IMD SolutionComputing LibraryShop main store

Explainer

Who owns the control network and DMZ between two companies

OT cybersecurity Published 7 min read

Short answer

Responsibility follows who administers the infrastructure, not the direction the data travels. Company A keeps its receiving PI environment and its boundary, Company B keeps its source servers and its boundary, and the connector host belongs to whichever organization runs it. Every firewall rule across a boundary is approved by the organization that owns that boundary.

On this page
  1. Ownership follows administration, not data direction
  2. What ISA/IEC 62443 calls the pieces
  3. The DMZ is a third zone with its own administrator
  4. Who runs the connector under each hosting arrangement
  5. The case: a relay in Company A's DMZ feeding Company A's PI server
  6. Writing the agreement down so the question stays closed
  7. Questions asked

When Company A asks Company B to send plant data into A's PI Server through a PI Connector, the ownership question has one answer: whoever administers each piece of infrastructure owns it, and the direction the data travels decides nothing. Company A administers its receiving PI environment and the boundary in front of it. Company B administers its source servers and its own boundary. The connector host belongs to whichever organization actually runs it, and every rule that crosses a zone boundary is approved by the organization that owns that zone. ISA/IEC 62443 gives these pieces their formal names, zones and conduits, and the worked case below lands the decision leg by leg.

Ownership follows administration, not data direction #

That Company B 'pushes' the data is a business outcome, not a network fact. Every connection has an initiating side and a receiving side, and the receiving side decides where the approval must come from. AVEVA's PI Connector documentation is explicit for this component: PI Connector Relay initiates a connection from the DMZ to PI Data Collection Manager in the control network, and positioning PI Data Collection Manager is what is required for the relay to make that initiation. So although B sends and A receives, the session terminates on A's control network, and A approves that rule no matter whose data it carries.

Keep three responsibilities apart, because they settle to different owners:

  • owning the data: Company B;
  • operating the transfer service: whichever organization runs the connector host;
  • authorizing traffic across each boundary: the organization that administers that boundary.

Company B can own the data while Company A operates the connector. Neither role gives either company authority over the other's firewall, and the word 'push' in an agreement never identifies which component initiates which session. The connector's documentation and its installed configuration do.

What ISA/IEC 62443 calls the pieces #

The standard models exactly this situation. A zone groups assets that share common security requirements, and a conduit is a logical or physical grouping of communication channels that connects two or more zones, carrying its own security requirements. The conduit between B's source zone and the DMZ is not the conduit between the DMZ and A's control network, and each has an owner on the side that receives its traffic.

Between two companies this means: A defines what may enter its control network and what may leave it toward the DMZ; B does the same for its source zone; the DMZ itself has exactly one administrator, fixed in the interconnection agreement rather than inferred from the data flow. Zoning holds only when it is drawn and enforced as a design, the same discipline behind segmenting edge platform networks for data, BMC and OS traffic.

The DMZ is a third zone with its own administrator #

An industrial DMZ is neither the IT network nor the OT network. It is a third zone with its own security policy, its own servers and its own administration. Whoever operates it controls its segmentation, which hosts are admitted, which rules change and when, and what is monitored there. That administrator is Company A if A built and runs the DMZ, Company B if B does, or a contracted third party; the agreement decides, not the data flow.

Two corollaries settle most of the argument in advance. A server holding plant-related data is not automatically part of a control network; its zone comes from the network diagram and the routing, not from what it stores. And a requirement that Company B must deliver does not put the DMZ under B; only administration does.

Who runs the connector under each hosting arrangement #

Three arrangements cover every deployment of this kind, and the criterion is the same each time: where the host sits, who administers it, and whether the connector's documented connections fit both zones' policies.

  • Connector host in Company A's environment. A administers the host, its placement, access to the receiving PI and the A-side boundary; B supplies source access, source credentials and its zone's policy. This works when the connector's supported topology can reach B's source across an approved interconnection.
  • Connector host in Company B's environment. B administers the host and the B-side boundary; A grants the connector's documented destination connections into its receiving PI. This works only if A's policy accepts sessions initiated from B's territory. Many receiving-side policies refuse that, which is why the DMZ relay pattern exists.
  • Host run by a contracted third party. The contract assigns host administration, the service account, certificates, monitoring and incident handling; each company authorizes access only to its own zone. The contract decides ownership here, not the diagram.

Prefer a clearly assigned host inside an existing managed environment over shared, informal administration, and name one organizational role as the transfer service owner even when another team operates the host.

The case: a relay in Company A's DMZ feeding Company A's PI server #

Take the arrangement as posed. The inputs:

  • Company A runs its receiving PI Server on its control network (given by the deployment).
  • Company B holds the source data on its own servers (given by the deployment).
  • The relay component sits in a DMZ, and the connector documentation sets the initiation direction: the relay initiates its connection from the DMZ to PI Data Collection Manager in the control network (AVEVA's PI Connector documentation).
  • Illustrative addresses: B's source server 192.168.60.20 in B's source zone, the relay host 192.168.50.10 in the DMZ, and PI Data Collection Manager at 10.1.20.15 in A's control network. The service and port on each leg come from the connector's documentation for the deployed version, never from the word 'push'.

The rule, in words: the organization that administers the zone receiving a session's initiation approves and enters that zone's firewall rule, scoped to the exact initiating address, the exact destination address and the exact service. No one edits a firewall they do not administer.

