IMD SolutionComputing LibraryShop main store

Troubleshooting

Tag Browse Tree missing from your designer palette

Edge computing and IIoT Published 7 min read

Short answer

The Tag Browse Tree and Power Table do not exist in the Ignition 7.6.6 designer; both ship in the 7.7 line, so no setting will reveal them. Verify the gateway and designer versions, then upgrade both to 7.7 or later, or rebuild the browse-and-drop behavior on 7.6.6 with a filtered tag list and a bounded tag history query.

On this page
  1. Confirm the cause before touching configuration
  2. Which release added the components
  3. Upgrade path: moving the project to the 7.7 line
  4. Worked example: sizing the history query return for three tags over seven days
  5. Rebuilding the search-and-drop behavior on 7.6.6
  6. Verify from a runtime client
  7. Questions asked

Nothing is misconfigured. The Tag Browse Tree and the Power Table are not part of the Ignition 7.6.6 designer; both components ship in the 7.7 line, so no palette, property or permission change will make them appear. Check the gateway and designer versions, then take one of two paths: upgrade both to 7.7 or later and wire the native components into your trend and table, or stay on 7.6.6 and rebuild the browse-and-drop behavior with a filtered tag list and a bounded tag history query. This article walks through confirming the cause, the upgrade sequence, the query sizing that keeps the result responsive, and the 7.6.6 build from the historian's own metadata.

Confirm the cause before touching configuration #

Work down this list; it takes minutes and it separates a version fact from a settings fault:

  • Read the gateway version on the gateway status page and the designer version in its about dialog. They must match.
  • Search the component palette for Tag Browse Tree and Power Table. On 7.6.6 neither appears, and no palette filter hides them.
  • Compare the release manuals: the 7.9 manual documents Tag Browse Tree among its Tables components, while the 7.6.6 manual lists neither component.
  • Open a copy of the project in a designer known to run 7.7 or later and confirm the components appear there. That isolates the release, not your project.

An absent palette entry is a version fact, not a settings fault, and the same reading applies to the CIMCO V6 send command that is absent rather than misconfigured.

Which release added the components #

Both the Tag Browse Tree and the Power Table were added in the 7.7 line: a 7.7.5 designer shows them, a 7.6.6 designer does not. The Tag Browse Tree is documented as similar to the Tag Browser in the designer, and it works in both the designer and the runtime client, which is exactly the search-then-display workflow the 7.6.6 project lacks. In later releases the Vision component sits in the Tables group of the palette, and the documented ad hoc charting workflow drags it from there onto an Easy Chart. Ignition 8 adds a Perspective version of the Tag Browse Tree with its own manual page, so the component name survives a major upgrade too.

One related trap: cloud marketplace windows built for the 7.7 line or newer will not carry the feature back into 7.6.6. Importing them there either fails or leaves empty containers where the components should be.

Upgrade path: moving the project to the 7.7 line #

Upgrade when you control the gateway and can schedule the window. The native components already handle browsing, drag sources, drop targets and pen management; a scripted rebuild makes you maintain all of that by hand.

  1. Take a full gateway backup from the gateway configuration page, and export the Vision project separately.
  2. Record the historian settings: the database connection, the history provider name, and every datasource the project's SQL queries use.
  3. Restore the backup onto a test gateway running the target 7.7 release. Open every window that uses charts, tables or scripting, and read the designer output console for script errors.
  4. Confirm with the vendor through its official support channel how your license carries across the version change before you book the production window, and verify the active runtime license on the deployed target afterwards. A licensing problem found after the upgrade becomes an outage.
  5. Upgrade production, then relaunch the designer so its version matches the gateway.

After the upgrade, check three things: both components appear in the palette, existing trends still return data, and the history provider shows connected on the gateway status page. If a trend comes up flat, check the query row limit before suspecting the data; the row-limit cause of a flat historian trend covers that case.

Worked example: sizing the history query return for three tags over seven days #

This is the sizing you must do either way, because the native workflow and the 7.6.6 rebuild both end in the same tag history query.

Inputs, each declared as an example unless it comes from your own project:

  • Three tags, selected in the runtime client after a search; that is the browse-and-drop case this article solves.
  • A chart range of 7 days set by the operator, which is 7 days times 86,400 s/day, or 604,800 s.
  • An example logging rate of 1 sample per second per tag with no deadband. Substitute your tags' actual rate; deadband logging stores far fewer rows than the scan rate suggests.
  • An example aggregation window of 60 s with an explicit aggregation mode and return size set on the query.

Rule in words: when the query specifies an aggregation mode and a return size, the return holds roughly the range divided by the aggregation window, per tag. Without them, it holds every stored sample.

Arithmetic:

  • Raw return without aggregation: 604,800 s at 1 sample per second gives 604,800 samples per tag; across 3 tags that is 1,814,400 rows pushed to the client.
  • With the 60 s window: 604,800 s divided by 60 s gives 10,080 rows per tag; across 3 tags that is 30,240 rows.
  • That is a 60-fold cut: 1,814,400 divided by 30,240 equals 60.

