Explainer
Why Portainer containers do not create a supported Soft dPAC
Short answer
A supported Soft dPAC is created only from EcoStruxure Automation Expert's Physical Device View, using Manage Soft dPAC > Activate services, on an open iPC running Debian or Ubuntu with Docker, Docker Compose and Python 3 where you hold administrator rights. Starting the container images in Portainer on a closed appliance reproduces, at best, the obsolete unsecured script workflow that nothing supports. A ping that succeeds while discovery fails is a subnet or firewall question on the interface you selected.
On this page
Portainer cannot create a supported Soft dPAC, whatever images you upload through it. A supported Soft dPAC controller is created in one supported place: EcoStruxure Automation Expert's Physical Device View, against an open iPC running Debian or Ubuntu with Docker, Docker Compose and Python 3, on an OS where you hold administrator rights. If the machine in front of you is a closed appliance administered only through a web interface — the UC20-WL2000-AC class of controller — its container UI can start images, but nothing it starts is a supported controller. A ping that succeeds while the tool will not discover the device is a separate, second fault: a subnet or firewall question on the interface you selected. This article keeps the three questions apart: what makes a host supported, where the supported creation runs, and why ping is not discovery.
What makes a host supported #
The prerequisite list is short and absolute: an open iPC, Debian or Ubuntu on it, Docker, Docker Compose and Python 3 installed, and administrator rights on that OS. Open is the operative word. Open means you can open a shell on the machine, install packages and run, under your own administrator account, every host-side step the engineering tool pushes to it. Prove each row before you plan anything else:
| Prerequisite | How you prove it on the machine |
|---|---|
| Open OS, Debian or Ubuntu | A terminal opens and your account can install packages |
| Docker and Docker Compose | Both respond to commands from your administrator account |
| Python 3 | The interpreter runs under the same account |
| Administrator rights | You can change services, users and networking on the OS, not only in the vendor web UI |
Miss one row and the machine is not a Soft dPAC host, no matter which containers it runs. A closed appliance fails the first row and the last row at once: its administration surface is the vendor's web interface, so there is no terminal in which you could prove the rows between. On a closed controller such as the UC20-WL2000-AC, the preinstalled Portainer is the only container tool you can reach, which is a management convenience, not a qualification. What a working host looks like once it runs — a Soft dPAC on an open edge computer beside analytics workloads — is what Run Soft DPAC on an Edge Computer Alongside Analytics describes.
Where the supported creation runs #
On Automation Expert 22.x releases (the sequence below matches v22.0.22181.16), creation runs from the engineering tool, in this order:
- Open the Physical Device View and add a server.
- Select the server's port and enter the iPC's IP address in its properties.
- Confirm the iPC is reachable before continuing; a ping from the engineering station is the quick check.
- Select the server itself, not the port, and run
Manage Soft dPAC > Activate servicesfrom its context menu. - When activation completes, a Docker logo appears on the server and new items appear in the Soft dPAC menu.
- Click start monitoring on the toolbar.
- Configure security from the same menu. Completed security configuration is indicated by a green shield; the tool asks for the first user when required, and the manual documents that first-user step.
- Create and configure the Soft dPAC controllers from the same Manage Soft dPAC menu.
The order is the security argument. The tool registers the controller and applies its security configuration, so only authorized users can log into it afterward.
What Portainer can and cannot do here #
Portainer is a container management UI. On a Soft dPAC host its supported roles come after activation: inspect the running services and clean up containers when needed. Starting the Soft dPAC images yourself achieves none of the sequence above — no server object, no activation, no security configuration, no registration with the engineering station. What you get reproduces, at best, the obsolete script workflow from the 21.1 era, and no official procedure exists for a Portainer-based creation. Rebuilding that workflow would mean analyzing the old host scripts and reproducing each action with the same parameters, and nothing supports the result. The gap is the reason the old method was retired: an unsecured controller has no authorized-user login to stand behind it. That makes one rule absolute: do not connect an unsecured Soft dPAC controller to a plant network that carries production traffic.
Two container facts on the host are still worth knowing. The services that activation deploys run as containers on the host engine, which is why a Docker logo appears on the server afterward, and how those containers address each other follows Docker's own networking — how Docker Modbus TCP containers find each other walks through that addressing for Modbus TCP services. Running unrelated containerized data services on the same machine is also a normal pattern — Deploying Edge Data Store in Docker on a controller PC is one example — but normal Docker operation and controller provisioning are different jobs, and only the engineering tool does the second.
