When a historian web client chart auto-refreshes itself

Edge computing and IIoT Published 6 min read

Short answer

Yes, the historian web client chart refreshes itself: installations report a cadence tied to the selected time range, roughly every 5 minutes on a last-hour view and every 15 minutes on a one-day view. Keep the range relative, measure the real interval in the browser, and run the Client Tool on a dedicated PC when you need continuous scrolling.

On this page
  1. What the chart does on its own
  2. Relative range versus absolute range
  3. Measure the interval your installation actually uses
  4. Worked example: what the cadence costs the server
  5. When the chart is not the cause
  6. Continuous scrolling at the monitor
  7. Keeping a kiosk display live
  8. Questions asked

Yes, the chart refreshes itself. The Historian Web Client trend re-queries the historian on an interval that follows the selected time range, so a display-only monitor stays live as long as the chart uses a relative range and the browser tab is never throttled. The cadence is not a per-chart setting you can tune, and the chart steps forward in jumps rather than scrolling. For a continuously moving line like play mode, run the Client Tool on a dedicated PC at the monitor. The checks below confirm what your installation actually does and what to change when the display goes stale.

What the chart does on its own #

The vendor documentation for the historian client tools documents a manual refresh only: a Refresh toolbar button and a right-click Refresh command on the chart. The automatic behavior is real but less well documented. Installations report that the chart refreshes by itself on an interval that depends on the time range — about every 5 minutes on a last-hour view and about every 15 minutes on a one-day view — and that the feature has existed since a 2017 release. Current documentation no longer prints those figures, so treat them as a working baseline to verify, not a specification. The interval is not exposed as a per-chart setting in any documentation this article could verify, which is why the practical path is to measure what your own installation does.

Relative range versus absolute range #

A refresh re-runs the query behind the chart. What happens next depends entirely on the range type:

  • Absolute range (a fixed start and end timestamp): the re-query returns the same window every time, so the picture never changes and the refresh looks broken.
  • Relative range (for example, the last hour): the window is re-evaluated against the current time on each refresh, so the right edge advances and the oldest data scrolls off.

The decision here is simple: any chart destined for a display-only monitor must use a relative range. Set it, save the view or note its URL, and reopen it once to confirm the monitor loads the same chart after a restart. If a relative range still shows a static picture, the problem is elsewhere — go to the measurement check.

Measure the interval your installation actually uses #

Read the interval instead of trusting the reported numbers. The browser shows you exactly when the chart asks the historian for data:

  1. Open the chart on the monitor's own browser, in the range you plan to display.
  2. Open the developer tools and switch to the Network tab.
  3. With the range set to the last hour, record the gap between two consecutive chart data requests.
  4. Change the range to one day and record the gap again.
  5. Compare the two. If the gap grows with the range, you are seeing the range-dependent refresh working as designed.

If no data requests appear at all over half an hour, the chart is not auto-refreshing on this version or configuration, and the Client Tool fallback at the end of this article is your answer. If requests do appear, quote the measured gap to the customer, not a remembered figure.

Worked example: what the cadence costs the server #

The refresh cadence determines both how fresh the display is and how much history each re-query reads, so it is worth running the numbers before you pick a range.

Take the reported baseline. A last-hour view refreshing about every 5 minutes fires 60 min ÷ 5 min = 12 refresh queries per hour, which is 12 × 24 = 288 queries per day. Each query reads 1 hour of history, so one chart reads 288 tag-hours of history per day. A one-day view refreshing about every 15 minutes fires 1,440 min ÷ 15 min = 96 queries per day, each reading 24 hours: 96 × 24 = 2,304 tag-hours per day — eight times the history read by the shorter view, for a display that updates three times less often.

The decision falls out of the arithmetic: pick the shortest relative range that still serves the visualization. It refreshes more often and reads less total history, which matters when a dozen kiosk charts hit the same server. If page loads on that server are already sluggish, work through the slow historian web client diagnostics before adding more refresh traffic.

When the chart is not the cause #

A refresh only asks the historian what it has already stored. Before blaming the cadence, compare the same tag in the Client Tool and read the timestamp of the last stored point against the current time:

What you see Meaning Next step
Client Tool shows newer data than the web chart The chart is simply between refreshes Wait one measured interval, then recheck
Both show the same stale last point Data is late or absent at the historian: collector offline, buffering backlog, or the tag is not collecting Troubleshoot the collector and the tag, not the chart
Flat line ends well before now on a slow-changing tag Deadband compression stores a point only on change Expect the flat tail; verify with a fast-changing tag

Also compare the browser's clock and time zone against the server. A skewed client clock shifts a relative window and shows up as missing recent data. If the tag itself has stopped recording while live values look good, that is a collector problem with its own trace, not a refresh setting.

