Remote access and virtualization
Earlier articles
Troubleshooting
Remote PLC access stops after a service plan change
When remote PLC access dies after a service plan change, the cloud entitlement layer failed, not the gateway, the LAN or the PLC. Test the four layers in order — gateway power and LAN, gateway configuration, service entitlement, user access — and repair only the layer that fails; no reset, cable change or PLC edit restores a removed subscription.
Checklist
Proxmox for SCADA and PLC engineering virtual machines
Yes — Proxmox runs Siemens SCADA and PLC engineering VMs; field teams use it for TIA Portal engineering over RDP and in-cabinet dedicated hosts. Commit per workload: pass the support-position, Layer 2 bridge, license and restore tests below before production, and size the host from measured demand.
Troubleshooting
Host blue screen during serial VM connection to a PLC
A host blue screen during a VM serial session to a PLC is a Windows 10 host crash in the USB-serial and virtualization stack, not a PLC or guest fault. Capture the stop code and version stack, check whether Workstation 14 is documented for your Windows 10 build (Broadcom lists Windows 10 1903 hosts from Workstation 15.x upward), then upgrade Workstation, refresh VMware Tools, and retest before touching adapter or PLC settings.
Troubleshooting
Fixing slow automation VMs on a Windows 11 host
The usual cause is the Microsoft hypervisor layer under VMware, confirmed by the turtle icon in the status bar. Turn off Memory Integrity, disable Virtual Machine Platform and Windows Hypervisor Platform, run bcdedit /set hypervisorlaunchtype off, reboot, and rerun the same workload — with IT approval on a work machine. Guest memory is ruled out: 16 GB did not help, and working setups run smaller allocations.
Troubleshooting
Fixing a VM remote PLC connection with a NAT adapter
Set the guest's virtual adapter to NAT with DHCP, disable every other guest adapter, and keep the remote-access soft key on the host. The failure that repeats is a second bridged adapter pulling the PLC route away from the NAT path. Test the host path first, then the guest, and check that no local subnet matches the plant network.