Troubleshooting
Process History cursor one hour off: check DST and hotfix
Short answer
A Process History cursor that lands an hour off the click is a workstation time-conversion fault, not lost history: the archive stores UTC and the console converts it for display. Confirm the displacement is exactly one hour on every workstation fed by the EWS time master, align time zone and daylight-saving settings with it, then apply the vendor's current workstation hotfix. Expect the fault to open or close at daylight-saving transitions, and never repair it by moving the historian server's clock.
On this page
When an operator opens a Process History View trend, clicks it, and the vertical cursor lands an hour after the click while the timestamp below the trend still reads true, the archive is not at fault. DeltaV stores history in UTC, and each workstation converts that stored time for display using its own time and date settings, daylight-saving behavior included. When the cursor mapping and the timestamp readout apply the daylight-saving term differently, the pair disagrees by exactly one hour on every workstation that shares the settings, and the disagreement opens or closes with the DST calendar, as the reported case did. Confirm the scope, align time zone and DST settings with the EWS time master, then apply the current workstation hotfix for your DeltaV release. Leave the historian server's clock alone: changing it re-labels how past data reads.
What the cursor and the timestamp are telling you #
The reported case showed two behaviors, and their combination is the signature of a display-conversion fault rather than bad data:
| What the operator does | What happens | What it points to |
|---|---|---|
| Clicks an empty part of the trend | Cursor line appears about an hour after the click; the timestamp below matches the click | The cursor is drawn through a different time conversion than the readout |
| Clicks the plotted line itself | Cursor lands on the click; the timestamp reads an hour less | The same two conversions crossed the other way |
| Checks the tag value elsewhere | The value tracks the process | Stored history and tag are healthy; keep the investigation console-side |
Whichever readout you trust, the pair contradicts itself, the contradiction spans exactly the daylight-saving shift, and the plotted line still sits at the correct wall-clock position. A historian or controller fault would move the line itself, and then cursor and timestamp would agree with each other about the wrong point. That split is what keeps this fault on the workstation side and the stored history out of scope.
Scope the fault before changing anything #
- Capture both behaviors on one workstation before touching any setting: the tag, the date range, the click position, where the cursor line lands, and the timestamp shown below the trend.
- Repeat the same clicks on every operator workstation. In the reported case all stations showed it, and all took their time from the EWS acting as the network's time master — a shared-configuration fault, not one bad bench machine.
- Check the plotted line against an independent view of the same tag. If values are missing rather than misplaced, that is a different fault, and fixing a DeltaV embedded trend that shows no PI history is the article for that symptom.
- Skip the reboot round: the historian machine, the engineering workstation and the OPC machine were all restarted in the reported case without effect, because nothing in volatile memory held the wrong conversion.
- Write down the calendar date and the DST state at first sighting. Behavior that begins or ends at a daylight-saving boundary is the strongest single clue this fault gives you.
Why the offset matches the daylight-saving hour #
History is stored in UTC; the console shows it in local time. Every displayed moment is computed as the stored UTC time plus the workstation's zone offset plus the DST shift when DST is in force. The cursor line and the timestamp readout are two consumers of that conversion, and the fault appears when they apply the DST term differently: one readout adds the shift, the other does not, and the gap equals the DST shift itself — the hour the calendar adds in spring and removes in autumn.
That arithmetic explains the reported chronology. All workstations took their time from the EWS, the EWS itself was set to adjust for daylight saving automatically, and the fault nevertheless cleared at the autumn transition: once the calendar left summer time, the shifted and unshifted conversions landed on the same wall-clock reading and the symptom disappeared on its own. The clearing proves the DST link; it is not a repair, and the wrong hour stays in the console settings or software until you align them and apply the hotfix.
The display side is only one of the places DST bites. When a real value reads hours off rather than a cursor, work the storage-side offset instead: checking the UTC offset when a historian shows a real value hours off. The transition itself also creates a duplicated hour in stored data, which is a retention question covered by what a historian keeps when it repeats 1 am after fall back. And wherever a plant device keeps its own calendar, the same three settings decide the shift — a UTC base, a signed offset and a DST enable flag — as walked through in configuring a controller calendar's DST flags against a UTC base.
