Troubleshooting
Why SIMATIC Manager in a VMware guest cannot find a host PLC engine
Short answer
Accessible Nodes is a discovery scan and will not list WinPLC-Engine running on the host, so an empty list is expected. Enter the host adapter's IP address in the engine and assign the same address to the CPU's Ethernet interface in the hardware configuration; the reported setup also needed engine version 1.6.1, since 1.3.0.0 failed, and a successful ping only proves guest-to-host reachability.

On this page
- Can the simulation software run inside the virtual machine instead of on the host?
- Why does Accessible Nodes not list a PLC engine running on the host?
- Which IP addresses do I set in the engine and the CPU's Ethernet interface?
- Does a ping from the guest to the host prove the engine connection works?
- How do you check the guest and the host adapter share one subnet?
- Which WinPLC-Engine version connects from a VMware guest?
- Why didn't disabling both firewalls make the engine visible?
- What is the decision for each failure in this setup?
- Questions asked
An empty Accessible Nodes list is the expected result when the PLC engine runs on the host PC outside the VMware guest: that function scans the local network for participants that announce themselves, and this engine is not among them. The connection is made by explicit addressing instead. In the reported arrangement — the engine and the simulation on a Windows 7 64-bit host, SIMATIC Manager in a Windows 7 32-bit guest — the connection failed with engine version 1.3.0.0 and worked after the move to 1.6.1. A successful ping from the guest to the host is the entry check, not the proof; the sections below take each branch in the order you meet it.
Can the simulation software run inside the virtual machine instead of on the host? #
The first-launch failure inside the guest is an application startup fault, not a network fault, and ITS is documented by its vendor as not usable in a virtual machine, so keep the simulation and the engine on the host with SIMATIC Manager in the guest.
A first start that ends in an external-component error fails before any PLC communication exists, so no adapter, subnet or firewall setting can repair it; an installation that completes is not evidence that the program runs. ITS, the product that failed this way in the reported guest, is restricted by its vendor to installations outside virtual machines.
Keep the split that works: simulation and WinPLC-Engine on the host, engineering station in the guest. Only once both host programs are open does the discovery question in the next section become the fault to chase.
Why does Accessible Nodes not list a PLC engine running on the host? #
Accessible Nodes is a discovery scan that lists the participants answering on the local network, and WinPLC-Engine on the host is not among the participants it reports over Ethernet, so an empty list in this arrangement is the expected result rather than evidence of a broken path.
STEP 7 documentation describes Accessible Nodes as an overview of the modules present on the local area network and their types: a browse of whatever answers the scan, not a test of a target named by address. The vendor of this engine confirms that its product does not turn up in the Ethernet scan, which means rescanning, swapping adapters or stripping services will never fill the list.
Read the empty list as information about the discovery mechanism, not about the path, and move straight to the explicit connection described next.
Which IP addresses do I set in the engine and the CPU's Ethernet interface? #
Enter one address in both places: set the host network adapter's IP address as the engine's address in WinPLC-Engine, then assign that same address to the CPU's Ethernet interface in SIMATIC Manager's hardware configuration, and never give that address to the guest's own adapter.
The address in the project identifies the endpoint the engineering session opens, and in this arrangement that endpoint is the host PC. If the engine's address and the CPU's interface address differ by a single octet, SIMATIC Manager opens the session toward a target where nothing listens, and the guest's adapter is the wrong holder for the address anyway: one address cannot belong to two stations.
Pick the adapter the guest actually reaches. On NAT or host-only networking that is the host's virtual adapter on the guest's subnet — a host with a physical LAN adapter plus virtual adapters presents several addresses that are not interchangeable. Then select the guest's virtual Ethernet adapter, over TCP/IP, as the engineering station's interface, so the session leaves through the network that holds the target.
Does a ping from the guest to the host prove the engine connection works? #
No: a ping from the guest to the host proves only that ICMP packets cross the virtual network and return; it does not prove the engine is listening on the addressed adapter, that the versions cooperate, or that the project's CPU points at that endpoint.
In the reported tests the ping succeeded while the connection failed, because the fault sat in the address pair and the engine version — exactly the things an ICMP exchange cannot see. Treat ping as the first check of the path, then judge the session itself: whether the addressed engine accepts the connection and whether the project's target points at it.
The same separation appears elsewhere in this library: why an industrial PC pings an S7-1500 but the runtime stays disconnected, and ping works while a PLC program download fails over remote access. Reachability at the network layer is not an application session.
