Running a second historian beside a DeltaV continuous historian

Edge computing and IIoT Published 7 min read

Short answer

Yes. The Advanced Continuous Historian keeps its native path and the second historian joins as one more client of the DeltaV OPC UA or OPC server. The design is decided by the server's published client counts, 25 concurrent history clients under the OPC History Server license, the connector's supported interface and recovery behavior, and per-path deadband and timestamp settings, so validate raw stored samples rather than trend lines.

On this page
  1. Where the second historian connects
  2. The numbers that set the ceiling
  3. OPC UA or OPC Classic for the collector
  4. Why two correct histories disagree
  5. Budgeting the 25-client history license before adding a collector
  6. Commissioning the parallel path
  7. The decision for each case
  8. Questions asked

Yes — two historians can collect the same DeltaV values in parallel, and the combination is common. The Advanced Continuous Historian keeps its native collection path untouched, and the second historian joins the DeltaV OPC UA or OPC server as one more client. Nothing in that arrangement conflicts by itself. The issues you will actually meet are countable: how many concurrent clients the installed servers are licensed and tested for, whether the second historian's connector speaks OPC UA or must connect as a 32-bit OPC Classic client, how it recovers values missed during a disconnect, and the deadband, interval and timestamp settings that make two correct histories look different on a trend. This article works each of those down to numbers and decisions.

Where the second historian connects #

The Advanced Continuous Historian collects through DeltaV's own path and does not read through the OPC servers, so adding an OPC client does not put the two historians in contention with each other. The second historian — AspenTech IP21 and Honeywell PHD are the usual candidates in this role — connects to the DeltaV OPC UA server, or to the Classic OPC server, and holds its own subscriptions. The server multiplexes those subscriptions; each client sees its own values, quality and timestamps.

A product name alone does not tell you which of those interfaces the connector actually supports, or how it behaves on a reconnect. Select the connector first, then the protocol. Before committing the integration effort at all, confirm the destination truly needs historian-grade storage: whether you need a historian or just an OPC tag server is a separate question with a cheaper answer. If the destination is a PI system rather than a third historian, moving DeltaV Continuous Historian data into a PI system is the better-trodden path.

The numbers that set the ceiling #

Every OPC server on the market publishes a client budget, and yours is the number the design must clear. For DeltaV history access, the DeltaV OPC History Server license provides up to 25 concurrent OPC Historical Data Access client connections, per the DeltaV OPC UA Servers and Clients product data sheet. Trend sessions that read history, report jobs and any backfill or recovery client all draw from that 25.

The live-data servers are budgeted separately. The supported client and subscription counts for the OPC UA server and the Classic OPC server in your release are stated in that same documentation set, so read them for the installed version rather than assuming headroom. For scale, other platforms publish equivalents — Ignition documents its OPC UA server at 100 active client connections, and Siemens documents 10 connected OPC UA clients tested on a Unified PC runtime acting as a server — which is the point: the number exists, it is finite, and you count against it.

OPC UA or OPC Classic for the collector #

Choose OPC UA when the installed DeltaV server and the connector both support it: endpoint-based connections, explicit certificate trust and firewall-friendly traffic make an unattended collector far easier to own than DCOM ever was. Choose OPC Classic only when the connector offers no UA path for your DeltaV release. That path carries a hard constraint: Emerson's client guidance for the DeltaV OPC server states "The OPC client application must be a 32-bit application." — 64-bit OPC clients are refused, so the collector service must run 32-bit, and Windows identity and COM/DCOM configuration become part of the connection you maintain.

Neither protocol choice, by itself, recovers values missed while the collector is down. Recovery is a connector feature: some connectors buffer locally and backfill through the history server on reconnect, others resume from the current value and leave a permanent gap. Buy the connector whose recovery behavior you can live with.

Why two correct histories disagree #

Two historians fed from the same server can both be healthy and still disagree on screen, because each path applies its own sampling interval, deadband, timestamp rule and storage compression. A collector that stores only on change beyond a deadband legitimately omits a short excursion that a fixed-interval collector keeps. A collector that timestamps on receipt differs from one that stores the source timestamp. Neither is wrong; they measure differently. Compare raw stored samples with their timestamps before comparing interpolated trend lines — row counts and event times over one identical window settle most mismatch complaints.

Separate collection faults from display faults while you are at it. A blank trend with valid stored samples is a tag binding or query problem. Bad-quality samples point at the connector, the server item or the source parameter. A flat line on a live process points at a dead subscription or an over-wide deadband.

Symptom on one history First place to look Usual distinction
Spike missing on one system Deadband and interval settings Filtering, not a fault
Same values, different times Source versus receipt timestamp rule Time interpretation, not data loss
Different sample counts Compression and interval Both correct, different semantics
Gap after an outage Connector buffering and backfill Recovery capability, not server capacity

Budgeting the 25-client history license before adding a collector #

The case: a plant adding a third-party historian beside the Advanced Continuous Historian wants to know whether history access still fits its license.

