Troubleshooting
MQTT Transmission connected but missing from the node list
Short answer
A connected badge only certifies the broker session; the gateway node list fills from the node's birth message and subscriptions. The compatibility matrix lists module 4.0.13 as supported on Ignition 8.1.21, so the fault sits in subscription behavior or MQTT Server ACLs. Read three logs from one attempt, repair the specific grants, and roll the new edge back to Ignition 8.1.18 with module 4.0.8 if production waits.
On this page
- Why does an edge that shows connected never reach the node list?
- Can MQTT Transmission 4.0.13 run on Ignition 8.1.21?
- What actually changed between modules 4.0.8 and 4.0.13?
- How do I catch the failure in one connection attempt?
- Do MQTT server ACLs block a 4.0.13 edge?
- Can I upgrade the gateway's MQTT Engine to 4.0.13 alone?
- What is the fastest way back if the line is waiting?
- What is the fix for each case?
- Questions asked
A new edge running MQTT Transmission 4.0.13 that shows connected but never lands in the gateway's node list is not fighting a version incompatibility: the module vendor's compatibility matrix lists 4.0.13 as supported on the Ignition releases in this upgrade, including 8.1.21. The fault sits in the steps after the connection — the subscriptions and the node birth message that actually populate MQTT Engine's list — and the module vendor's support specifically flagged changed subscription behavior and MQTT Server ACLs as the place to look. Capture gateway, edge and broker logs for one connection attempt, compare them against a working edge, and repair the specific grant or subscription the logs show failing. If production is waiting, the tested way back is rolling the new edge to Ignition 8.1.18 with module 4.0.8, the pairing the reported upgrade run proved out.
Why does an edge that shows connected never reach the node list? #
Because the connected badge only certifies the broker session: MQTT Engine builds its node list from the edge node's birth message and the subscriptions behind it, so an edge that stops between CONNACK and that birth stays invisible while every status light on the edge stays green.
An MQTT connection and a registered node are two different milestones. The Transmission module can hold a healthy session, keep its store-and-forward queue intact, and still never deliver the birth certificate that tells MQTT Engine a node exists. Judge an upgrade by the node list, not by the connection badge — and remember the reverse fault, where a dead node lingers as online on stale state, covered in why MQTT Engine shows online status after an edge node drops.
Can MQTT Transmission 4.0.13 run on Ignition 8.1.21? #
Yes: the vendor's published compatibility matrix lists the 4.0.13 Cirrus Link modules as supported on the Ignition releases in this upgrade, including 8.1.21 and 8.1.19, so the version pair on the failing edge is not your root cause.
Read the matrix as the preflight check it is: it clears a pairing for install, and it does not certify every mixed-version topology in the field. The reported run shows the gap — the gateway sat on Ignition 8.1.19 with modules at 4.0.8, and its older edges on 8.1.7 with 4.0.8 kept working after the gateway upgrade, so the gateway's Ignition release alone broke nothing. The variables that changed for the new node were both of the edge's versions at once: Ignition 8.1.21 with Transmission 4.0.13.
What actually changed between modules 4.0.8 and 4.0.13? #
Subscription handling changed between those module releases, and that is where one real upgrade run broke: a new edge on Ignition 8.1.21 with Transmission 4.0.13 reported connected yet never appeared in the gateway's node list, while the older edges kept working.
The vendor's support reply on this exact symptom named two suspects — subscription behavior differences between 4.0.8 and 4.0.13, and MQTT Server ACLs — and both stay hypotheses until your own logs confirm one. What the run did establish is a table of tested combinations you can reuse:
| Gateway (Ignition / modules) | Edge side (Ignition / Transmission) | Reported result |
|---|---|---|
| 8.1.7 / 4.0.8 | 8.1.7 / 4.0.8 | Normal communications |
| 8.1.19 / 4.0.8 | existing edges on 8.1.7 / 4.0.8 | Older edges kept working |
| 8.1.19 / 4.0.8 | 8.1.21 / 4.0.13 | Connected, absent from the node list |
| 8.1.19 / 4.0.8 | 8.1.21 / 4.0.8 | No connection to MQTT Engine at all |
| 8.1.19 / 4.0.8 | 8.1.18 / 4.0.8 | Normal communications restored |
These are one plant's reported symptoms, not vendor test data, and no row ever ran the gateway's modules at 4.0.13 — keep that in mind when you plan the gateway upgrade.
How do I catch the failure in one connection attempt? #
Capture three logs for one attempt — gateway, edge and MQTT broker — and line them up by timestamp: a healthy edge walks four broker steps, CONNECT, CONNACK, SUBSCRIBE, then the birth PUBLISH, and the failing edge's last completed step names the layer that drops it.
Collect before you change anything:
- The gateway's log lines and MQTT Engine lines around the attempt window.
- The edge's Transmission log lines for the same window, with its client ID.
- The broker's connect, subscribe, publish-deny and ACL lines for that client ID.
- The namespace string and node name the edge publishes under.
Worked example, with example timestamps on three NTP-synchronized hosts agreeing within one second: the working edge logs CONNECT at 14:02:05, SUBSCRIBE at 14:02:05 and its birth PUBLISH at 14:02:06 — 4 of 4 steps in one second. The failing edge logs CONNECT and CONNACK at 14:02:31, then nothing: 0 SUBSCRIBE packets and 0 birth publishes from that client ID at the broker, which is 2 of 4 steps. The missing steps 3 and 4 put the cut between session acceptance and subscription — an authorization or subscription-format problem at the broker or its ACLs, not a network fault and not a version-pair fault. If the hosts' clocks drift, add the measured offset before comparing.
