Whether an S7-1500 Software Controller runs on an IPC is decided per model and configuration, not per IPC family: CPU 1507S and CPU 1508S have different approved lists, IPC427D and IPC477D need a Core i3 or higher, the failsafe editions need NVRAM on listed models, RAID and NVMe configurations of four models are excluded, and the IPC327G is blocked at both the hypervisor and TIA Portal.

On this page
  1. What decides whether an S7-1500 Software Controller runs on an IPC?
  2. Which IPC models are approved for each software CPU?
  3. Does the processor inside the IPC change the approval?
  4. Why does the failsafe edition need NVRAM?
  5. Which RAID, NVMe and slot configurations are excluded?
  6. Why will the Software Controller not run on an IPC327G?
  7. Which controller release and TIA Portal version does your project need?
  8. How do you narrow the list to one approved host?
  9. Questions asked

The S7-1500 Software Controller, CPU 1507S and CPU 1508S, is approved per IPC model and configuration, not per IPC family. The delivery releases for V21.8 and V21.9 show why one family splits: the controllers list different hosts — the first carries the longer list, the second the shorter one — the IPC427D and IPC477D need a Core i3 or better, the failsafe editions need NVRAM on part of the list, RAID and NVMe configurations on the IPC627E, IPC677E, IPC647E and IPC847E are excluded, and the IPC327G is blocked twice over. Below is each check with its documented list, the arithmetic that narrows the pool, and the decision for a standard case, a failsafe case and a rejected case.

What decides whether an S7-1500 Software Controller runs on an IPC? #

Six documented checks decide it: the controller release, the IPC model, the controller edition, the fitted processor, the NVRAM configuration for failsafe editions, and the storage or slot configuration — and no family name substitutes for any of them.

The authority for all six is the delivery release for the exact controller version you install: it approves hosts per model and per configuration, and anything it does not name is not approved. Two layers enforce that approval. At runtime the controller does not run on Windows alone; it runs on a hypervisor, the software layer between the hardware and the operating systems, and that hypervisor's hardware support covers only the listed IPCs. In engineering, TIA Portal offers the software controller only on supported devices, and the device view blocks the configuration on anything else. A PC that boots Windows perfectly can therefore fail both layers, which is the whole answer to "some IPCs and not others".

Which IPC models are approved for each software CPU? #

For V21.8 and V21.9 the controller with the longer list is approved on 15 IPC models across box, panel and rack formats, the one with the shorter list on 11, and the rack models IPC647D and IPC847D carry the standard controller only.

The model lists are identical for the two releases:

IPC format CPU 1507S (F) CPU 1508S (F)
Box PC IPC227E, IPC427D, IPC427E, IPC627D, IPC827D, IPC627E IPC427E, IPC627D, IPC827D, IPC627E
Panel PC IPC277E, IPC477D, IPC477E, IPC677D, IPC677E IPC477E, IPC677D, IPC677E
Rack PC, standard and failsafe CPU IPC647E, IPC847E IPC647E, IPC847E
Rack PC, standard CPU only IPC647D, IPC847D IPC647D, IPC847D

Three rules come with the table. Every entry stays subject to the processor, NVRAM and storage checks that follow, so a listed model in an excluded configuration is still not approved. Model similarity transfers nothing: the IPC227E entry does not reach the IPC227G, which only a later release names, and the longer list's approval of the IPC427D does not put it on the shorter list. And the D-generation rack entries are standard-only, so a project that needs the failsafe edition cannot use an IPC647D or IPC847D, however well the standard controller runs there.

Does the processor inside the IPC change the approval? #

Yes, for the controller with the longer list: the IPC427D and the IPC477D are supported only from a Core i3 processor upward, so the same model with a lesser processor fails the approval even though its name is on the list.

Read the fitted processor from the order record or the device's system information before you approve anything; a higher Core processor satisfies the line and anything below that class does not. These are the only entries in the two releases that carry a processor restriction, and because neither model is on the shorter list, the rule matters only for projects on the longer-list controller. A matching enclosure with a weaker CPU is the classic way a replacement that "is on the list" still fails.

Why does the failsafe edition need NVRAM? #

The failsafe editions require NVRAM, nonvolatile memory implemented as buffered SRAM in these IPCs, on 9 models for the longer list's F edition and on 5 models for the shorter list's F edition, and an ordinary SSD is not that memory.

