Troubleshooting
When eSync File Catcher stops, remote sync and SQL logging stop
Short answer
SQL logging from a Flexy 205 stops when the eSync File Catcher on the PC that runs eSync stops, even when eSync connection history still looks active. Start the File Catcher from the eSync application's own controls, then prove recovery with the Flexy synchronization status and one confirmed SQL Server write. A PC restart is not a fix: it worked once and failed on the next outage.
On this page
- Why did SQL logging from my Flexy 205 stop?
- Is eSync connection history proof that data reached SQL Server?
- How do I check whether the eSync File Catcher is still running?
- How do I confirm synchronization end to end?
- Will restarting the PC bring synchronization back?
- How much data did the outage cost me?
- What can stop the File Catcher again?
- What is the decision for each outcome?
- Questions asked
SQL logging from an Ewon Flexy 205 through eSync stops when the eSync File Catcher stops. In the reported case, eSync connection history still showed exchange activity while the Flexy configuration showed no synchronization, and the stopped File Catcher was the confirmed immediate cause. The recovery that works is to start the File Catcher again from the eSync application's own controls, then prove recovery with three checkpoints: the File Catcher running state, the Flexy synchronization status, and one confirmed write in SQL Server. A PC restart is not a fix — one restart restored the link once, and on the next outage a restart did nothing.
Why did SQL logging from my Flexy 205 stop? #
In the reported case, SQL logging stopped because the eSync File Catcher had stopped, which broke synchronization between the Flexy 205 and eSync; no separate fault showed on the Flexy, SQL Server, the network or the PC hardware, so the File Catcher state is your first check.
The chain is short. The Flexy 205 collects data at the machine, eSync synchronizes with the Ewon, and eSync delivers the result into SQL Server. The File Catcher is the eSync-side component in that chain, and when its process stops, delivery stops with it. The vendor's external device sync guide for eSync 2 is the reference for everything on the eSync side.
The timeline in the reported case is the pattern to recognize: logging ran for days, stopped, a PC restart appeared to fix it, and the stop came back. That pattern points at one state you can read, not at a dozen settings — and the state that coincided with the halt was the File Catcher having stopped.
Is eSync connection history proof that data reached SQL Server? #
No — a connection-history entry records an exchange attempt at the eSync end, and in the reported case it looked active while the Flexy configuration showed no synchronization, so history alone cannot prove that Flexy data was written to SQL Server.
A history entry tells you an exchange happened or was attempted. It does not tell you which rows landed in the database. When the two ends disagree, believe the end closest to the data: the Flexy's own synchronization status first, then a queried row in SQL Server. Record both statuses and the time of the check, because the disagreement itself is diagnostic.
This gap between a live-looking indication and a confirmed write is the same trap as why historian tags stop recording while live data stays good: the front of the pipeline looks alive while the record at the back went silent.
How do I check whether the eSync File Catcher is still running? #
Open the eSync application on the PC that runs it and read the File Catcher's own running state before touching anything else; the reported evidence names no Windows service name, executable or registry key for the File Catcher, so use the control surfaces the eSync application itself provides.
If it shows stopped, start it with the start control the application provides, then watch it through the next exchange interval instead of glancing once. Do not change unidentified settings merely because the process stopped — a wrong edit there destroys the diagnostic state you need. If the process starts and then stops again, that repeat stop is the most valuable observation you can capture; the record to keep is listed further down.
How do I confirm synchronization end to end? #
Verify three checkpoints in order — the File Catcher running state, the Flexy synchronization status shown in the Ewon configuration setup, and one confirmed write in SQL Server — and treat recovery as proven only when the third one passes.
- File Catcher running state. Read it in the eSync application on the PC that runs eSync. If it shows stopped, start it there and move on only once it holds.
- Flexy synchronization status. Read it in the Ewon configuration setup on the Flexy 205. The vendor's eSync 2 guide also has you confirm a completed exchange at the eSync application status, so verify at both ends, never one.
- One confirmed write. Query the target table for the newest timestamp of a tag you recognize. Successful login, provisioned schema and history entries all sit before the write; only the queried row confirms it. The SQL Server error log, viewable by Microsoft's documented procedure, helps you check what processes finished around the stop time. If SQL Server itself refuses connections after an outage, work through reconnecting an edge PC to SQL Server after connection loss before blaming the File Catcher.
If any two checkpoints disagree, write down both statuses and the time of the check. That separates a historical connection indication from a current successful transfer.
Will restarting the PC bring synchronization back? #
Treat a restart as a temporary recovery at best: in the reported case the first restart restored synchronization and a later restart left it dead, so a restart that works today proves nothing about the underlying cause and must never stand in for the three checkpoints.
