Edge computing and IIoT Published 7 min read By IMD Solution engineering team

Short answer

A Perspective Edge Power Chart that alternates between its populated view and an empty chart on Ignition 8.1.17 was traced to a space in the configured project name. Remove the space in the Gateway configuration's Project Name field, retest with the same tag in a fresh session, and keep the historian untouched. An underscore-only project name on Edge 8.1.47 that still flashes is a separate, unresolved case: reproduce it and escalate to the vendor.

On this page
  1. Why does a Power Chart on Perspective Edge flash between two chart states?
  2. How do you tell a chart fault from missing historian data?
  3. Which Gateway setting stops the Power Chart flashing?
  4. How do you change the project name without breaking project access?
  5. What if the project name has no space in it?
  6. Why does reinstalling Ignition not stop the flashing?
  7. Questions asked

A Perspective Edge Power Chart that swaps between its populated trend and an empty chart is, in the reported cases, not a failing display and not missing history: on Ignition 8.1.17 the trigger was a space in the configured project name, and removing that space stopped the flashing without a reinstall. The symptom starts when a historized tag is selected, follows any tag rather than one bad tag, survives client restarts, and leaves the Gateway logs quiet, which is why it gets misread as a historian outage. Work the checks in order: separate display from data, edit the project name as a single controlled change, prove the chart stable, and handle the underscore-only Edge 8.1.47 report as its own case.

Why does a Power Chart on Perspective Edge flash between two chart states? #

A space in the configured project name was the reported trigger on Ignition 8.1.17: a Power Chart with one historized tag alternated between its populated chart and an empty chart, and removing the space stopped the flashing.

The Perspective component manual describes the Power Chart as collecting and drawing data from the pens configured on it, so selecting a pen starts the chart's history query and redraw work. The reported flashing began exactly at that point, which identifies a trigger rather than a defective tag: the chart misbehaved with the first tag that was added, then with any other tag, and it sat still with no tags selected. The same view flashed in the Designer and in the running session, and the Gateway logs showed nothing. A quiet log is not proof of health, because rendering and request failures on the client side can occur without a matching Gateway error entry.

How do you tell a chart fault from missing historian data? #

A chart that flashes while another display still serves the same tag's values is a display fault, and the quickest separator is the empty selection: with no tags selected the reported chart stayed stable, which points the investigation at the chart and its project configuration.

Run these checks before touching the historian:

  • Select a different historized tag. The reported flashing followed every tag; when a symptom is not tag-specific, stop editing pens and look at project-level configuration.
  • Clear all tags from the chart. A stable empty chart confirms that an active trend selection triggers the symptom; treat that state as diagnostic, not as a repair.
  • Reload the session or restart the client. A project-level configuration fault stays after the client reconnects, so a fresh session that still flashes points away from stale client state.
  • Query the same tag through another history display. Values there mean the historian is collecting; nothing anywhere moves the fault to collection.
  • Read the Gateway logs during a reproduction, and record the result even when it is silent.

If the same tag shows nothing in any display, move to the collection side: historian trend empty: PLC tag collection troubleshooting covers that path. Blanking also has documented data-side causes unrelated to naming, and why a slow tag blanks the Easy Chart after bad quality is one of them; neither matches the reported flashing, which left the historian serving data. Keep the logging configuration untouched through all of this, because changing logging or deleting history mid-test destroys the comparisons that separate a rendering fault from a data fault.

Which Gateway setting stops the Power Chart flashing? #

The setting is the project's own name: the Project Name field in the Gateway configuration, reported on 8.1.17 under Gateway > Config > Gateway Setting > Project Name, and the space in that value is what sets the chart flashing.

Read the current value before editing anything else, and keep two names apart: the configured project name is the identifier that project resources resolve against, while a visible page title is only a label. That is why a naming defect can reach a component whose own configuration is valid. If your build's menu differs from the reported path, find the Project Name field in the Gateway configuration's settings area and change nothing else on that page.

How do you change the project name without breaking project access? #

Back up first, change only the name, and retest with the same tag in a fresh session: the reported repair left the historian and the chart configuration untouched, so the space removal was the only variable when the chart held steady.

  1. Back up the Gateway configuration and export the affected project with the built-in backup and export functions. Write down the exact current Project Name value.
  2. List what depends on the name: launch links, Workstation shortcuts, and any reference that embeds the old name. Schedule the edit for a window when no operator session depends on that chart, because a rename can drop running sessions, and give operators a verified alternative trend display for that window.
  3. Open the Project Name field under Gateway > Config > Gateway Setting > Project Name and delete the space. Save, and change nothing else on the page.
  4. Update the dependent references from the previous step to the new name.
  5. Launch a fresh session through the operator's normal path, select the same historized tag, and watch through several cycles of the previous flashing period: the pen stays present, values keep drawing, and changing the time range does not blank the chart. Repeat in the Designer and in the running session.
  6. Keep the change only when the chart and normal project access both pass. If access breaks, restore the recorded name and configuration from the backup through normal administration instead of editing further.

