Edge computing and IIoT Published 5 min read

Short answer

The warnings come from an independently configured standalone IDAS, not from the historian data path. Stopping the Windows service that hosts aahSupervisor.exe ended them in the documented case while partner sync and AppServer data continued; IDAS properties, security reconfiguration and a full reinstall do not touch the standalone instance.

On this page
  1. Where the warning comes from
  2. What does not stop it
  3. Stop the service that hosts aahSupervisor.exe
  4. Verify you silenced noise, not data
  5. Make the fix survive a reboot
  6. Remove the standalone configuration permanently
  7. Questions asked

Stop the Windows service that hosts aahSupervisor.exe. On a newly installed Historian 23 node set up as a partner collecting from AppServer, the repeating IDAS connection warnings came from an independently configured standalone IDAS: they continued even while Historian was shut down, and stopping that one service ended them while partner synchronization and AppServer data kept working. Disabling IDAS through its properties, re-running the Security configuration, and a full reinstall against a rebuilt database all failed to quiet the logger, because none of them govern the standalone instance. The service stop is the fix to try first; removing the standalone configuration files is the permanent form of the same fix.

Where the warning comes from #

A Historian install carries an integrated IDAS, whose documented configuration path runs through the Operations Control Management Console, with the historian reconfiguring itself dynamically as settings change. A standalone IDAS is a separate deployment: the vendor's remote-node procedure installs the IDAS software on a node without the Historian Server software, so its processes and startup files have a lifecycle of their own. When a full Historian install lands on a node that already holds standalone IDAS configuration, the two components stay separate. In the documented installation they were configured independently and never merged.

That separation produces a diagnostic signature you can read straight off the machine:

  • Warnings repeat while Historian is shut down. A management-console shutdown is not a Windows service stop, so a separately registered supervisor keeps running and keeps attempting its connection.
  • Partner synchronization and AppServer-sourced data continue while the warnings repeat. The warning-producing connection and the intended data path are separate items; noise in one is not evidence of a fault in the other.
  • Disabling and enabling IDAS through its properties changes nothing. Those edits only take effect once pending changes are committed, and in the documented case the commit was made in both states with no effect on the warnings.
  • The Configurator offers no IDAS category to switch off. The standalone configuration has no toggle there, so it is managed as a service and as files, not as a properties page.

What does not stop it #

Each of these was tried in the documented installation, and the aahidas messages kept repeating after every one:

  • Disabling, then enabling, IDAS through the IDAS properties, committing pending changes each time.
  • Re-running the Security configuration in the Configurator, removing and re-adding users.
  • Deleting the idascfg_-prefixed .dat file under C:\ProgramData\ArchestrA\Historian\IDAS\Configurations — the remedy in the IDAS-deadlock technote, which addresses a different fault.
  • Adding a throwaway I/O server under IDAS and deleting it again.
  • Disabling the connection to the SMS.
  • Uninstalling Historian completely, reinstalling, and dropping and recreating the database.

The reinstall is the expensive non-fix. The warnings resumed against a freshly built database, which on its own says the source sits outside the Historian runtime.

Stop the service that hosts aahSupervisor.exe #

  1. Open the services console and identify the service by its executable path, not its display name: inspect each candidate's path in its properties and take the one whose path contains aahSupervisor.exe.
  2. Record the service name, its startup type, its listed dependencies, and which applications the supervisor hosts.
  3. Stop the service inside a maintenance window. The one caution that matters here: this supervisor can host more than the unwanted IDAS component, and the dependency and hosting check in step 2 is what makes the stop a decision rather than a gamble.
  4. Confirm aahSupervisor.exe no longer appears among running processes.
  5. Filter aaLogger to the aahidas component and watch for new entries for longer than the recurrence interval you measured before the stop.

Illustrative timing: if the logger showed one aahidas warning every 30 s before the stop, watch for 10 intervals — 10 × 30 s = 300 s, or 5 minutes — and require zero new aahidas entries in that window. In the documented case the stop produced a clean logger immediately and data kept flowing; quiet logger plus fresh data is the pass condition.

Verify you silenced noise, not data #

A quiet logger with stale timestamps is a failed result. Before calling it done:

  • Confirm the partner is connected and synchronization with the primary is running — the same health checks used when running redundant InTouch historians with parallel tag logging.
  • Read an AppServer-sourced tag on the partner and confirm its value and timestamp are newer than the service-stop time, compared against the baseline recorded before the stop.
  • Keep aaLogger filtered to aahidas for the full observation window.

