Why an Edge and Standard gateway pair is not high availability

Edge computing and IIoT Published 8 min read

Short answer

Sync Services between an Ignition Edge gateway and a Standard Ignition gateway is a resumable one-way copy of history, audit records and alarm journal entries — buffering, not failover. Nothing decides which collector is authoritative, so two connections to one PLC duplicate alarms and split history into series that never merge. Assign one history and one alarm owner per PLC, and accept that Edge hardware failure leaves a gap, not a takeover.

On this page
  1. What Sync Services does, and what it does not
  2. Two independent collectors on one PLC
  3. Why every alarm fires twice
  4. Why the two histories never merge
  5. What an uplink outage costs, and what bounds it
  6. When the Edge gateway itself dies
  7. The decision for each case
  8. Questions asked

An Ignition Edge gateway synchronized to a Standard Ignition gateway is a buffering architecture, not a high-availability one. Sync Services is a resumable, one-way copy of data the Edge gateway has already collected, and nothing between the two gateways decides which collector is authoritative. When both poll the same PLC, each raises its own alarms and writes its own history, and the two histories never merge. The decision: give each PLC one history and one alarm owner, treat the uplink as the protected resource, and accept that the Edge device itself has no takeover — only a gap. Covering node failure takes a true redundant pair.

What Sync Services does, and what it does not #

The Ignition User Manual documents the scope in one line: Sync Services synchronizes historian data, audit records and alarm journal entries from the Edge gateway to a Standard Ignition gateway. Sync Services keeps track of where it is in the backlog, so after a link failure it resumes from where it stopped and delivers the stored data into whichever history provider you configured to receive synced data. That is the entire mechanism: a one-way, resumable copy of records the Edge gateway already produced.

It coordinates nothing at the source. There is no shared tag state between the two gateways, no election of an active node and no handover of driver connections. Coordinated OPC tag behavior — one node active, a second node taking over the same tags — belongs to a true redundant Ignition pair, a licensed capability of standard Ignition; the plant-level version of that design is two redundant historians behind redundant SCADA gateways. Edge plus Standard answers a different threat: the plant network.

Two independent collectors on one PLC #

When both gateways connect to the same PLC, each opens its own driver connection, builds its own tag values, evaluates its own alarms and writes its own history. Neither knows the other exists. Every hop carries its own failure mode:

Hop Carries Breaks when Result
PLC to Edge driver Live polling on the local segment Local cable, switch, Edge hardware or OS failure Edge tags go bad quality; no local history, no alarms
PLC to Standard driver Live polling across the plant network Plant network fault Standard tags go bad quality; no central history for those tags
Edge to Standard Synced history, alarm journal, audit records WAN or backbone fault Edge keeps storing locally; sync resumes when the link returns
Standard to clients Trends, alarm tables, displays Server or client network fault Operators lose the central view

Decide ownership per PLC before changing any configuration. One gateway collects history and evaluates alarms for each point; the other either does not connect to that PLC or connects for live view only. To audit this, open the device connection status on each gateway and list every connection in three columns: PLC address, gateway, role (history, alarms, live view). Any PLC that shows two gateways holding the history or alarms role will duplicate.

Why every alarm fires twice #

An Ignition alarm belongs to the gateway that evaluates it; its identity is the source gateway plus the tag provider plus the tag path. Both gateways see the same PLC bit and each raises its own event. The Edge event then arrives centrally through the sync, where it is treated as a separate alarm because it comes from a different source. That is correct behavior for two independent collectors, not a fault — and it is a safety problem, because an operator who acknowledges one copy leaves the other active and unseen.

Worked example, with assumed inputs: one PLC raises 40 alarm occurrences during a shift. Two evaluating gateways produce 2 × 40 = 80 events, and after the sync the central journal holds 80 records. Operators clear the copies they can see on one path; 80 − 40 = 40 remain active on the other path until someone finds the second owner.

The fix is ownership. Keep alarm definitions only on the gateway that owns the point — normally the history owner — and remove or disable them on the non-owning gateway. If both sides share a UDT, bind the alarm enable property to a parameter and set it false on the non-owning side. Where two Edge gateways cover overlapping equipment, split the definitions by equipment so each machine alarms on one gateway. Test it by forcing a condition in the PLC: the central alarm status table must show one active event and the journal one record. If instead a single event appears twice from one source, that is a different fault — see why an Ignition alarm journal logs every alarm twice.

Why the two histories never merge #

Synced history keeps its origin. Data collected by the Edge gateway is stored under the Edge gateway's history identity, and the Standard gateway's tag for the same PLC address has a different path. Nothing de-duplicates or splices the two, so:

  • A trend pen bound to the Standard tag never shows Edge-collected samples.
  • One physical point appears as two separate, overlapping series.
  • During an outage, the Edge series goes flat centrally until the backlog lands.

Keep one series per point. When the Edge gateway owns a point's history, do not historize that point on the Standard gateway, and bind the central charts to the synced Edge history path. When the uplink drops, the pen shows a gap; after the sync catches up, the same pen fills in — no provider switch and no chart reconfiguration. Check it by browsing the historical tags in the central trend component: each physical point must appear once. A point listed under both histories means history is still enabled on the non-owning side.