What if the project name has no space in it? #

An Edge 8.1.47 project whose name used underscores instead of spaces kept flashing, so the space-removal repair does not cover that case, and underscores are not established as a cause by that report.

Treat it as a separate reproduction, not a second application of the same fix. Do not rename underscores out expecting the flashing to stop; nothing in the reported cases shows that it helps. Capture the installed version, the exact project name, the behavior in the Designer and in the running session, and a short recording of the flashing with a tag selected and with none; add the Gateway logs even when they are quiet, and open a support case with the vendor carrying all of it. While that case is open, run a verified alternative trend display so production trending does not wait on the investigation, and leave the historian configuration alone so the case keeps its evidence.

Why does reinstalling Ignition not stop the flashing? #

A reinstall was the step the reported installation wanted to avoid, and it is the wrong first move: reinstalling does not necessarily change a retained project name or other retained configuration, so it spends downtime without touching the documented trigger.

The reported repair ended at a single field edit, so make the name check the rule and keep reinstall as a later step only when the vendor's support directs it for its own reasons. Keep version expectations grounded too: the reported cases define no complete affected range and no correcting build, and the separate flashing report on Edge 8.1.47 shows that a space-free name does not clear every case. Read the installed version from the Gateway web interface and put it, the exact project name, and the reproduction steps into any report; that is what turns an observation into something support can act on.

Reported condition Decision
Ignition 8.1.17, flashing with any historized tag selected, space in the project name Remove the space at the Gateway level, retest with the same tag in a fresh session, and keep the change.
Flashing in both the Designer and the running session Change the project name once; do not chase tags, pens, or individual clients.
Edge 8.1.47, underscore-only project name, still flashing Separate case: reproduce with logs and a recording, escalate to the vendor, and run a verified alternative trend meanwhile.
Values missing in every history display, not only the chart Collection fault: investigate the tag's historize settings and historian access before touching the chart.

That is the whole decision. Space in the name and flashing with a tag selected on the reported build: remove the space and prove it. No space and still flashing: reproduce and escalate. History missing everywhere: fix collection first, because the chart is not the fault.

Questions asked

What does the flashing cycle look like when it happens?

The populated chart with the selected tag's history stays visible for roughly a second, then an empty chart state flashes for a split second before the populated view returns. The cycle repeats as long as a tag stays selected, and it appears in the Designer and in the running session, whether that session runs in a browser or in Workstation.

Is there an Ignition release that fixes the flashing?

No fixed release is documented in the reported cases. One installation on 8.1.17 stopped flashing after the project-name edit, and a later Edge 8.1.47 case kept flashing with an underscore-only name, so the affected range and any correcting build are unknown. Read the installed version from the Gateway web interface and include it, the exact project name, and a short reproduction in a support case to the vendor.

Does a space in the project name break anything besides the Power Chart?

The reported cases document only the Power Chart flashing while a historized tag is selected. No documented list ties project-name spaces to other Perspective faults, and the reported installations named no second symptom. After a rename, test the views and data connections your operators actually use, because a project identifier participates in resource resolution beyond one chart.

Should new projects avoid spaces in their names?

Yes on the builds where this was reported: a name without spaces removes the one documented trigger for the flashing. That does not clear the Edge 8.1.47 case, which kept flashing without any space, so treat a space-free name as the first prevention step rather than a guarantee, and reproduce with logs any flashing that survives it.

Keep reading

  • Troubleshooting

    Fix Ignition SQL Server connection faults after an upgrade

    After an Ignition 8.1.x upgrade, a faulted SQL Server connection is almost never a credentials problem: the new Java runtime disables TLS 1.0 and 1.1 (builds from 8u291), and a Microsoft JDBC driver as old as 4.0 cannot run on it. Read the Gateway exception, then patch SQL Server to TLS 1.2 per KB3135244 or replace the driver; the reported working pair was 9.4 in place of 4.0.

    Edge computing and IIoT

  • Troubleshooting

    PowerChart component error on empty DB Table Historian data

    A PowerChart component error on a DB Table Historian query has two reported triggers: a query that returns no records while pointCount is -1 or 0, the settings that prevent interpolation, and a date range so narrow that rangeStartDate and rangeEndDate become the same timestamp. Recover by selecting a timeframe with data and re-adding the pen, or adding another pen to force a re-render. Keep pointCount unchanged and send the browser console error to support.

    Edge computing and IIoT

  • Troubleshooting

    Fix Ignition custom historian aggregates that return zeros

    A zero-filled result from an Ignition custom historian aggregate means the callback failed, not that every stored value was zero. The Gateway log names the cause: NameError: global name 'shared' is not defined, raised in pyaggimpl. Select the project that contains your aggregate's script library as the Gateway Scripting Project, publish it, and rerun the query.

    Edge computing and IIoT

Suspended and locked on a redundant Process Historian pair