Worked leg by leg:

  • Leg 1, relay to source: 192.168.50.10 initiates toward 192.168.60.20. The receiving zone is B's source zone, so B approves and enters that rule on its own boundary.
  • Leg 2, relay to destination: 192.168.50.10 initiates toward 10.1.20.15. The receiving zone is A's control network, so A approves and enters that rule on its own boundary.
  • The host: 192.168.50.10 sits in the DMZ, which A administers in the common receiving-side pattern. A installs, patches, monitors and restores the relay; B supplies the connector software, the source credentials and product support for its own server.

Result: two conduits, two approvals, one host owner. B approves one rule, A approves one rule, and neither company holds an account on the other's firewall.

Decision, with its threshold: if a session's initiation lands in your zone, your organization approves that rule; if a host sits in your zone, your organization administers it. Applied here, Company A owns the control network, the DMZ, the relay host and the DMZ-to-control-network rule, and Company B owns its source zone and the relay-to-source rule. If either side's policy refuses its leg, the connector host moves and the legs are worked again with the new addresses; the ownership logic does not change with them.

Writing the agreement down so the question stays closed #

Record five things and the ownership argument never reopens:

  • the path: every zone from B's source server through the connector host to A's receiving PI, with the administering organization marked on each component;
  • the legs: initiating host, receiving endpoint, transport, service and port, taken from the connector documentation and the installed configuration;
  • the approvals: A authorizes A-side access and B authorizes B-side access, each scoped to documented endpoints and services and never to whole networks; the same discipline as remote SCADA access through firewalls and proxies;
  • the service owner: who installs and updates the connector, holds the service account, renews certificates where used, monitors delivery and restores service after host failure; a successful connectivity test is no substitute for this name;
  • the acceptance test: write a known value and timestamp at B's source, then confirm that tag, value and timestamp at the PI destination; a connectivity check proves reachability, and a confirmed write proves delivery.

An account list or a vendor portal role is not endpoint authorization; remote access gateways do not identify approved service PCs, so name the addresses instead. Any management interface exposed across the boundary rides behind an approved rule, the same way web server access belongs behind approved network rules.

One safety rule stands above the paperwork: never widen a rule between the two companies' networks to speed up troubleshooting, because a broad intercompany opening defeats the zoning the DMZ exists to provide.

Where the two organizations still cannot agree who administers a shared asset, the dispute is contractual rather than technical, and the same resolution logic applies as in control system IP ownership disputes between engineer and client.

Questions asked

Can Company B hold administrator rights on Company A's firewall so it can manage its own rule?

No. The organization that administers a boundary keeps the only administrator accounts on it. Company B receives a rule scoped to the relay host's address and the connector's documented service; when that rule must change, B requests the change through A's change process and A enters it. Shared firewall administration across company lines removes the separation the DMZ provides and leaves no single organization accountable for the rule base.

Who runs the DMZ if neither company wants the job?

Contract a third party and put the duties in the agreement: host administration, the service account and its credentials, certificate renewal where used, delivery monitoring, incident response and restoration after host failure. Each company still authorizes access only to its own zone and names one organizational role as counterpart to the provider. If nobody contracts for the zone, the transfer should not be built; an unowned DMZ is an unmanaged one.

Does a data diode remove the ownership question?

It narrows it. A one-way diode enforces that no return connection can be initiated into Company A's control network, which suits a publish-only feed. It does not suit a connector that needs acknowledgments, retries or remote management, and the diode itself, its allow rules and the documented procedure for applying updates still need a named administrator on one company's side. The boundary shrinks; the ownership question stays.

A tag on a screen is stale, whose problem is it?

Work from the destination backwards before anyone opens a cross-company ticket. Read the tag in the receiving PI environment itself: if it holds current data, the fault sits in the display binding or client access, which Company A's side owns. If the point is stale, compare its last timestamp with the source server's and read the connector's diagnostics. Each level belongs to a different organization's support scope, so record where the failure sits first.

What changes if the connector host moves from the DMZ into the control network?

Every leg is worked again from the new host address. The session would then initiate inside the control network toward B's source, so B would need to approve an inbound rule arriving from A's plant zone, a crossing most OT policies refuse because a compromised connector host would hold a live session into the control network. That refusal is why the relay sits in the DMZ, keeping the inbound leg short and scoped.

Keep reading

  • Explainer

    Why remote access gateways do not identify approved service PCs

    A remote access gateway authenticates two things: the account and the target device. The PC running the client is never checked, so an approved-service-PC requirement cannot be met inside the gateway. Terminate a VPN with client certificates in front of it, keep a source-IP allowlist as a coarse filter, and segment so a compromised client reaches only its machine LANs.

    OT cybersecurity

  • How-to

    Networking a DOS CNC control to Windows 10 safely

    Connect the DOS control to a dedicated Windows 10 Ethernet adapter, leave that adapter on its public (unidentified) profile, serve one shared folder over SMB1 on a static 192.168.10.0/24 link with no gateway, and allow inbound SMB only from that subnet. The shop side keeps its private profile and firewall, the control maps the share as F:, and the whole link stays off the internet.

    OT cybersecurity

  • Troubleshooting

    Ping works but PLC program download fails over remote access

    ICMP success proves only the routed IP path, not the programming session. A download opens separate query and download connections on documented TCP and UDP ports, and broadcast discovery does not cross a routed VPN. Point the controller's default gateway at the remote-access router LAN address, permit both programming ports to the controller LAN IP, and add the controller manually by IP.

    Remote access and virtualization