A restart resets process state, which is why the first one appeared to work; it changes nothing about why the File Catcher terminated. Operationally that means two rules. Run the three checkpoints after every restart, including one that appears to work. And do not write "reboot the eSync PC" into your recovery procedure as the remedy — write the three checkpoints there and record the reboot as one input, not as the fix.
How much data did the outage cost me? #
Measure the gap between the newest timestamp eSync recorded and the newest timestamp actually present in the SQL Server table; in the worked example below the difference is 33 minutes of history that never reached the database.
Worked example with example values. You notice at 09:40 that logging has gone quiet. eSync connection history shows the last completed exchange at 09:40. The Flexy-side status says the Flexy 205 has not synchronized since 09:07. On the database side, query the target table for its newest timestamp: on an example table line1_counts with an example timestamp column event_time, SELECT MAX(event_time) FROM line1_counts; returns 09:07.
The arithmetic: 09:40 minus 09:07 is 33 minutes. If the Flexy logs one row each minute — an example logging period, not a documented default — the missing window corresponds to about 33 expected rows. Whether values from that window can still arrive later depends on how the Flexy's logging and buffering are configured; the reported evidence does not say, so treat any backfill as unverified until a queried timestamp shows it arrived. Run this same subtraction each morning against the newest SQL timestamp and it doubles as a cheap daily health check.
What can stop the File Catcher again? #
The reported evidence does not establish why the File Catcher terminated, so capture state at each stop instead of guessing: note the time, whether the PC had rebooted, whether the File Catcher could be started from eSync's own controls, and whether it stopped again afterwards.
The honest answer to "what are the possibilities" is that this case identifies none. Blaming the Flexy, SQL Server, the network or the PC without capture would be guessing. Make the next stop expensive to repeat by recording, at the time it happens:
- the stop time and the three checkpoint statuses at that moment;
- whether the PC rebooted between the last good exchange and the stop;
- whether a File Catcher start held or the process stopped again;
- any diagnostics or logs the eSync application exports;
- the newest confirmed SQL timestamp, so the data gap is quantified rather than remembered.
With that record, a repeated stop goes to the vendor's support channel as evidence rather than as a story. If the File Catcher runs steadily but the Flexy still reports no synchronization, the fault sits elsewhere — Flexy-side connection status or the path between the sites — and the eSync 2 guide is the reference for those checks.
What is the decision for each outcome? #
Decide by outcome: File Catcher stopped, start it and run the three checkpoints; it stays up and SQL writes resumed, fixed; it stops again, capture and escalate; it runs but the Flexy still shows no synchronization, chase the Flexy side and the network path.
| What you find | What it means | What you do |
|---|---|---|
| File Catcher stopped | The confirmed interruption cause | Start it from the eSync application's own controls, then run all three checkpoints |
| It holds and a queried SQL row is current | End-to-end recovery proven | Record the stop window and keep the capture list ready for a repeat |
| It stops again | Unresolved root cause on the eSync side | Send the captured record through the vendor's support channel |
| It runs but the Flexy shows no synchronization | Fault elsewhere in the chain | Check the Flexy connection status and the eSync exchange per the vendor's guide |
In every case the proof is identical: a File Catcher that stays up, a Flexy that reports synchronization, and a timestamp in SQL Server that advances. Keep the three-checkpoint habit and the next stop is found in minutes instead of days.
Questions asked
What is the eSync File Catcher responsible for?
Its state is what makes or breaks the delivery leg from the Flexy to SQL Server: when the File Catcher stops, delivery stops with it, and the fix belongs on the eSync side rather than in the Flexy configuration. In the reported case the stopped File Catcher was the confirmed immediate cause of the interruption.
Where do I read the Flexy's own synchronization status?
In the Ewon configuration setup pages of the Flexy 205, the same view that contradicted eSync connection history in the reported case. It is the device-side record of whether that Flexy completed synchronization, so read it together with the File Catcher state and a queried SQL timestamp; one end alone has already proven misleading.
How do I tell a completed connection from a delivered row?
A completed connection or exchange entry proves reachability at one end. A delivered row needs a query against the target table returning a timestamp you recognize inside the current logging window.
What should I send the vendor when the File Catcher stops repeatedly?
Send the stop times, the three checkpoint statuses at each stop, whether the PC rebooted between the last good exchange and the stop, whether a File Catcher start held, any diagnostics eSync exports, and the newest confirmed SQL timestamp. That record separates an eSync-side process fault from a Flexy, network or SQL Server fault without another round of guessing.
Can a stopped File Catcher corrupt the SQL tables?
Nothing in the reported case suggests wrong rows, only absent ones. When delivery resumes, compare the newest SQL timestamp with the newest eSync exchange before assuming the missing interval was filled late; the database query, not the connection history, tells you what actually arrived, and anything not present was not delivered.