Why one thin client VM misses graphics updates

Remote access and virtualization Published 7 min read By IMD Solution engineering team

Short answer

When nine of ten thin client VMs receive graphic changes and one stays stale, the Auto Update transport to that node is the fault, not the graphics. Check whether the Auto-Update Service allows display updates for that node, then set the DeltaVAdmin password with servpwd.exe to the value the working nodes use, and confirm delivery with a unique test label, never with the download status.

On this page
  1. How a graphic change reaches a thin client VM
  2. Read the symptom as a path fault
  3. Check whether the node is allowed display updates
  4. Match the DeltaVAdmin credential on the node
  5. Prove delivery with a labelled change
  6. When the permission and the credential are right
  7. Where each branch ends
  8. Mistakes that burn hours on this fault
  9. Questions asked

One stale node out of ten is a transport fault, not a graphics fault. When nine thin client VMs take every graphic change and one never does, and a display copied to the failing machine by hand runs correctly, the display files and the operator station runtime on that VM are proven healthy. What is broken is the Auto Update pull from the ProPlus to that one node. Work the checks in order: the node's display update permission in the Auto-Update Service dialog, the DeltaVAdmin credential set with servpwd.exe, then a labelled test change that proves delivery on the node itself. The reference system runs version 13.3.1 with ten thin clients on ten virtual machines; none of the checks below involves editing or re-exporting the displays.

How a graphic change reaches a thin client VM #

The path has four steps. Edit the display on the ProPlus, download the ProPlus, download the operator stations on the virtual machines, and let the Auto Update service on each node pull the changed display files onto that node. Running the first three steps in that order is correct and already part of this site's routine, so the order is not the fault.

The thin client adds nothing to this path. It mirrors the virtual machine's desktop and stores no display files, so rebooting it cannot change what the VM shows. What belongs on the thin client versus the host is an architecture decision — the thick client versus thin client HMI comparison for a control system upgrade covers that split — but on a running system the desk device holds nothing and its reboots change nothing. Rebooting the VM and repeating the full operating station download leave the two per-node items untouched, and those two items are the only things that can differ between this node and its peers: the node's Auto-Update Service settings and its local DeltaVAdmin credential.

Read the symptom as a path fault #

Layer in the path What the healthy nodes tell you Verdict for the stale node
Display file content on the ProPlus The other nodes show the new graphics Files are valid; do not re-edit or re-export them
Operator station runtime on the failing VM The manual copy runs and draws correctly Runtime is healthy; do not reinstall it
Display update permission for the node One node skipped while every download reports success First suspect: the service may be forbidden to update displays here
DeltaVAdmin credential on the node Peers authenticate with the recorded value Second suspect: this node's local credential differs
The thin client Reboots of it change nothing on screen Not a suspect: it stores no displays

Two per-node items survive every reboot and every download: the node's update permission and its local credential. That is why the table points there first.

Check whether the node is allowed display updates #

Read this first because it costs nothing and decides the branch:

  1. From the Start menu, open DeltaV Engineering and then Auto-Update Service.
  2. Select the failing node in the list.
  3. Read the check boxes that say what the service may update on that node.

Display updates unticked: the service skips graphics for this node by design. Tick the box, apply, and confirm with the labelled-change test below. A box left unticked by an earlier maintenance session, or never ticked on a rebuilt VM, produces exactly this one-node-out-of-ten pattern.

Display updates ticked: the permission is not the cause. Open the same dialog for a working node and compare every box; a difference between the good node and the failing node is the finding. If all boxes match, go to the credential check.

Match the DeltaVAdmin credential on the node #

The Auto Update service on each computer runs against a local credential, and the DeltaVAdmin password is set per computer with servpwd.exe, which requires administrator privilege. Whether that credential governs Auto Update on a given system is a point to prove by result, not assume, so treat the reset as a test with a measurable outcome.

  1. Log on to the failing VM with an administrator account and open an elevated command prompt.
  2. Run servpwd.exe and enter the same DeltaVAdmin password the nine working nodes use. Take the value from the site's password record; a new value on one node creates a second mismatch.
  3. Restart the Auto Update service on the node, or reboot the VM if the site procedure calls for it.
  4. Run the labelled-change test in the next section and read the result.

If graphics now arrive, the credential was the cause. If they do not, the password is eliminated and the permission comparison deserves a second look before the service-level checks. One hardening note: Credential Guard exists to protect local service identities, and a local service account holding administrative privilege defeats the protection it is meant to provide, so keep that account's privileges no broader than the service needs.

Prove delivery with a labelled change #

The download dialogs confirm the ProPlus and the virtual machines took the distribution; they say nothing about the node's own pull. Judge the fix at the node:

  1. Make a trivial, visible edit to one display — a text label with a string no operator screen already uses, for example CHK-GFX-NODE3.
  2. Download the ProPlus, then download the virtual machines, in the order the site already uses.
  3. On the failing VM, open that display and look for the new label. Check the display file's modified timestamp against the time of the VM download.
  4. Open the same display from a thin client session on that VM and confirm the label there too.
  5. Repeat on one working node to confirm the test itself is valid.