Make the fix survive a reboot #

Stopping a service does not change its startup type. The decision splits on one fact from step 2:

  • Nothing else on the node needs that supervisor: set its startup type to Disabled so it does not return at boot, and record the original setting so the change stays reversible.
  • Another installed feature shares the supervisor: leave startup alone and remove the standalone IDAS configuration instead, so the supervisor stops launching IDAS without losing its other work.

Remove the standalone configuration permanently #

Two locations under C:\ProgramData\ArchestrA\Historian carry the standalone IDAS, and both get a backup copy before any change:

  • The IDAS configuration: rename aahIDAS.config, and back up the idascfg_-prefixed .dat files under IDAS\Configurations rather than deleting them outright, so the removal stays reversible.
  • StartupConfig.xml: this file is required. It should hold exactly one application element, the OWINHost entry whose path points at aahOwinHostlocal.exe. The documented installation's file already matched that state and needed no edit; if yours lists more than one application element, copy the file and remove only the extras.

An InsightPublisher folder at C:\Program Files (x86)\Wonderware\InTouch\InsightPublisher with no matching entry in Programs and Features is a leftover, not proof of an installed feature, and it was not the warning source in the documented case.

None of this file work was needed there: the service stop alone gave a clean log, and the operator stopped at that. That is the endpoint to aim for — stop the service, verify the data paths, disable startup after the dependency check, and touch files only when a service setting cannot deliver the result.

Questions asked

Will the IDAS warnings return after a reboot if I only stop the service?

Yes. Stopping a service leaves its startup type unchanged, so a service set to Automatic starts again at boot and the warnings come back with it. Once you have confirmed partner sync and AppServer data are intact, set the startup type to Manual or Disabled and record the original setting in case another feature on the node needs the supervisor.

Why is there no IDAS entry in the Configurator to switch off?

The integrated IDAS and a standalone remote-node IDAS are configured independently, and a full Historian install over a node that already holds standalone IDAS files does not merge them. The Configurator exposes the integrated component, so the standalone configuration has no toggle there. In the documented case the category appeared during reinstall, could not be cleared, and was absent afterwards.

Is it safe to edit StartupConfig.xml?

The file is required and should contain exactly one application element, the OWINHost entry whose path points at aahOwinHostlocal.exe. In the documented installation it already matched that state and needed no edit. If yours lists more than one application element, copy the file first and remove only the extra entries, then restart so the supervisor reads the corrected startup list.

Does a leftover InsightPublisher folder cause the warnings?

Not by itself. A folder under Program Files (x86) with no matching entry in Programs and Features is a leftover, not proof of an installed or running feature. Check whether any service or startup file references that path; if nothing does, it is not your warning source.

Do the aahidas messages mean my tags are failing?

No. In the documented case partner synchronization and AppServer-sourced values continued while the warnings repeated, and both kept working after the service stop. The message tracks a standalone component's connection attempt, not the acquisition path, so confirm tag health with fresh timestamps rather than reading it out of the warning.

Keep reading

  • Troubleshooting

    Why InTouch stops logging to Historian after WindowMaker edits

    When every historized tag stops after a WindowMaker edit and values pile up in the InTouch store-and-forward buffer, the delivery path to the Historian has failed, not the tags. Restarting the Historian in OCMC does not clear it. Run osconfiguratorutility.exe to reapply the node's firewall rules and folder permissions, and logging resumes.

    Edge computing and IIoT

  • Troubleshooting

    Why Wonderware System Platform tags do not reach Historian

    When Historian shows only system tags, attribute historization alone is not the end of it: System Platform submits application data only when the Platform-level Log to Historian setting is on, with Engine historian node information and the Galaxy-to-Historian configuration in place. PLC tags acquired directly bypass this chain and are configured in the System Management Console instead.

    Edge computing and IIoT

  • Explainer

    Can plant historian software run in Docker containers

    The processes will start, but historian services hold retained state and are not documented to communicate statelessly, so a started container proves nothing about collection, calculations, events, or queries surviving replacement. Keep the working deployment in production and evaluate containers only in an isolated test, with a volume mapped for every path that holds data or configuration, passing a counted query across a restart, a recreate, and a host move.