NVRAM retains safety-relevant data without operating power, and the release states the requirement per IPC configuration. It groups some designations — IPC2x7E, IPC4x7D, IPC4x7E — and expanded to the models that appear in the compatibility lists, the requirement covers:

  • F edition of the longer-list controller: IPC227E, IPC277E, IPC427D, IPC477D, IPC427E, IPC477E, IPC627D, IPC677D, IPC827D.
  • F edition of the shorter-list controller: IPC427E, IPC477E, IPC627D, IPC677D, IPC827D.

The grouped designations do not extend the approval to every IPC with a similar name; only the listed expansions count. The V21.9 information repeats the second line under a heading that names the longer list's F edition, and the V21.8 wording establishes that it belongs to the shorter list's F edition, so apply it there. The rack models IPC647E and IPC847E host standard and failsafe CPU without appearing in the NVRAM note; their failsafe approval stands on the rack entry itself. One safety line to hold: a failsafe controller on a named model without the required NVRAM fitted is not the approved safety controller, so never commission safety functions on it and never work around the requirement.

Which RAID, NVMe and slot configurations are excluded? #

On the IPC627E, IPC677E, IPC647E and IPC847E, both releases exclude RAID configurations and configurations with NVMe drives, and V21.8 also excludes the IPC627E variant with 5 PCI/PCIe slots.

RAID combines drives under a storage controller; NVMe is a storage interface and command protocol. The two are independent checks: a non-RAID unit can still contain an NVMe drive, and a unit with no NVMe drive can still run its disks behind a RAID controller, so read the drive inventory and the controller mode, not just one of them. On the slot variant, V21.9 repeats the RAID and NVMe lines but not the 5-slot line; treat the 5-slot IPC627E as excluded under both releases, because no delivery release approves that chassis configuration.

Why will the Software Controller not run on an IPC327G? #

Because the controller does not run on Windows alone: the hypervisor beneath it does not support the IPC327G hardware, and TIA Portal blocks the software controller on that device in the device view, so the pair fails at runtime and in engineering.

The two blocks are independent. Even if the engineering block were circumvented — it should not be — the runtime still could not start the controller, because the hypervisor's hardware support is the gate, not processor performance. The same failure applies to any PC outside the lists: an office PC, a third-party box PC or a generic industrial computer with a stronger processor changes nothing. The decision for the IPC327G is no, at any configuration; it is absent from the V21.8 and V21.9 lists, and the later platform additions described below do not name it either, so the answer is a listed host, not a workaround.

Which controller release and TIA Portal version does your project need? #

V21.9 corresponds functionally to firmware V2.9 of the advanced controllers, continues projects from version V2.0 of the longer-list controller, V2.6 of the shorter-list one and CPU 1505SP V2.5, and needs TIA Portal V17 for its new functions.

Backward compatibility is a project statement, not a hardware one: continuing an older project on V21.9 adds no IPC to the lists. To use the V2.9 functionality the engineering side must be at TIA Portal V17; a project kept on an older release runs the controller without the new functions. For maintenance planning, the Windows variant of V21.9 is delivered and maintained with enhancements and security patches until January 2026, so schedule the step to a newer release ahead of that date. Newer releases also widen the hardware: the V30.0 delivery release of July 2023 added the IPC227G and IPC277G, the IPC BX-39A and IPC PX-39A platforms, M.2 SSD support on all platforms and SIMATIC Industrial OS V3.2.4 support. A G-generation host therefore pairs with that later release, not with V21.8 or V21.9 — the release decides as much as the model.

How do you narrow the list to one approved host? #

Count the pool down in the order of the checks: the standard longer-list controller starts with 15 approved models, and the failsafe editions end with 11 candidates on the longer list and 7 on the shorter list before the storage exclusions.

The same model-and-configuration discipline applies whenever hardware-bound software loses its host, as when choosing a box PC replacement for hardware-bound software. When the dead unit cannot be queried, identify the software it ran from the project archives before ordering anything — the same first step as when replacing an unknown panel PC.

Worked example, hypothetical but built from the documented lists: a plant must replace the host of a failsafe project on the longer-list controller, on V21.9, and collects four offers.

