pictures.
- Licensing. Start runtime: no license warning, no restricted-mode banner.
- Controller connectivity. Run this with the process in a safe state, because a migrated runtime driving live outputs for the first time is a commissioning test, not a software check. Every channel must show good quality and its values must match the controller or a reference instrument.
- Archiving. Let runtime log through a full archive cycle and confirm new alarm and tag-log entries are written and readable in the trend and alarm controls. Whether those runtime archives should later feed a central historian is a separate design question, covered in WinCC runtime archives versus a central process historian.
- Rollback readiness. The untouched 7.0 SP3 copy and the old drive stay available until the plant has run a full production cycle on the replacement, and the old IPC can still start its original runtime if the cutover is reversed.
The decision for each case #
- 7.3 supports the replacement's operating system: run both hops on the replacement itself, in order, on copies.
- 7.3 does not support it: run the first hop on a staging machine with a supported OS and move only the migrated project folder to the replacement for the second hop.
- The 7.3 media is delayed and the project is small: rebuilding it by hand in 7.5 is a valid alternative, but it is a new project with full commissioning and its own validation, not a migration; choose it only when everything in the project can be rebuilt and tested faster than the support request takes.
- Every case: migrate copies only, move the licenses before the old drive leaves your hands, and keep the original project plus the old IPC through one full production cycle.
Questions asked
Can the migrated 7.5 project move into TIA Portal later?
Not with current tooling: the TIA Portal V20 migration documentation, published 11/2024, states that migrating projects from WinCC V7 is not supported. A project that must end in TIA Portal needs an older TIA Portal release that still offers WinCC V7 migration, followed by an upgrade inside TIA Portal. Plan on WinCC 7.5 as the long-term platform unless that extra path is justified.
Can the 7.3 hop run in a virtual machine?
Yes, provided the guest operating system is one the 7.3 release notes list as supported. The first hop converts project data and needs no process connection, so a virtual machine on spare engineering hardware works as the staging machine. Keep it until the 7.5 project is verified, then archive the migrated 7.3 project folder together with the rollback image.
Does the temporary 7.3 installation need its own license?
Settle that in the same support request: state that 7.3 will be installed only to convert the project, and ask Technical Support to confirm in writing whether the existing licenses cover that use or an upgrade license is required. An answer before the media arrives prevents a halted cutover over licensing.
Can computer names or tag names change during the migration?
Keep the migration a pure version change: same project name, computer name and tag names. A rename during migration adds a second possible cause to every fault found afterwards. If the replacement must carry a new computer name, apply it as a separate step after the 7.5 project runs clean, and test it alone.