Worked example: a 13:00 UTC sample on a UTC+1 plant in summer #
Illustrative example with round numbers, not a measured result. Inputs: a sample stored at 13:00 UTC, the archive's storage base; a plant on UTC+1 standard time with summer time in force, so the correct local offset is UTC+2; and the displacement reported between cursor and timestamp, one hour.
The rule in words: the console's displayed time is the stored UTC time plus the zone offset plus the DST shift when the conversion applies it, and the cursor and the timestamp must run the same conversion for the pair to agree.
Arithmetic: correct display 13:00 + 2 h = 15:00. A conversion that misses the DST term gives 13:00 + 1 h = 14:00. Disagreement between the two readouts: 15:00 − 14:00 = 1 h, exactly the displacement reported, independent of which tag is on the trend.
Result: a full DST hour of cursor-versus-timestamp contradiction, identical on every workstation sharing the zone settings, opening at the spring change and closing at the autumn one.
Decision: a mismatch that equals the DST shift, appears plant-wide and locks to the DST calendar is a workstation conversion fault. Repair the console — align zone and DST settings with the time master and apply the current workstation hotfix — and change nothing in the archive.
The fix, in order #
- Record the evidence first: both click behaviors, both readouts, on each affected station, with dates.
- Align each workstation with the EWS time master — same time zone, same DST enablement, and a displayed clock that matches the master when compared side by side.
- Apply the current workstation hotfix for your DeltaV release. No hotfix identifier was recorded for this case, so obtain it through the vendor's own support channel and match it to your installed build and symptom — the same discipline as applying hotfix NK-1900-1074 to an AMS Device Manager 14.1.1 workstation, where build and symptom are confirmed before the package goes on.
- Retest both clicks on every workstation immediately after the change: cursor on the click with a true timestamp below, and a line click that keeps the pair consistent.
- Leave the historian server's and controller clocks untouched. Changing server time settings alters how past data displays, and on a running network the clock also feeds alarms, schedules and batch records, so confine changes to the workstation side and a quiet window.
- Verify across the next DST transition. The reported fault cleared itself at one; with settings aligned and the hotfix installed, the display should hold steady through the next spring change, and that transition is your acceptance test.
The decision for each case #
- Displacement equal to the DST hour, on every station, changing at a DST boundary: console conversion fault. Align workstation settings with the EWS time master and apply the current workstation hotfix; the stored history needs nothing.
- Same displacement but on a single station only: that machine's zone, DST or software level. Correct that workstation first, then hotfix it.
- Cursor and timestamp agree with each other but the line sits at the wrong wall-clock time: value-side fault, not this one — work the UTC offset and time-synchronization checks instead.
- Displacement of odd minutes rather than a DST hour: clock drift or a broken synchronization path between the time master and the node; repair the sync before touching trend software.
- Fault persists after alignment and hotfix: escalate to the vendor with your recorded click positions, cursor times and timestamps; never edit stored history to make a display agree.
Questions asked
The fault cleared itself when daylight saving ended — is anything still wrong?
The transition only confirms the DST link: once the calendar left summer time, the wrong conversion and the right one landed on the same wall-clock reading, so the symptom vanished without the underlying setting or software being corrected. The stored UTC history never moved. Treat the clearing as diagnostic evidence, keep your recorded screenshots, and still align the workstation settings and apply the current workstation hotfix so the fault does not return at the next spring change.
Does installing the workstation hotfix change the stored history?
No. A workstation hotfix changes how the console converts and draws times; the historian keeps its values in UTC and the archive is not touched by the install. That separation is exactly why the fix is console-side: after the hotfix, the same stored samples are drawn at the corrected local times with cursor and timestamp agreeing. Close the open Process History windows and re-open the trend after the install so every readout picks up the corrected conversion.
My trend offset is about 25 minutes, not an hour. Same fault?
No. A daylight-saving mismatch can only displace a readout by the DST shift itself; no zone or calendar setting produces a smaller offset. A 25-minute displacement means the workstation clock is drifting or stepping against the time master, which is a time-synchronization fault rather than a conversion one. Compare the workstation clock against the EWS and the upstream time source, and repair the synchronization path before touching trend software.
Where does the workstation hotfix come from?
From the control-system vendor's own support channel, matched to your exact DeltaV release and installed workstation build — never from a copy saved on another machine or a third-party download site. No hotfix identifier was recorded for the reported case, so ask the vendor for the current workstation rollup for your release and confirm that its symptom list covers the cursor displacement before deploying it to every operator station.