Explainer
Remote PLC access through HMI transparent mode
Short answer
Yes, when the HMI's transparent mode passes the PLC programming protocol unchanged between its Ethernet side and its serial RS-422 side, and you carry that serial stream over the remote gateway's virtual COM port end to end. A cyclic data exchange through a second PLC proves only data transfer; it is not programming access, which only a completed online connection through the full route proves.

On this page
- Can you reach a serial PLC for programming through its HMI?
- What does transparent mode actually do to your programming protocol?
- Why does a working data link not prove programming access?
- How do you carry the programming tunnel across a remote access gateway?
- How do you test the whole route before trusting it?
- What happens to the route when the HMI loses the PLC?
- When should you route around the HMI instead?
- Questions asked
An HMI in transparent mode can give you remote programming access to the serial PLC behind it, but only when the programming protocol passes through the HMI unchanged and you carry that serial stream across the remote gateway as a virtual COM port. The decision rule is simple: test the full route with an online connection from the programming software, and classify a cyclic data exchange through a second PLC as data transfer only. This article explains what transparent mode does on a Mitsubishi GOT serving an FX-series CPU, why a working tag exchange proves nothing about programming access, how to set up and test the virtual serial path over a remote access gateway, and what to do when the route fails or the HMI must come down.
Can you reach a serial PLC for programming through its HMI? #
You can, but only when the HMI's transparent mode passes your programming protocol unchanged from its Ethernet side to its serial side, which gives you one fixed route — engineering PC, remote gateway, HMI Ethernet, HMI serial port, PLC — four hops, all of them serial-transparent end to end. Your installation already proves half of that route: the engineering station reaches the GOT 2103 over Ethernet and programs the FX1N over the panel's RS-422 link with the GOT set to transparent mode. So the GOT's Ethernet pass-through already accepts programming traffic from a network client. The only open question is whether a remote client, delivered through the gateway's tunnel, is treated the same way — and that is a test, not an assumption.
What does transparent mode actually do to your programming protocol? #
Transparent mode turns the HMI into a protocol pass-through: the GOT forwards the frames arriving on its Ethernet side out of the RS-422 port to the FX CPU and returns the replies untouched, so the programming software talks to the PLC exactly as if its cable were plugged in locally. The pass-through lives in the GOT's communication settings, and its serial side uses the parameters of the PLC channel already defined in the panel project. Two consequences follow. First, your frames are never rewritten, so the FX programming protocol behaves on the far side of the tunnel as the Mitsubishi FX serial communication documentation describes it on a direct cable. Second, the GOT's own screen polling and your programming traffic share that one serial link, so a busy panel competes with your session for the line.
Why does a working data link not prove programming access? #
A cyclic data exchange proves only that the HMI can move values between two PLCs; it says nothing about programming access, because online monitoring, forcing and program download open a dedicated session that the HMI must pass through, not generate itself. The workaround already running in your plant makes the distinction concrete: the gateway writes tags into a Siemens PLC, and the GOT cyclic exchange copies those values between the Siemens CPU and the Mitsubishi FX CPU. Values arrive in the FX data registers, the process keeps working, and none of it exercises a programming session. The same boundary appears whenever you are collecting serial PLC data through remote HMI panels: data collection rides the HMI's own polling, while engineering access rides the pass-through. Accept the workaround for what it does, and do not let a green value in the PLC convince you the tunnel is ready for GX Developer.
How do you carry the programming tunnel across a remote access gateway? #
You use the remote gateway's virtual serial port — eWON calls this feature VCOM — so the programming software opens a local COM port that the gateway carries across its tunnel to the HMI's serial side. In this architecture the tunnel peer is not a serial device server but the GOT's Ethernet port: VCOM simply puts the remote engineering PC on the same Ethernet footing as the local station that already programs through the panel. Configure the virtual port on the engineering PC, point the gateway side at the GOT's address on the machine LAN, and set one side of the tunnel as client rather than both, the same one-side-client rule that the PortServer TS 8 serial tunnel guide explains for plain device-server tunnels. The gateway and its VPN endpoints must pass that tunnel reliably, which is a selection question covered in choosing a firewall and VPN for an industrial remote access router.
How do you test the whole route before trusting it? #
Run one write-and-read cycle through every hop and accept the route only when the value comes back identical: for example write 1234 to data register D100 through the tunnel, read it back through the same route, and pass the route only on an exact 1234. Work through it in order:
- Open the programming software on the virtual COM port and connect online to the FX1N; the session must establish and hold, not just pulse.
- Write K1234 to D100. The check is arithmetic you can do on paper: 1234 decimal is 0x04D2, because 4 x 256 + 13 x 16 + 2 = 1024 + 208 + 2 = 1234. A read-back showing 4D2 in a hexadecimal display is the same value, not a truncated transfer.
- Force one bit and watch the CPU accept and report it, which exercises the session's write path, not just its read path.
- Keep the monitor open through a normal production cycle and confirm the serial link carries it without dropping.
A successful ping is not on this list on purpose: reachability without a working session proves nothing, as the article on a ping that works while a PLC program download fails over remote access shows. And one safety line belongs here: put someone at the machine able to stop it before you send any program change through a remote tunnel.
What happens to the route when the HMI loses the PLC? #
The route dies with the HMI's own link: Mitsubishi's GOT2000 utility documentation states that if a communication fault, including cable disconnection, occurs during monitoring, communication between the GOT and the PLC CPU is suspended. Your pass-through session rides that same link, so a loose RS-422 connector, a panel restart or a GOT project transfer suspends both the HMI screens and your programming session at the same moment. Plan engineering windows around it: program through the transparent route only while the panel is healthy, and expect to reconnect and recheck the register values from step 2 of the test whenever the panel has been touched. When a session drops and will not come back, the failure is usually at one hop, and the article on a PLC agent that will not go online remotely walks the same hop-by-hop isolation for a gateway route.
When should you route around the HMI instead? #
Route around the HMI when transparent mode fails the end-to-end test or when the panel must be powered down: a dedicated serial gateway on the RS-422 programming line keeps programming access independent of the HMI project, its pass-through settings and its power state. The decision for each case:
- Programming access is the goal and the online test passes: keep the transparent route, standardize the virtual COM port settings, and treat the pass-through configuration as part of the panel's change control.
- Only tag values are needed: the second-PLC cyclic exchange stands on its own, and you owe it no further programming tests.
- The pass-through test fails or panel downtime makes the route unusable: check the CPU's option boards for a second serial channel and give the gateway its own port, or accept scheduled access through the panel, because the FX1N's single programming line cannot serve both demands reliably at once.
Commit to one of those three after the test, and record which path you proved: engineering access through the full route, or data exchange through the HMI. The two are not interchangeable, and the difference is exactly one online connection.
Questions asked
Which serial parameters have to match across the transparent route?
The virtual COM port on the engineering PC must use the same station number, baud rate, parity and stop bits as the GOT's PLC-side channel, and those values must match the FX CPU's communication parameters. Take them from the GOT project and the PLC parameters rather than assuming defaults, and change both ends of the route together when you retune it.
Can a GOT project download and a programming session share the pass-through?
Not safely at the same time. A GOT project transfer can restart the panel's communication, and a restart suspends the link between the GOT and the PLC CPU, which drops any active programming session through the pass-through. Schedule HMI project transfers for a window when nobody is online with the PLC.
What happens if two engineers open the tunnel at once?
The FX programming link serves one master, so coordinate one online session at a time. Close the first virtual COM port before the second engineer connects, and treat an unexplained timeout right after a second client joined as a collision on the pass-through rather than a cable fault.