Inputs, each with its source:

  • Licensed ceiling: 25 concurrent OPC Historical Data Access client connections — documented in the DeltaV OPC UA Servers and Clients product data sheet.
  • Existing concurrent history clients, an illustrative mid-size unit: 8 operator stations with one trend session each (8 connections), 2 scheduled report jobs (2), 1 engineering analysis session (1).
  • New load: the second historian's live collection rides the live-data server, but if its connector backfills through the history server it opens 1 more concurrent session during recovery.

Rule in words: the sum of simultaneous history clients must stay at or below the licensed ceiling.

Arithmetic: 8 + 2 + 1 = 11 existing connections. Adding the recovery session: 11 + 1 = 12. Headroom: 25 − 12 = 13.

Decision: proceed. Twelve connections used leaves 13 spare, which covers report jobs added later. The threshold is 25 concurrent — if planned sessions would pass it, either license additional connections or schedule report and backfill windows so they do not overlap. If the connector parallelizes recovery across several sessions, count each one.

Commissioning the parallel path #

  1. Baseline the plant as it runs today: save representative Advanced Continuous Historian trends and the OPC server's client and resource diagnostics before anything changes.
  2. Fix the connector choice and its licensing against the installed DeltaV release before mapping production tags.
  3. Configure the unattended identity — OPC UA endpoint, security policy, certificate trust and user identity, or the Classic path's Windows account and DCOM settings — and test under the account the collector service actually runs as.
  4. Grant read access only. A history collector needs to read; control-write permission adds risk and buys nothing.
  5. Pilot with a small tag set that includes fast analogs and discrete states; verify item identifiers, data types, engineering units and quality mapping against the server namespace.
  6. Set interval, deadband and timestamp rule deliberately, and to comparable values where the two histories will be compared.
  7. Stage the expansion while watching server client counts, collector backlog and data freshness, then close the pilot gaps by backfilling trend history from the plant historian before widening the set.

Run the collector on its own Windows host rather than a shared workstation; for a cabinet installation, a fanless mini PC is a common fit for that role.

The decision for each case #

  • Second historian over OPC UA (IP21, PHD or similar with a UA connector): go. Count clients against the published budgets, verify the connector's interface and recovery in writing, and align deadband and timestamps where agreement matters.
  • Connector is OPC Classic only: still viable, but the collector runs 32-bit and you own its DCOM configuration. Treat it as a waypoint, not a destination.
  • The goal is identical histories: align interval, deadband and timestamp settings, then judge agreement on raw stored samples. Expect legitimate small differences, not bitwise identity.
  • Planned concurrent history clients above the licensed ceiling: license more connections or de-schedule. Do not run at the ceiling with backfill pending.

The native Advanced Continuous Historian is not the constraint in any of these cases; the server budgets, the connector's recovery behavior and the collection semantics are.

Questions asked

Does the second historian add load on the DeltaV controllers?

The added client terminates at the DeltaV OPC or OPC UA server, which multiplexes subscriptions onto the control network. What you manage is the server's published client and subscription budget and its processing headroom, so watch the server's own diagnostics and data freshness while the collector starts, and compare them with the baseline you saved beforehand.

Which third-party historians have a documented DeltaV connector?

AspenTech IP21 and Honeywell PHD appear regularly in this role, but the product name alone does not tell you which DeltaV interface the connector supports, whether it buffers through a disconnect, or how it backfills. Get the supported-interface list and the recovery mechanism in writing from the connector vendor, and confirm the license covers continuous collection before mapping production tags.

How many clients can read DeltaV history before we hit the limit?

Every concurrent history reader draws from that licensed count: trend sessions that read history, report jobs, dashboards and any backfill or recovery session. Count each one, as the worked example shows. If planned concurrency would pass it, license additional connections or move backfill windows off peak.

Why does one historian show a spike the other misses?

Usually a deadband. A collector that stores only when a value moves beyond its deadband can drop a short excursion that a fixed-interval collector kept. Pull the raw stored samples for the same window from both systems: if both stored it, the difference is trend interpolation on screen; if only one stored it, the deadband or interval is the cause.

Keep reading

  • Comparison

    Canary historian export paths: MQTT publisher or API read

    Canary gives you two confirmed ways to move historian data out: the Publisher service, which pushes real-time values to MQTT or Kafka as Sparkplug B or JSON, and the Read API, which an external client calls to pull stored data. An outbound OPC UA server is not a confirmed option.

    Edge computing and IIoT

  • How-to

    Expose historian latest values over OPC UA or MQTT

    Yes — connect an integration gateway to the historian's classic I/O Server over SuiteLink (application name aahiosvrsvc, topic TagName) and publish the current values as OPC DA and MQTT. After a historian restart the I/O Server and the Live table return nothing until the source sends a new value, so a true last-known-from-disk read needs T-SQL or the historian SDK.

    Edge computing and IIoT

  • Comparison

    Move DeltaV Continuous Historian data into a PI system

    When PI points exist, collect DeltaV live values with OPC DA and recover history with OPC HDA; when points and AF structure are missing, let the DeltaV Smart Connector create them from EntHist.xml. Add PI-to-PI only for a second office-LAN server. Prove buffering, service identity and archive coverage by test before the bulk load.

    Edge computing and IIoT