Reading the broker side first saves the most time: the page on troubleshooting MQTT broker connect errors in gateway logs covers the connect-stage lines you will be comparing against.
Do MQTT server ACLs block a 4.0.13 edge? #
They can, and the module vendor specifically flagged MQTT Server ACLs as the suspect for this symptom: check that the edge's user holds subscribe rights on the namespace the gateway reads and publish rights on that node's own birth and data topics.
Compare the new edge's grants line by line with a working edge's: same user pattern, same namespace, same subscribe and publish permissions. A grant set tuned to 4.0.8 behavior can quietly deny a 4.0.13 edge, because the newer module may subscribe or publish topic patterns the old grants never covered, and a denied subscribe looks from the edge like a network drop — connected, yet deaf. Birth and data messages ride different topic patterns, and a consumer can accept one while dropping the other, the same split seen when an MQTT collector logs DBIRTH but ignores DDATA. One caution: never clear the symptom by widening the ACL to allow-all on the OT namespace, because that hands every client publish rights to plant topics — grant the specific patterns the edge actually needs.
Can I upgrade the gateway's MQTT Engine to 4.0.13 alone? #
Not alone: the vendor's install guidance requires every Cirrus Link module inside one Ignition install to carry the same version number, so MQTT Engine and MQTT Transmission on that gateway must move to 4.0.13 together.
The vendor documents the reason separately: mismatched module versions can cause class-loading faults that destabilize the install. No documented rule ties an edge's module version to the gateway's, so the 4.0.8 edges need not jump in the same window. The reported run never tested a 4.0.13 gateway against a 4.0.8 edge, though, so treat that cross-station pairing as unproven: bench one gateway at 4.0.13 with one edge at 4.0.8, confirm connect, birth and live values, and only then touch the production gateway. If the bench fails, the upgrade window takes the edges with it — which is how the reported site eventually landed.
What is the fastest way back if the line is waiting? #
Roll the new edge back to the pairing the reported run proved out: Ignition 8.1.18 with MQTT Transmission 4.0.8 restored normal communications, after which the edge reappeared in the gateway node list; do it in a maintenance window, because the reinstall restarts the module's session.
Roll both versions together. The same run tried module 4.0.8 alone on the edge's original Ignition 8.1.21 and could not connect at all, so downgrading the module without the platform is not a recovery path. After the rollback, confirm three things before calling it fixed: the edge reconnects, the node appears in MQTT Engine's list, and live values arrive at the gateway. Keep the log capture from the failed attempt — it is the evidence that makes the 4.0.13 path work on the next try.
What is the fix for each case? #
Fix order: confirm the pairing against the compatibility matrix, capture the three logs, read the missing step, repair the ACL grant or subscription it names, and if production waits, roll the new edge back to Ignition 8.1.18 with Transmission 4.0.8 until a bench proves the 4.0.13 path.
By case:
- New edge on Transmission 4.0.13, connected but absent from the node list: the pairing is supported, so stay on it and diagnose — broker logs first, then ACL grants against a working edge.
- Edge on Transmission 4.0.8 that cannot connect at all: leave that pairing behind — take the tested rollback pairing or move forward to 4.0.13, whichever your bench proves.
- Gateway upgrade planned: move MQTT Engine and MQTT Transmission to 4.0.13 together, bench the new gateway against one old edge, and fold the edges into the window if the bench fails.
- Long term: land every station on one consistent Ignition and module set — the reported site's final state, working from then on, with every mixed-version variable removed.
Questions asked
Where is the compatibility matrix for the Cirrus Link MQTT modules?
The module vendor publishes the matrix and the per-release notes with the module downloads, reached from the Ignition third-party modules download page for your exact Ignition version. Read it before every mixed-version change: it is the reference that clears module 4.0.13 on the Ignition releases in this upgrade, and it is updated as new gateway and module releases come out.
Why must both MQTT modules on one gateway share a version?
Because the vendor's install guidance states that all Cirrus Link modules inside one Ignition install must be at the same version, and mismatches can cause class-loading problems that destabilize the system. The rule binds the modules within each station to each other, not your edges to the gateway.
How do I order the upgrades across a multi-edge site?
Move the gateway's two modules together first, bench one edge against the new gateway while the rest stay in production, then advance the edges in small batches, checking node registration and live values after each batch. Keep a written table of every station's working pairing; it turns the next upgrade from a symptom hunt into a checklist.
What should go into a support ticket for this symptom?
Gateway and MQTT Engine logs, the edge's Transmission logs, and broker logs from one timestamped connection attempt, plus the exact Ignition and module versions on every station, the edge's client ID, its namespace and node name, and the MQTT Server ACL grants for the edge's user. The vendor's support asked for logs at exactly this scope to close subscription-level faults quickly.
Did the reported site finish on one version everywhere?
Yes. After the failed mixed attempts, every station moved to one consistent, newer Ignition and module set, and communications worked from then on. That proves a uniform deployment clears the symptom, but it does not isolate which single grant or subscription caused the trouble, so keep your log capture before you mass-upgrade.