The pool arithmetic first. The standard list holds 15 models; the standard-only entries are the IPC627E, IPC677E, IPC647D and IPC847D, so 15 − 4 = 11 models can host an F controller. The NVRAM note covers 9 of them — IPC227E, IPC277E, IPC427D, IPC477D, IPC427E, IPC477E, IPC627D, IPC677D, IPC827D — and the remaining 2 are the rack models IPC647E and IPC847E: 9 + 2 = 11. For the CPU 1508S F the same standard-only models drop out, the NVRAM note covers 5 — IPC427E, IPC477E, IPC627D, IPC677D, IPC827D — plus the 2 rack models: 5 + 2 = 7.

Then the offers:

  • Offer A, an IPC477D with a processor below the required class: rejected at the processor check; the model approval demands more than the enclosure.
  • Offer B, an IPC477D with a Core i5 for the F controller: model and processor pass, so approve it only in the NVRAM configuration, confirmed in the order record.
  • Offer C, an IPC647E with NVMe drives: rejected at the storage exclusion even though the model is failsafe-capable; reorder with an approved drive configuration.
  • Offer D, an IPC327G: rejected at both layers, at any configuration.

The decisions per case:

  • Standard edition of either software controller: any model on the matching list that passes the processor and storage checks, standard-only rack models included.
  • F edition on the longer list: the NVRAM models with the NVRAM configuration fitted, plus the rack models IPC647E and IPC847E.
  • F edition on the shorter list: only the NVRAM models of that list, plus the same rack models.
  • IPC327G or any unlisted PC: no, at any configuration — choose a listed host, or the release that names the hardware.

Questions asked

Is every IPC approved for the CPU 1508S also approved for the CPU 1507S?

Yes. The shorter list is a strict subset of the longer one, so a host approved for the CPU 1508S always carries the CPU 1507S approval, while the reverse fails for the IPC227E, IPC427D, IPC277E and IPC477D, which the shorter list does not name. A project on the second controller therefore never widens the host choice beyond what the first allows.

Can the failsafe edition run without NVRAM if the safety program is small?

No. The delivery release states the NVRAM requirement per IPC configuration and nothing in it scales the requirement by program size, so an F controller on a named model without the fitted NVRAM is not the approved safety controller. Commission safety functions only on a configuration that matches the release, and treat a missing NVRAM configuration as a reason to reconfigure or replace the host, not a tuning problem.

Does the processor restriction also apply to the CPU 1508S?

The question never arises. The IPC427D and IPC477D are the models tied to the processor line, and neither appears on the shorter list, so there is no approved configuration on them for the second controller at any processor. On the hosts that list does name, no processor restriction is stated; the configuration limits that remain are the NVRAM and storage lines.

How long can a plant stay on version V21.9?

The Windows variant of V21.9 is delivered and maintained with enhancements and security patches until January 2026, and delivery of the Linux variant ends in July 2026, so a new installation should already target a newer release. Existing installations keep running after those dates; what ends is the supply of enhancements and patches, which is the point to schedule the upgrade.

Keep reading

  • Troubleshooting

    How to prove an IPC slowdown is hardware not software

    A slow HMI on a booting IPC is not fault evidence. Capture per-process CPU, memory, disk and network under the production workload first: saturation with a clean event log is a sizing or software problem, and only an error that repeats under a separate one-component stress load — twice, with a matching Windows event — convicts the hardware.

    Industrial and panel PCs

  • Selection guide

    PCS 7 V6.0 on Windows 2000: picking replacement IPC hardware

    Do not stand up Windows 2000 under VMware on an IPC 547E as a replacement for a PCS 7 V6.0 station: that combination is not a documented compatible path. Check the exact hardware, operating system, release and S7-400 interface in the vendor compatibility tool, keep V6.0 only on listed native hardware you can still obtain, and otherwise migrate the operating system and PCS 7 together in one coordinated step.

    Industrial and panel PCs

  • Selection guide

    Running Windows 7 on an industrial PC: which IPC supports it

    The release entry for the exact order number decides, not the processor. The SIMATIC IPC 627C is released for Windows 7 Ultimate in 32-bit and 64-bit, the IPC 427C shipped as Windows 7 Ultimate 32-bit only, and the IPC 427B has no documented Windows 7 driver set, so it stays on Windows XP. Match edition and bitness to the nameplate order number before installing.

    Industrial and panel PCs