Why Noto Sans renders differently on an Ignition Edge gateway

Edge computing and IIoT Published 5 min read By IMD Solution engineering team

Short answer

The difference is the rendering environment: your PC or main gateway and the Linux-based Edge appliance do not present the same fonts to the runtime, and you cannot open the appliance's shell to see why. Confirm it with matching screenshots of the same view, record every version, deploy a test copy with a comparable font, and escalate with that evidence.

On this page
  1. What is confirmed and what stays a hypothesis
  2. Where the font actually comes from
  3. Diagnose by controlled comparison
  4. Comparing one Noto Sans view on Edge 8.1.47 and the main gateway
  5. Treat the firmware update as a controlled test
  6. The decision for your case
  7. Questions asked

Your project is not broken. When a Vision application developed on a Windows PC renders every Noto Sans component differently after migrating to an Ignition Edge appliance, the effective rendering environment changed, not the project. The appliance runs a Linux image you cannot log into, so you cannot prove whether Noto Sans is missing, substituted, or configured differently. That is why you diagnose this by controlled comparison, not by guessing: capture a baseline, record every version, test a comparable font, and escalate with evidence.

What is confirmed and what stays a hypothesis #

Keep these four findings apart, because only the first two are proven:

  • Confirmed: the same project content looks correct on the PC or main gateway and wrong on the Edge appliance. The migration changed the rendering environment; nothing in the project changed.
  • Confirmed: the appliance's Linux file system is not accessible to you. Font presence or substitution cannot be shown directly from the outside.
  • Unverified: a firmware update fixes the rendering. Updates were proposed and released during the original case, but no successful result was documented.
  • Hypothesis only: running a settings daemon so Java tells Linux which fonts to use fixed a similar symptom on a full Ignition installation on Linux HMI computers. That was a different installation type, not an Edge appliance, so do not treat it as the established cause on your device.

Where the font actually comes from #

The runtime does not ship fonts inside your project. Fonts are installed on the operating system, and the Designer or client reads the available fonts when it starts. That is the whole mechanism, and it explains the symptom: your development PC and the main gateway have Noto Sans available, and the appliance's Linux image evidently does not present it the same way.

An appliance maker ships the Edge runtime essentially as the runtime vendor releases it, so font behavior inside that runtime is a question for the runtime vendor's support channel, with the appliance vendor's ticket as the entry point. For the browser-based side of the same problem, the write-up on troubleshooting Perspective Noto Sans fonts on Edge covers the session-delivered case.

Diagnose by controlled comparison #

Work through this sequence in order and change only one thing at a time:

  1. Find every component in the project that explicitly selects Noto Sans as its font family, and pick one representative view for the comparison.
  2. Capture a screenshot of that view on the reference runtime (your PC or the main gateway) and on the Edge appliance, with identical text, component size, weight and style.
  3. Record the appliance firmware build, the Ignition Edge version and every installed module version. Do this before changing anything.
  4. Deploy a test copy of the project with a comparable font substituted for Noto Sans, and capture the same view again on both runtimes.
  5. If the test copy renders consistently, keep that font as the documented workaround and continue with step 6 only if Noto Sans is a hard design requirement.
  6. Submit the screenshots, the version inventory and the test result through the vendor's support channel. A support ticket was the escalation path that produced movement in the original case.

Comparing one Noto Sans view on Edge 8.1.47 and the main gateway #

This worked example uses a typical case for this topic; the Edge version is the one documented in a comparable offline-font case, and everything else comes from the procedure above.

Inputs:

  • One representative view that explicitly sets Noto Sans (from your project search, step 1).
  • Two runtimes to compare: the main gateway as the reference and the Edge appliance (for example an appliance reporting Ignition Edge 8.1.47).
  • Two rounds of capture: the baseline project and the comparable-font test copy.

Rule: each round needs the same view captured on every runtime, so the capture count is the number of runtimes times the number of rounds.

Arithmetic: 1 view × 2 runtimes = 2 captures for the baseline. Repeat after the test deployment: 2 rounds × 2 runtimes = 4 captures in total, plus one version inventory (firmware build, Edge version, every module version).