How do you check the guest and the host adapter share one subnet? #
Take the host adapter address the guest can reach — for example 192.168.67.2 on a VMware NAT network — enter it in the engine, and assign the same address to the CPU's Ethernet interface in the project.
Worked example with an example pair; read your own host adapter and substitute its value:
- Host side of the NAT adapter: 192.168.67.2, subnet mask 255.255.255.0.
- Guest adapter, assigned by the virtual network's DHCP service: 192.168.67.128, subnet mask 255.255.255.0.
Both sides ANDed with the mask land in one network: 192.168.67.128 AND 255.255.255.0 gives 192.168.67.0, and 192.168.67.2 AND 255.255.255.0 gives 192.168.67.0 as well. Same network, no gateway, traffic that never leaves the virtual switch. Enter 192.168.67.2 in WinPLC-Engine, assign the same address to the CPU's Ethernet interface in the hardware configuration, then ping that address from the guest so the test hits the exact endpoint the project will open.
A different subnet does not change the rule: engine and CPU both take the reachable host adapter's address, whatever its value is.
Which WinPLC-Engine version connects from a VMware guest? #
On the reported host-and-guest pair the connection failed with WinPLC-Engine 1.3.0.0 and succeeded after the move to 1.6.1, so once the addresses match and the ping reaches the right adapter, the engine version is the next branch to change.
Record the version from the running engine rather than from a desktop shortcut, because an older installation left running will poison the comparison. Change the version alone — keep the address pair, the guest network and the project untouched — so the result attributes to the version and to nothing else.
This is one reported result on one host-and-guest pair, not a claim that the older build fails through every hypervisor; what it establishes is that the arrangement connects with the newer engine build, and says nothing about other releases. Install the engine from the vendor or its authorized channels only, matched to your operating system.
Why didn't disabling both firewalls make the engine visible? #
Disabling the host and guest firewalls did not make the engine appear in the reported tests, which tells you the fault sat in addressing and version rather than in packet filtering — so restore both firewalls and, if filtering ever blocks a later test, add scoped rules instead.
Both firewalls were down and the engine stayed invisible, which moves the search to the branches above. Keep the guest on a NAT or host-only segment rather than bridged onto the plant network while commissioning, and when a rule is genuinely needed, scope it to the engine's traffic on the virtual adapter instead of leaving a machine open.
What is the decision for each failure in this setup? #
Each failure in this setup has one decision: an application that fails at first launch stays off the guest, an empty Accessible Nodes list gets no more scans, matching addresses with a dead connection get a version change, and a failed ping gets the virtual network checked.
- The simulation fails at its first start inside the guest: it stays on the host, because ITS is not usable in a virtual machine and the error predates any network traffic.
- Accessible Nodes stays empty while the guest pings the host: stop scanning, enter the host adapter's address in the engine, and assign the same address to the CPU's Ethernet interface.
- The addresses match, the ping reaches the right adapter, and the connection still fails: change the engine version — the reported setup connected only after the move to 1.6.1.
- The guest cannot ping the chosen host address: the fault is the virtual network attachment, not the engine, and fixing a VM remote PLC connection with a NAT adapter shows the adapter side of that fault class.
When SIMATIC Manager goes online to the addressed engine, the job is done: simulation and engine on the host, engineering station in the guest, one address in both places, firewalls back on.
Questions asked
Can SIMATIC Manager reach the engine without a virtual machine at all?
Yes. On a single PC the endpoint is that PC's network adapter, so you enter the adapter's IP address in WinPLC-Engine and assign the same address to the CPU's Ethernet interface in the project. The Accessible Nodes limitation is identical there, because the scan and the explicit connection are separate mechanisms whether or not a hypervisor sits in between.
What changes when the target is a real PLC on the plant network instead of the host engine?
The guest needs a route onto that network, normally a bridged adapter, and the project's CPU then carries the controller's real IP address on its Ethernet interface. The two checks survive unchanged: guest and controller in one subnet, then a genuine online test, because reachability alone has never opened an application session.
How do I identify the right host adapter address when the host has several?
Run ipconfig on the host and note each adapter's address; the guest shows its own the same way. Match the two by subnet — the host adapter whose network matches the guest's address is the one that goes into the engine and the CPU interface — and confirm the pick with a ping from the guest.
Does any of this depend on Windows 7 or on one specific hypervisor?
No. The discovery scan, the two-place endpoint address and ping as a reachability check behave the same on current Windows or Linux guests and on other hypervisor products. What stays tied to the reported installation is the version result, so treat it as evidence that the arrangement works with that build rather than as a general release table.