Continuous scrolling at the monitor #

The web client chart updates in periodic steps; it has no play mode. When the customer wants a line that moves continuously the way the Client Tool does, the answer is to run the Client Tool in play mode on a Windows PC at the monitor — a fanless mini PC mounted behind the display handles a single trend without effort. The trade-offs:

  • Client Tool, play mode: continuous update, exactly the behavior being asked for; needs an installed client and a Windows machine at the point of display.
  • Web client chart, built-in refresh: periodic steps tied to the range; browser only, no client install.
  • Browser page auto-refresh: full page reload on a timer; flickers, can drop the session, and was found poor in responsiveness when tested. Use it only as a last resort, set no faster than the built-in cadence — a reload gains nothing over a refresh the chart already performs.

Keeping a kiosk display live #

A display-only monitor fails quietly: the picture freezes, the session lapses, or the tab stops running. Set the kiosk up so none of that happens:

  • Set the chart to a relative range such as the last hour, and save the view or its URL so the monitor reopens the same chart.
  • On the PC driving the display, disable sleep, screen blanking, and any browser power-saving or tab-suspension feature; a throttled tab pauses the refresh requests.
  • Confirm the login or session does not expire. When it lapses, the chart stops updating and may show a login page instead of the trend.
  • Leave the display untouched for several hours and confirm the data requests from the Network tab continue at the measured interval.
  • At the end of a refresh cycle, compare the chart's right-edge timestamp against the Client Tool for one tag. Matching timestamps confirm the display is live.

If the monitor reaches the client through a reverse proxy, session lifetime and timeout settings live there too — the reverse proxy setup for a historian web client covers that path. When the refresh works but the page itself takes too long to come up after a restart, the web client page-load diagnosis narrows down where the delay sits.

Questions asked

Does the web client chart refresh itself without a button click?

Yes, on an interval tied to the selected time range. Installations report roughly every 5 minutes on a last-hour view and about every 15 minutes on a one-day view, but current documentation no longer states these figures. Measure the real interval on your installation: open the browser's developer tools, watch the Network tab, and time the gap between consecutive chart data requests.

Can the web client chart scroll continuously like the Client Tool in play mode?

No. The web client chart updates in periodic steps when it re-queries; it does not scroll. For a continuously moving line at the monitor, install the Client Tool on a PC beside the display and use its play mode. The browser chart remains the simpler option when an update every few minutes is enough for the visualization.

Is a browser page auto-refresh extension a good workaround?

It works, but it reloads the whole application: the view flickers, the session can drop to a login page, and browser throttling can pause a background tab. If you use it at all, set the interval no shorter than the chart's built-in cadence, because a full reload gains nothing over a refresh the chart already performs. Engineers who tried it found it poor in responsiveness.

Why does my chart's line stay flat at the right edge?

Two usual causes. An absolute start and end time fixes the query window, so even a successful re-query returns the same picture; switch to a relative range such as the last hour. Or the tag stores a point only on change, so a slow-changing signal shows a flat tail. Verify with a fast-changing tag or compare the last stored timestamp against the Client Tool.

Keep reading

  • Troubleshooting

    Diagnose a slow historian web client page load on the server

    Capture the load in the browser Network tab with the cache disabled and split each slow request into connection, TLS, waiting and download phases. When waiting for server response holds most of the time, the historian web services are waiting on the shared SQL Server host: cap Max server memory, check disk latency, then send support a redacted HAR. The timing split, not the total load time, decides the cause.

    Edge computing and IIoT

  • How-to

    Expose a historian web client through a reverse proxy

    Forward a port, mapping the client-facing port 8069 to the web client site on port 32569, whenever a host-and-port URL is acceptable; use a rewriting reverse proxy only when the URL must carry a path such as /hcweb, because the web client returns local URLs and redirects that plain forwarding does not rewrite.

    Edge computing and IIoT

  • Troubleshooting

    Historian Client concurrent licenses on one RDS server

    Two users running five Historian Client applications on one RDS server consume two concurrent seats, because the Historian Client Desktop concurrent license is allocated per Windows session, not per application. Seats beyond the live-session count come from disconnected sessions still running clients; set a disconnected-session logoff limit on the RDS collection to stop them accumulating.