Result: compare round one against round two. If the baseline pair differs and the test-copy pair matches on text, size, weight and style, the Noto Sans family is confirmed as the variable.

Decision: if the comparable-font test copy renders identically on both runtimes, ship it and keep the Noto Sans question open only with support. If the difference survives the substitution, the font family is not the cause; stop changing fonts and send all four captures plus the inventory to support.

Treat the firmware update as a controlled test #

The appliance in the original case was running dated software, and updating firmware was the proposed next step with a new firmware release pending. Handle that as an experiment, not a fix:

  • Back up the application and configuration first.
  • Apply only the vendor-approved update for your exact device.
  • Record the version inventory again afterward, because an update on these appliances has been documented to change several module versions while leaving the Ignition Edge version number unchanged. The Edge version alone does not describe the runtime you are comparing.
  • Redeploy the identical comparison view and check it against the captured baseline.

If Noto Sans still renders differently after the update, restore the comparable-font workaround and hand the before-and-after evidence to support. Do not stack a second change on top of an unverified first one.

The decision for your case #

If consistent display across runtimes matters more than the specific typeface, replace Noto Sans with the comparable font in the deployed project and close the issue; this was the accepted outcome in the original case and it is a legitimate engineering choice, not a defeat. If Noto Sans is a design requirement, run the comparison procedure, open the support ticket with the screenshots, the full version inventory and the test result, and keep the comparable font in production until support confirms the font situation on the appliance image. What you should not do is keep swapping fonts or reconfiguring Java on machines you can inspect, hoping it fixes a device you can't.

Questions asked

Do I install fonts into Ignition or into the operating system?

Into the operating system. The runtime does not carry its own font set into a project; the Designer and each client read the fonts the operating system makes available when they start. A font installed after the Designer or client is already running is not picked up until that process restarts, which is also why a change on one machine never propagates to another by itself.

Why does the text still show at all if Noto Sans is missing on the appliance?

Because the Java runtime the gateway runs on guarantees five logical font names that every implementation must support: Serif, SansSerif, Monospaced, Dialog, and DialogInput. When a requested physical family is unavailable, the text is drawn with the physical font mapped to the logical name, so labels keep their content but change metrics, weight and spacing.

Can I deliver the font with the project instead of fixing each machine?

Only in Perspective. A font bundled into the gateway's asset directory is delivered automatically to every connecting session, which is the documented route for custom fonts in offline Edge deployments. Vision has no equivalent: its fonts come from the client machine's operating system, so an Edge-hosted Vision client needs the font on whatever machine runs it.

Why record module versions if the Ignition Edge version number is enough?

Because it is not enough. A firmware update on an Edge appliance has been documented to change several module versions while leaving the Edge version number identical, so two appliances reporting the same Edge version can run different module code. Record the firmware build, the Edge version and every module version, or your before-and-after comparison proves nothing.

Keep reading

  • Troubleshooting

    Could not read catapult properties: fix an empty gateway.xml

    The IllegalStateException: Could not read catapult properties at an Ignition 8.0.16 edge gateway startup means the gateway failed to parse its persisted properties file, not that permissions are wrong. In the recorded case gateway.xml in the data folder was zero bytes. Stop the service, rename gateway.xml, and the gateway starts from gateway.xml_clean; then reapply the gateway-level settings the damaged file held.

    Edge computing and IIoT

  • Troubleshooting

    Ignition Edge stuck starting after a Java trust store corruption

    The gateway page stays at Gateway is starting because module initialization dies when Java cannot build its default SSL context — wrapper.log shows java.security.NoSuchAlgorithmException for DefaultSSLContext under SunJSSE. Copy cacerts and cacerts.bak out of lib\runtime\jre-win\lib\security in the installation the service runs, rename cacerts.bak to cacerts, restart the service, and the gateway comes up.

    Edge computing and IIoT

  • How-to

    Managing recipes on Ignition Edge without a database

    Yes. Keep the recipe set on the Edge gateway itself — a dataset tag or a JSON file loaded by a script — look it up by tool ID, and write the resolved values to the Siemens PLC behind a request/accept handshake so PLC logic, not the HMI, decides when the new settings go active.

    Edge computing and IIoT

Why a lot filter opens the wrong report template