Decision: pick the aggregation window so the return fits the client's row budget, and set the mode and return size explicitly rather than leaving the query raw. For this range, a 60 s window at 10,080 rows per tag is a sound starting point; halving the window doubles the rows, so a 30 s window means 60,480 rows total and a stalling risk on an ordinary client. To hand operators a bounded tail instead of a fixed range, the last N stored records from an Ignition tag history query shows the query form.

Rebuilding the search-and-drop behavior on 7.6.6 #

Stay on 7.6.6 when validation, contract or a third-party module freezes the gateway. The historian stores each historized tag path in a metadata table inside the history database, alongside its retired and created timestamps, and the sample data lives in partitioned tables that reference those paths. Build the search step from that metadata:

  1. Open the history database with a SQL client and find the metadata table holding the tag paths and their retired flags.
  2. Add a text field and a list to the window. Bind the list to a SQL query against that metadata table, filtered with a LIKE on the search text, restricted to rows that are not retired, and limited to a capped row count. Require a minimum search string so an empty box does not pull the whole tag list.
  3. On selection, use a script to build the pen dataset for an Easy Chart from the selected paths, and run the same tag history query, with the aggregation window from the worked example above, to fill a standard table. Use the tag history query function from the scripting reference for your release rather than raw SQL against the partitions.

The pitfalls that bite this build:

Pitfall Symptom Fix
Retired paths not filtered out Duplicate entries; old paths return nothing Filter on the retired flag in the metadata query
Querying the partitions directly Data vanishes at a partition boundary Go through the tag history query function, not raw SQL
Path case or provider prefix mismatch Selection returns an empty dataset Build the path in the same format the tag editor shows
Unbounded search Slow client on large tag counts Require a minimum search string and cap the returned rows

Verify from a runtime client #

Test from a launched client, not the designer, because drag sources and drop targets behave differently there:

  • Search a partial tag name and confirm only live, historized paths come back.
  • Select three tags and confirm the chart shows three pens plotting data across a range where the tags were changing.
  • Confirm the table shows a timestamp column plus one column per selected tag, with values matching the chart at the same timestamps.
  • Narrow the date range and confirm both the chart and the table update to the same window.

If a dragged tag produces a pen with no data, the tag is right and its history configuration is wrong: check that history is enabled on the tag and that its history provider is the one the chart queries.

The decision, restated: on 7.6.6 the missing components are a release boundary, not a fault, so either schedule the upgrade to 7.7 or later and use the native Tag Browse Tree and Power Table, or build the filtered metadata search with a bounded history query and accept the scripting you now own.

Questions asked

Can I import a marketplace window that uses the Tag Browse Tree into a 7.6.6 gateway?

No. The window is built against components the 7.6.6 release does not contain, so the import either fails or drops the components and leaves empty containers. Rebuild the behavior with the parts 7.6.6 has, or upgrade the gateway and designer to the 7.7 line or later first and import the window afterwards.

How do I confirm the gateway and designer are on the same version?

Read the gateway version on the gateway status page and the designer version in its about dialog. Both numbers must match before you open the project; a designer older than the gateway cannot edit windows that release supports, and components missing from the palette are one symptom of that gap.

Why does a tag I dragged onto the chart show an empty pen?

The tag itself is fine; the history configuration is not. Check that history is enabled on the tag, that the tag's history provider is the one the chart queries, that the tree shows the tag provider the operator expects, and that the chart date range covers a period when the tag was actually changing.

Does anything besides the window size limit the rows a tag history query returns?

Yes: the aggregation mode and return size you set on the query, the logging rate and deadband style on each tag, and any row limit the client enforces. Deadband-style logging stores fewer samples before the query even runs, so the raw return can be far smaller than the scan rate alone suggests.

Keep reading

  • Troubleshooting

    Stale historian tag browse tree entries after a restore

    A historical tag browse tree lists the identities the edge historian has stored samples under, and a gateway restore replaces live tag configuration without touching that store. On a disposable development machine, stop the gateway, move the local .idb file out with a copy kept, and restart to clear them; Root Node Path trims the visible hierarchy without deleting data.

    Edge computing and IIoT

  • How-to

    How to log Ignition tags every 15 minutes to a database

    To capture Ignition tag values on a strict 15-minute schedule, use a scheduled SQL Bridge transaction group that inserts a snapshot row into a database table, then point the report's query at that table. The tag historian is deadband-driven and stores asynchronously, so it cannot be set to one fixed 15-minute timestamp.

    Edge computing and IIoT

  • Troubleshooting

    Reading default historian data in SQL Server the supported way

    Attaching a SQL Server DSN to the SystemHistorian tag does store the historian's tables in SQL Server, but they are keyed to internal tag IDs, not tag names. Keep the default historian as the store and read the data through the REST SQLQuery endpoint, building an ID-to-name lookup from the Parms tables and paging large ranges in blocks of about ten thousand records.

    Edge computing and IIoT