Short answer

PI Connector for PI System Health discovers only the PI services installed on its own machine, so a split PI Data Archive and PI AF Server arrangement needs one connector on each server. Excel is not required. Open TCP 5457 from the Data Archive node to the AF Server node so the connector can write its health elements.

On this page
  1. Why the connector only sees its own machine
  2. Where the connector goes, service by service
  3. What the connector host needs
  4. The Excel message during installation
  5. Ports when the servers are split
  6. Working the split-server case: one Data Archive node, one AF Server node
  7. Tracing a health value that never appears
  8. Questions asked

Install PI Connector for PI System Health on each server whose PI services you want monitored. With PI Data Archive on one machine and PI AF Server on another, that means one connector per machine: the connector discovers services by querying the local machine registry, so a copy on your workstation discovers none of the server software. Excel is not a requirement anywhere in this deployment. The only network change the split arrangement adds is TCP port 5457 open from the Data Archive node to the AF Server node, the path the connector uses to write its health elements into PI AF. This article sets out the placement rule per service, the host prerequisites, the Excel message that appears during a non-elevated install, the port rule, and a trace for a health value that never appears.

Why the connector only sees its own machine #

The connector archives health information for the local PI system in three areas: PI AF Server, PI Data Archive and PI Analysis Service. To find them, it queries the local machine registry and checks whether each one is correctly installed. Registry presence is discovery. Only discovered services can be selected for monitoring, and only selected services get their PI AF elements and assets. The connector framework also documents a PI AF element for each connector instance itself, holding that instance's configuration and status.

Keep discovery separate from communication. Local discovery decides what the connector can monitor at all; network connections decide whether it can reach PI Data Archive and PI AF to write results. A working connection to a remote server never makes that server's installed services local to the connector. The same split between producing data locally and reaching a destination runs through edge designs — why an edge gateway needs an HTTP endpoint to write a database makes the same point one step removed — and here it means a green network test proves nothing about discovery.

Two different faults therefore produce an incomplete health display: a service the connector never discovered, or a service it discovered but cannot write about. The trace at the end of this article separates the two.

Where the connector goes, service by service #

Choose the install location by the service you must monitor, not by where Excel lives or where administration normally happens.

You need health for Install the connector on That install cannot see
PI Data Archive on its own node The Data Archive node AF Server or Analysis Service on other nodes
PI AF Server, with Analysis Service on the same node The AF Server node The Data Archive on its other node
Both servers in a split arrangement Each node, two installs Nothing, between the two
OPC interfaces sending data to the Data Archive Nothing extra: the Data Archive node's connector watches the local Network Manager Interfaces feeding a different Data Archive node
The PI software on your workstation Nowhere: a client node is the wrong home for this connector Everything on the servers

The registry rule also fixes the count: several supported services on one machine all fall under that machine's single connector, so you size the deployment by hosts holding services, not by product names.

What the connector host needs #

For the release line in the reported case, PI Connector for PI System Health version 1.0.1.13, the software requirements list a 64-bit Microsoft Windows node — server class Windows Server 2008 SP2 or later in that historical list — with minimums of PI Data Archive 2015 (3.4.x) or later, PI Asset Framework Server 2015 (2.7.0) or later and PI Asset Framework Client 2015 R2 (2.7.5) or later on their respective nodes. The PI Connector Administration Site runs in an HTML5-capable browser; the same historical list names Internet Explorer 10 and 11, Chrome 44 or later and Firefox 39 or later, desktop mode. Those entries record what that release era required, not a recommendation for a new build.

The Excel message during installation #

In the reported installation, a first pass that was not run elevated showed a message saying one feature would not work without Excel. An uninstall followed by a reinstall with administrator privileges made the message disappear, and the reinstall then completed cleanly. Excel is not a connector prerequisite, so the common IT preference to keep Office off monitored servers costs nothing here: never install Excel to satisfy an installer warning.

Work an appearance of the message in this order:

  1. Record the exact installer version, the message text and the feature it names.
  2. Confirm the installation package came from the manufacturer or an authorized distributor.
  3. Use the vendor's documented uninstall procedure, then reinstall with administrator privileges.
  4. Reopen the PI Connector Administration Site and confirm the local services are discovered.
  5. If the message returns after an elevated reinstall, take the named feature and the installer logs to the vendor's support channel rather than adding Excel.

Ports when the servers are split #

After discovery, the connector writes health elements into PI AF. When PI Data Archive and PI AF Server share a node, that write stays local. When they are split, vendor guidance for this connector is to open TCP port 5457 from the Data Archive node to the AF Server node; the connector installed on the AF node writes to its own AF Server locally. A split arrangement therefore adds exactly one cross-network rule per Data Archive node, and scoping it to those two nodes keeps the opening narrow.

Interface monitoring adds nothing in the other direction. An OPC interface node receives no connector install and no port opened toward it: the connector on the Data Archive node watches the Network Manager running locally on that node, and interface health arrives there on its own. Nothing reaches out to the interface itself.