A new label on the failing node closes the problem. An old label, with the Auto-Update boxes matching a working node and the DeltaVAdmin password confirmed the same, means the service is not running its pull on that node.

When the permission and the credential are right #

Compare the failing VM to a working one at the service level:

  • Is the Auto Update service actually running on the node?
  • Does the node entry in the Auto-Update Service list match the VM's real computer name?
  • Can the VM reach the ProPlus over the network by name? A pull that dies after the network answers behaves like ping works but a program download still fails — the path responds, and the session or the identity behind it does not.

A VM cloned, rebuilt or renamed recently can carry a stale name, an old identity or a different network profile, and a fault that began within roughly the last month points at a change to that VM: a restored snapshot, a template redeploy, a rename or a patch cycle. Correct the identity and the settings, then run the labelled-change test again.

Do not keep the manual file copy as the fix. It hides the fault, and the next graphic change leaves the node running different displays from its peers with no alarm anywhere.

Where each branch ends #

  • Display updates unticked for the node: tick it, apply, and confirm with the labelled change. This is the most common ending of this fault.
  • Boxes identical to a working node and the credential matched with servpwd.exe: the labelled change arrives and the fault is closed.
  • Boxes identical, credential matched, label still absent: check the service state, the node name and name resolution on that VM; if a clone, snapshot restore, rename or patch touched the machine in the failure window, correct the identity first; if the service side is clean, escalate through Emerson's official support channel.

Mistakes that burn hours on this fault #

  • Rebooting the thin client. It holds no graphics and cannot change the result.
  • Repeating the full operating station download before reading the node's Auto-Update boxes. The download does not touch per-node service settings or the local credential.
  • Setting a new DeltaVAdmin password on one node. Match the system's recorded value instead.
  • Judging success from the download status. Judge from the display file's timestamp and the visible label at the node.
  • Leaving the manual file copy in place. It proves file health once and then masks the fault.

Questions asked

What should I send to support when the node still stays stale?

Include the failing node's computer name, the DeltaV version, 13.3.1 in this case, the running state of its Auto Update service, the node's Auto-Update Service check boxes beside a working node's, the servpwd.exe result, and what changed on that VM within the last month: a snapshot restore, a clone, a rename or a patch cycle. Send it through Emerson's official support channel.

Can a snapshot restore or a clone cause this exact fault?

Yes, and the timing fits. A restored snapshot or a template redeploy rolls the VM back to settings the rest of the system has moved past: an unticked display update box, a node entry that no longer matches the VM's computer name, or a DeltaVAdmin password older than the current system value. Re-read the node boxes and the servpwd.exe value after any restore or redeploy.

Why does the download report success while the display stays old?

The download steps cover the ProPlus and the operator station software on the virtual machines. Delivery to each node is a separate pull by that node's Auto Update service, and no download dialog reports its result. That is why the verdict comes from the display file's modified timestamp and a visible test label at the node, never from the download window.

Why did the fault start without anyone touching that node?

The settings that decide display delivery changed silently: a maintenance session that unticked the box, a patch cycle on the VM, a restore from an older snapshot, or a credential that no longer matches after a password change elsewhere in the system. Because every download still reports success, nothing in the normal edit-and-download workflow reveals the fault until an operator notices a stale screen.

Does anything need redoing on the thin client after the VM is fixed?

No. The thin client shows whatever the virtual machine's desktop shows, so once the VM holds the current display, the device presents it on the next draw of that screen. If the display was open during the fix, close and reopen it. No firmware update, reinstall or setting change on the thin client takes part in display delivery.

Keep reading

  • Troubleshooting

    Why a VTScadaLIGHT thin client needs a VPN, not SSL setup

    Changing the SSL certificate will not open VTScadaLIGHT to outside thin clients: the free edition requires a VPN for its one free thin client connection from outside the network. Confirm the edition, prove the application host responds locally, then reach it over the site VPN. Only after a connection reaches the host should you match the certificate's name and trust chain to that host.

    Remote access and virtualization

  • Troubleshooting

    Why MPI works but PROFIBUS does not in a STEP 7 VM

    A working MPI connection proves only the MPI path, not the PROFIBUS path, even when both run through the same USB adapter and CPU interface. Test each layer in turn: adapter mode, VM USB assignment, bus parameters, physical network, then the CPU's MPI/DP interface. In the reported case the cause was an intermittent fault at that interface, so the VM was not the culprit.

    Remote access and virtualization

  • Troubleshooting

    Fixing a VMware VM stuck with a multi-monitor layout

    When a VMware guest keeps drawing a three-monitor layout on one panel after undocking, the host and the guest both report a single display, so the fault sits in the Workstation window, not in the VM configuration. Switch the application theme to Light — switch away and back if it is already Light — to force the window rebuild, keep Monitors on Use host settings for monitors, and exit Unity before you unplug the externals.

    Remote access and virtualization