An uplink outage is the case this design is for: the Edge gateway keeps collecting into its local store, the sync holds its place in the backlog, and when the link returns the data flows to the receiving provider and the central gap closes with no loss — provided the local store still holds the oldest samples. The store is finite, and the retention limit is documented for each Edge version in the Ignition User Manual. Commit your design against that number: the longest outage you ride through must be shorter than the documented retention. If your worst-case outage is longer, this architecture does not meet the goal, and no setting changes that. The configuration side is covered in setting historian pruning and retention for Ignition tag history.

Worked example, with assumed inputs: a 37-minute uplink outage at 1-second logging holds 37 × 60 = 2,220 samples per tag in the backlog. With 300 owned tags that is 2,220 × 300 = 666,000 samples to push after reconnect. The drain time depends on the link and is not worth predicting; what matters is that every sample still exists as long as the outage fits inside the retention window.

Prove it at the physical layer: unplug the Edge uplink for a timed interval of several minutes, reconnect, wait for the backlog to clear, then query the central historian across that interval. The data must be continuous, with no gap where the cable was out.

When the Edge gateway itself dies #

Here the architecture has no answer, and the honest decision follows from that. When the Edge gateway stops, nothing polls the PLC. The Standard gateway cannot take over transparently because it has no knowledge of the Edge tags' state, alarm status or ownership. The options trade gap coverage against duplication:

Option Behavior while the Edge gateway is down Duplication Depends on
A. Edge is the sole collector History gap, no alarms, no live values None Edge hardware only
B. Standard also polls, live view only Operators keep live values; the history gap remains None The plant network, the same one that already fails
C. Both gateways historize Coverage continues only while the plant network is up Two non-merging series and duplicate alarms unless ownership is enforced Plant network plus ownership discipline

Option C buys little: it covers Edge death only when the network is healthy, and it reintroduces exactly the duplication this design exists to avoid. Commit to A or B. Under either, the gap ends when the gateway — or its replacement, another fanless edge box PC — is back and its drivers reconnect. If losing data or live values for the repair time is unacceptable, the requirement is node-failure coverage, and the answer is a true redundant pair, not a second collector on the same PLC.

The decision for each case #

Three cases cover every variant of this question.

Frequent network outages, reliable Edge hardware. Edge owns history and alarms for its PLCs; the Standard gateway connects live-view only or not at all; Sync Services targets one receiving provider; the documented local retention must exceed the worst outage. This is the design Edge sync exists for.

Edge node failure must not interrupt collection or live values. Edge plus Standard cannot deliver it — there is no takeover. Use a true redundant pair on a network made redundant (redundant branches under a spanning-tree protocol is the usual plant fix), or accept option B's gap and keep a spare edge gateway box powered and imaged.

Both threats in one plant. Fix the network first. With redundant network paths, a standard redundant pair covers both failure modes, and the Edge-plus-Standard duplication problem disappears with it.

One rule holds in all three cases: one history owner and one alarm owner per PLC. Everything else in this article follows from it.

Questions asked

Does Sync Services copy anything from the Standard gateway back to the Edge gateway?

No. The synchronization documented for Ignition Edge runs one way only: records move from the Edge gateway to the Standard side and nothing is pushed back. The Edge gateway therefore never becomes a warm standby for the central system, and its local tag values are not updated from the central gateway.

Is this the same fault as an alarm journal that logs one event twice?

No. Two owners on one PLC produce two alarm events with two different source gateways, and acknowledging one leaves the other active. A journal that writes one event twice repeats rows for a single event from a single source. Check the source on the journal records: two sources means two owners and the fix is ownership; one source means a journal fault on that gateway.

What happens to the backlog if the Edge gateway fails while the uplink is still down?

It is lost with the device. The local store and the sync backlog both live on the Edge gateway, so a device failure during a network outage takes the collected-but-unsent samples along with future collection. Store-and-forward cannot backfill samples that were never forwarded, which is why the repair-time gap under a sole-collector or live-view-only design is unavoidable.

Do I need the redundancy license for Sync Services to work?

No. Sync Services belongs to the Edge edition and needs no redundancy license; it moves records from the Edge gateway to the Standard gateway on its own. The redundancy license is what coordinates a master and backup node in a true redundant pair. They cover different failures: sync rides out link outages, redundancy rides out node failures, and only redundancy gives takeover.

Keep reading

  • Explainer

    AVEVA Historian Connector redundancy options explained

    AVEVA Historian Connector v3.1 does not manage failover between redundant Historians. For collection redundancy, run two Connectors, each writing to its own Historian, with configurations you keep identical by procedure; use Historian partner and client failover only to cover temporary access loss.

    Edge computing and IIoT

  • Selection guide

    Choosing a PI System to Oracle integration route with validation

    With read-only PI access and cleansing owned by the receiving side, pull AF assets and status with the PI OLEDB Enterprise Provider through SSIS into a staging SQL Server, qualify transitions there — reject momentary interruptions and anything older than 2 hours — then write Oracle. Event Frames and the RDBMS interface need PI-side configuration or tag-based mapping that loses AF context.

    Edge computing and IIoT

  • Selection guide

    Choosing an edge data path for periodic records

    For independent periodic samples, Tag Historian with Edge Sync Services is the reliable path and buffers 35 days locally. For one atomic row per collection cycle, use MQTT Transmission records landing in MQTT Recorder. For true transaction groups, license a standard gateway for that node.

    Edge computing and IIoT