Why the old script route stays retired #
Through the 21.1-era releases, installation ran from scripts on the host. On an open host those scripts still execute, and what they produce is an unsecured controller: none of the per-user security configuration the supported flow applies. That gap is why the vendor retired the method, and it does not shrink on a closed appliance — a closed appliance only takes away the shell you would need to audit or undo what the containers did.
Ping is reachability, discovery is separate #
A successful ping proves one thing: IP packets reach that address. Discovery is a different exchange that Automation Expert runs, and the vendor's device-discovery guidance puts a hard condition on it: the engineering station and the devices must be in the same subnet. Two consequences follow.
First, discovery returns the host — your iPC — not the individual Soft dPAC controllers. Controllers appear in the project after you create them in the tool, so a discovered host with nothing underneath it is a normal screen, not a fault.
Second, an adapter that finds devices while the onboard port does not is telling you the two interfaces are not in the same situation. Host firewalls treat interfaces and network profiles individually, so one station can pass discovery on one NIC and fail on the other. And when the Soft dPAC host itself runs Docker Engine on Debian, read the firewall limitations documented in Docker's Debian installation guide before debugging: Docker's rules change how traffic is filtered on that host. The reachability-versus-session split is not unique to Soft dPAC either — Why an Industrial PC Pings an S7-1500 but Runtime Stays Disconnected works the same fault for a runtime connection.
A worked subnet check #
Put the devices at 192.168.1.50 with mask 255.255.255.0. The USB-Ethernet adapter sits at 192.168.1.20 on the same mask: 192.168.1.20 AND 255.255.255.0 gives 192.168.1.0, and 192.168.1.50 AND 255.255.255.0 gives 192.168.1.0, so both ends share a subnet, discovery traffic stays local and the tool finds the host. The onboard port sits at 10.0.20.5 on the same mask: 10.0.20.5 AND 255.255.255.0 gives 10.0.20.0, a different subnet from 192.168.1.0, so discovery must cross a router, where either no route exists or a firewall drops the exchange. Ping crosses that router fine, which is exactly the split you observe: reachable on both paths, discoverable on one. The fix follows the arithmetic: put the interface the tool uses on the device subnet, or build a routed path and permit the discovery traffic through the firewalls on it, then rerun discovery.
The decision, case by case #
- Open iPC, and you hold administrator rights: create the controller with the Physical Device View sequence above and secure it to the green shield. Afterward, Portainer is a legitimate inspection and cleanup tool on the same host, and nothing more.
- Closed appliance, web interface only — the UC20-WL2000-AC case: it is not a Soft dPAC host, and no upload order changes that. Move the runtime to an open industrial mini PC that meets every row of the prerequisite table, and retire the appliance from this role.
- Ping works, discovery does not: stop debugging containers; the fault is in subnets, routes or firewall rules on the selected interface. Same subnet, or an explicitly permitted routed path, then rerun discovery and expect the host, not the controllers.
Questions asked
Does the preinstalled Portainer satisfy the Soft dPAC host prerequisites?
No. Portainer runs on the Docker engine, so the engine itself is present, but the prerequisite list also names Docker Compose, Python 3 and an administrator account on the host OS. On a closed, web-managed appliance you can neither verify those components nor run anything with administrator rights, so the host requirement is unmet. The supported path is an open iPC where you can prove every prerequisite from a shell.
Which scripts did the obsolete installation method use?
The 21.1-era method ran install.py and startSoftdPAC.sh on the host. They still execute on an open host, but the result is an unsecured controller without the security configuration the supported flow applies, which is why the vendor retired the method for cybersecurity reasons. No procedure documents a Portainer reproduction of those scripts, and nothing supports the result.
Can a Windows PC serve as the Soft dPAC host?
Not as the host. The prerequisite names Linux, Debian or Ubuntu, on an iPC you administer. A Windows workstation runs EcoStruxure Automation Expert as the engineering station and drives the Physical Device View, but the Soft dPAC services are deployed onto the Linux host, so the two roles stay on two machines.
Is there a route to run the runtime on a closed controller?
The runtime's developer has pointed to porting the IEC 61499 runtime to closed controllers through the Universal Automation Organization as a possible future option. Nothing in the current supported flow installs a Soft dPAC on a closed appliance, so the working decision today is unchanged: an open host you administer, created from Physical Device View.