IMD SolutionComputing LibraryShop main store

Troubleshooting

Why a historian report template lacks identification fields

Edge computing and IIoT Published 4 min read

Short answer

The Historian Analysis templates in Report Engine v10 expose four columns: variable, timestamp, value and status flags. Neither they nor the Historian Trend Analysis template offer Identification or Resource Labels, and no template setting adds them. Pull that metadata through the archive's documented data-access layer into a custom report, or escalate to the vendor with the exact version and field list.

On this page
  1. What the Historian Analysis template exposes
  2. Why column settings cannot add the fields
  3. What switching templates gets you
  4. Checking a six-field report against the four exposed columns
  5. Where the missing fields must come from
  6. Verifying any answer before you rely on it
  7. Questions asked

Report Engine v10 gives the Historian Analysis templates exactly four selectable columns: variable, timestamp, value and status flags. Identification and Resource Labels are not among them, the Historian Trend Analysis template does not expose them either, and no template setting in this version adds a field the underlying mapping does not retrieve. Those two items are archive-side metadata, so the report gets them by reading the archive through its documented data-access layer and joining them into a custom report, or by raising a supported-customization request with the vendor. Below is the check that establishes the limit, the arithmetic that sizes the gap, and the two paths that close it.

What the Historian Analysis template exposes #

The Historian Analysis templates in Report Engine v10 present a fixed set of selectable columns:

  • variable — the archive variable or tag each row belongs to
  • timestamp — the time the sample was stored
  • value — the stored sample itself
  • status flags — the quality and state bits recorded with that sample

Identification and Resource Labels do not appear in that list. That set is specific to this version of the templates; another release can expose a different list, so read the column picker of the release you actually run. Exposing a slice of what the archive holds is normal behavior for a configuration tool, not a fault — the same pattern explains why historian configuration shows only system tags.

Why column settings cannot add the fields #

A report column can only display a field the template's data mapping has already retrieved. The Historian Analysis mapping reads the time-series stream — variable, timestamp, value, status flags — while Identification and Resource Labels are attributes attached to the archived objects, not samples in that stream. A layout option that makes a column visible changes what is printed, not what is fetched: the mapping never requests those attributes, so a column added in the layout stays empty. That is why the setting you are looking for does not exist at template level, and why no arrangement of columns retrieves the metadata.

What switching templates gets you #

The only configuration-level alternative is another supplied template with a different column set. The Historian Trend Analysis template was checked field by field in this deployment and contains neither Identification nor Resource Labels, so the switch changes formatting, not coverage. The rule before rebuilding anything: open the candidate template's column picker and check every required field against it. A switch pays only when the missing column actually exists there; otherwise you have rebuilt the same report with the same gap.

Checking a six-field report against the four exposed columns #

Inputs, each with its source:

  • Required fields: 6 — variable, timestamp, value, status flags, Identification, Resource Labels, taken from the reporting requirement.
  • Selectable columns in the Report Engine v10 Historian Analysis template: 4 — variable, timestamp, value, status flags, read from the template's column picker.
  • Historian Trend Analysis template: Identification and Resource Labels absent, confirmed field by field.

The rule in words: a template satisfies a report only field by field. Count the required fields that exist as selectable columns; the remainder is the gap no template setting can close.

The arithmetic, written out:

  • 6 required fields − 4 matched columns = 2 unmatched fields: Identification and Resource Labels.
  • 4 matched ÷ 6 required ≈ 0.67, so about 67 percent of the requirement sits inside the template.
  • After the switch to Historian Trend Analysis the same 2 fields are absent, so the gap stays at 2.

Decision: at a gap of 0, finish the report inside the template. At a gap of 1 field or more, stop adjusting columns and move the missing fields outside the template. This requirement sits at 2, so the work goes to the data-access path or the vendor request.

Where the missing fields must come from #

Two paths close a gap the templates cannot:

  • Read the metadata through the archive's documented data-access layer. The values and the Identification and Resource Labels attributes both live in the archive, so a custom report built on the documented access method can select both and join them on the variable. The pattern is the same one behind exposing historian latest values over OPC UA or MQTT: one documented interface on the archive, read by your own client.
  • Raise it with the vendor's support team as a customization question, sending the four facts listed above and asking whether a supported template, customization or data-access method exposes those fields for archive data.

Verifying any answer before you rely on it #

Whichever path produces a candidate report, generate it and confirm each requested field carries the expected archive-associated information for a known variable. A visible column with empty cells is a layout change, not a delivered field. Keep the working four-column report in service until the replacement reproduces it, so a failed experiment never leaves the plant without its data.

Questions asked

Can I add custom columns to a Report Engine v10 Historian Analysis template?

Not by any procedure documented for this version. The template offers variable, timestamp, value and status flags, and a column added in the layout stays empty because the data mapping never requests the extra attributes. Column visibility and data retrieval are separate things; only the second one fills a field.

Does the Historian Trend Analysis template include Identification and Resource Labels?

No. It was checked field by field in the deployment that raised this question and contains neither. Template switching only helps when the column you need exists in the other template's picker, so open that list and compare every required field before rebuilding the report around it.

What information should I send the vendor's support team?

Four items: the data source is the historian archive; the software is Report Engine v10; the required fields are Identification and Resource Labels; the Historian Analysis and Historian Trend Analysis templates were both checked and neither exposes them. Then ask directly whether a supported template, customization or documented data-access method exposes those fields.

Where do Identification and Resource Labels actually live?

On the archive side, as attributes of the archived objects rather than samples in the time-series stream the analysis templates read. Any report that shows them has to fetch them from the archive through a documented access method and join them to the values on the variable.

How do I prove a proposed fix actually delivered the fields?

Generate the report and read the cells for each requested field. A field is delivered when it carries the archive-associated information you expect for a known variable; an empty column means only the layout changed. Run this check before retiring the working four-column report.

Keep reading

  • Troubleshooting

    Edge trend shows no historian data: fix the doubled SELECT

    The trend stays blank because a complete SELECT statement was pasted into the Table field, so the gateway wraps it in its own SELECT ... FROM and SQL Server rejects the result as incorrect syntax near the keyword select. Put only Runtime.dbo.History in Table, carry DateTime, TagName and Value in the column controls, and move TagName = 'SysTimeSec' into the filter control.

    Edge computing and IIoT

  • Explainer

    Log one-second trends and one-minute reports in one historian

    Yes. One historian archive serves both rates: keep the one-second acquisition for trends and add either a second one-minute logging schedule on the same tag or a one-minute aggregate computed from the one-second records. Choose the aggregate for sums and averages, the second schedule only when the report must acquire its own minute value; one-second logging stores 60 times the records.

    Edge computing and IIoT

  • Troubleshooting

    Why the Expression option is missing in Historian Web Client

    The Expression control in the Web Trend interface is licensed content: it appears only when the active license reports the Advanced Historian feature as licensed. An administrator account adds permissions, not entitlement, and the 2023 R2 SP1 upgrade did not remove the feature. When the license includes Advanced but the control stays hidden, re-run Historian Search in the AVEVA Configurator and reboot.

    Edge computing and IIoT