If the connector reports it cannot reach the AF Server, check the account before the firewall. The vendor's connection guidance is to verify the domain and account name entry format first, then work through the firewall and port considerations, where the split-server rule from the first paragraph sits.

Working the split-server case: one Data Archive node, one AF Server node #

Inputs, as reported: PI Data Archive runs on one node, called DA1 here, while PI AF Server and PI Analysis Service run on a second node, AF1; OPC interfaces send their data to DA1. The connector is PI Connector for PI System Health version 1.0.1.13. The rule, from the connector documentation: a connector discovers only services correctly installed on its own machine, through that machine's registry. The write path: each connector sends its health elements to the AF Server, which needs TCP 5457 open across the network when the AF Server sits on another node.

The arithmetic:

  • Connectors to install = nodes holding a monitored service = 2: DA1 holds the Data Archive, AF1 holds the AF Server and the Analysis Service, so one install on each.
  • New cross-network firewall rules = writes leaving their own node = 1: DA1 to AF1 on the AF write port. The AF1 connector writes locally and adds 0.
  • Interface node changes = 0 installs and 0 ports opened toward the PCN, because interface health is read from the Network Manager on DA1.
  • Workstation installs = 0, because a desktop registry lists none of the server services.

Result: 2 connector installs, 1 new firewall rule, 0 changes on interface nodes or desktops.

Decision: install the connector on DA1 and on AF1 and open the AF write port from DA1 toward AF1; change nothing on the interface node or the workstation. The threshold to carry to any PI System: a node that runs a service you must monitor and has no connector stays unmonitored, so every such node gets an install.

Tracing a health value that never appears #

Work from the missing element back to the service:

  1. Compare the connector's hostname with the hostname running the missing service. Different names mean discovery never happened; no configuration recovers a service the connector's own registry never listed, so add a connector on that service's node.
  2. Check the local installation of the service on the connector node. Discovery needs a correctly installed service, and a broken install or registration hides it from the registry query.
  3. Check the monitored-service selection in the PI Connector Administration Site. A discovered but unselected service creates no elements or assets.
  4. Check the write path. Confirm the connector instance's own configuration and status element appears in PI AF, enter the domain and account name in the correct format, and on a split arrangement confirm the AF write port is reachable from the connector node.
  5. Confirm one known value end to end: a health message you recognize, with its timestamp, for a Data Archive the documented message list covers — that list runs from PI Server 2010 onward.

If an element exists but its values stall, the fault is in the write path, not discovery. Changing a display binding cannot fix a service the connector never discovered.

Questions asked

What changes if PI Analysis Service runs on its own third server?

Treat every host holding a service you must monitor the same way: discovery is per machine, so that third machine needs its own connector for its health to reach PI AF. A connector on the AF Server node sees only what is installed on that node. Count connectors by hosts, not by product names, because several services on one machine still fall under that machine's single connector.

Do administrator rights matter only during installation?

They are an installation operation: the installer registers components and writes protected configuration, which is why the non-elevated install in the reported case behaved differently. The account the connector uses at runtime is a separate matter that the release documentation governs. Run the installer elevated once, then configure runtime accounts and monitoring per that release instead of carrying installation privileges into daily operation.

The connector is already on a desktop. What is the clean way to fix the placement?

Uninstall it from the desktop using the vendor's documented uninstall procedure, then install one connector on each server that holds a service you must monitor. Reopen the PI Connector Administration Site on each server and confirm the local services are discovered before selecting monitoring. Nothing configured on the desktop copy recovers the servers' services, because its registry never listed them.

How large does a connector host need to be?

The connector administration documentation lists, for the machine PI Connector Relay is installed on, a dual-core or greater processor, 8 GB or greater RAM and 50 GB of disk space. If the deployment adds a Relay node, size it to at least that. Placement follows services and registry discovery, so host sizing never changes which machine a connector belongs on.

Keep reading

  • Explainer

    Connecting Node-RED and FUXA on one edge server

    Running Node-RED and FUXA on one edge server does not share tags between them; the documented paths are OPC UA and MQTT. Use OPC UA when a side must browse the other's tags and carry typed PLC data both ways, MQTT JSON for event publishing and command topics, and set the publishing intervals from a measured staleness budget rather than switching protocol for speed.

    Edge computing and IIoT

  • Explainer

    Do you need a historian or just an OPC tag server?

    No. An OPC tag server (OPC DA) supplies the current value, quality and timestamp of each item and stores nothing, so monthly figures need a historian or a SQL logger collecting from that same server. Keep a reporting client like ActiveFactory only if you also run the historian it expects.

    Edge computing and IIoT

  • How-to

    Reusing Ignition edge tag structures on a central gateway

    Yes. Rebuild the edge UDTs as reference tags in a realtime provider at the central gateway so copied windows resolve unchanged, cluster the four brokers into two pairs, publish the regional and backup streams under distinct Edge Node IDs, and let the national UDT select the healthy source per tag.

    Edge computing and IIoT

SQL Server 2022 setup for System Platform 2023 R2 SP1