Edge computing and IIoT Published 7 min read

Short answer

Yes, System Platform 2014 R2 can log to AVEVA Historian 2023 R2 — but only across a server boundary. The Historian Server 2023 technology matrix lists the pair under Product Interoperability / Compatibility, not Product Coexistence, so the two cannot share one machine. Run the 2023 R2 Historian on its own server, point the Galaxy at it by node name, and keep Store Forward enabled on the 2014 R2 node so outages backfill.

On this page
  1. Coexistence versus interoperability
  2. The three layouts, and the one that fails
  3. What actually crosses the network
  4. Building the split-server layout
  5. Sizing Store Forward for the outage you accept
  6. Prove the backfill before go-live
  7. What the operator sees when the path breaks
  8. If a 2014 R2 historian already holds your history
  9. The decision, case by case
  10. Questions asked

Yes, System Platform 2014 R2 can historize into AVEVA Historian 2023 R2, and the 2014 R2 node does have store-and-forward backfill — Store Forward in the product's own vocabulary. Both answers carry one condition: the two products run on separate servers. The Historian Server 2023 technology matrix lists Application Server 2014 R2 under Product Interoperability / Compatibility and leaves it out of Product Coexistence, and that pair of lists is the entire architecture decision. Keep the 2014 R2 platform where it is, stand the 2023 R2 Historian up on its own machine, and let the network plus Store Forward carry the data.

Coexistence versus interoperability #

Two words decide this design, and they are not interchangeable. Product Coexistence is the technology matrix's list of products supported installed on the same machine. Product Interoperability / Compatibility is its list of products supported working together while installed on different machines. The Historian Server 2023 technology matrix, maintained within the AVEVA Global Customer Support (GCS) technology matrix, is the document that decides which list a pair belongs to.

Application Server 2014 R2 appears against Historian 2023 R2 in interoperability and nowhere in coexistence. Read that absence as the boundary it is: the restriction sits at installation level, not behind a setting you can change. A same-machine design is not a risky variant of the supported one; it is outside support entirely.

The three layouts, and the one that fails #

Layout Same machine? Supported? Decision
A — Application Server 2014 R2 and Historian 2023 R2 on one machine Yes No Two different versions of Application Server and Historian cannot be installed on the same machine. Dead end, including as a temporary step.
B — Application Server 2014 R2 nodes logging to a dedicated Historian 2023 R2 server No Yes, as interoperability Data crosses the network; Store Forward buffers on the sending node. The 2014 R2 runtime stays untouched.
C — Migrate an existing 2014 R2 historian to Historian 2023 R2 No Yes The technology matrix lists System Platform 2014 R2 as compatible, and the vendor's migration guide covers the historian move.

Choose B when the plant keeps its 2014 R2 platform and wants the newer historian. Add C only where a 2014 R2 historian already holds history you must keep. Never A.

What actually crosses the network #

This settles the collector question that comes with every one of these projects. In layout B the 2014 R2 node does not take on the Historian's data-acquisition role (IDAS in the older naming). Application Server sends its own historized attribute values to the Historian server across the network. The buffering that protects that data during an outage is Store Forward on the sending node, which is also what backfills the gap afterwards.

One scoping note: Store Forward behavior is documented per release and patch level, so confirm it for your exact 2014 R2 patch level in the technology matrix and product documentation before you promise operations a backfill window.

Building the split-server layout #

  1. Provision a dedicated machine for Historian 2023 R2 with no Application Server 2014 R2 components on it — a rack server, or an industrial mini PC in the cabinet when the tag count is modest.
  2. Leave the Application Server 2014 R2 nodes alone. An in-place upgrade is a full System Platform project, not part of this one.
  3. Open the path between the nodes: name resolution that works in both directions, and the firewall ports the product documentation lists for each version.
  4. Synchronize clocks between the nodes. Buffered samples keep the timestamp they carried at the source, so drift bends history.
  5. In the IDE, point the Galaxy historian configuration at the Historian 2023 R2 server by node name, then redeploy the platform and the engines so they pick up the target.
  6. Enable Store Forward on the Application Server node and record the buffer's location from the platform configuration so you can watch it during testing.
  7. Enable historization on the attributes that need it and redeploy the affected objects.

Sizing Store Forward for the outage you accept #

Store Forward turns a network outage into a disk-space question, and disk space is the number you commit to. Here is the arithmetic with illustrative inputs; put your own counts in their place.

A platform historizes 2,000 attributes, and deadband logging stores on average one sample per attribute every 10 seconds:

  • Sample rate: 2,000 attributes ÷ 10 s = 200 samples per second.
  • Longest accepted outage, a two-hour switch replacement: 2 h = 7,200 s, so 200 samples/s × 7,200 s = 1,440,000 buffered samples.
  • At an assumed 50 bytes per buffered sample — replace this with your own measured footprint — 1,440,000 × 50 B = 72 MB.
  • The same plant riding out a full 8-hour network loss: 200 samples/s × 28,800 s = 5,760,000 samples, or 288 MB at the same footprint.

The result moves with two things: tag count, and how much the values move. Deadband logging stores more when the process is upset — exactly when networks fail — so double the figure before choosing the buffer volume. A full buffer is the failure this arithmetic prevents; the same failure exists in every store-and-forward stack, and Ignition store and forward buffer-full troubleshooting covers that platform's version of it.

Prove the backfill before go-live #

Compatibility on paper is not commissioning evidence. Run the outage once:

  1. Confirm a historized attribute trends live from the 2023 R2 server.
  2. Break the network path between the nodes — disable the Application Server node's adapter or block the route — with the runtime running.
  3. Note the start and end times, and wait long enough for a clear gap; the two-hour window above is a sensible target.
  4. Restore the path.
  5. Re-query the trend across the outage window and confirm the buffered samples arrived at their original timestamps.
  6. Confirm the Store Forward buffer on the Application Server node drained.

A passed test belongs in the commissioning file. A failed one is a finding while it is still cheap.

What the operator sees when the path breaks #

Symptom Likely cause Where to look
Live values update, trend stays empty for new data Attribute not historized, or object not redeployed IDE historization setting; redeploy status
Trend stops at a point, live values continue Link to the Historian lost; data sitting in the node's buffer Network path, name resolution, firewall; Store Forward buffer
Gap remains after the link returns Store Forward disabled, or buffer not forwarded Store Forward configuration; Historian log for late-arriving data
New data lands with shifted timestamps Clock drift between the nodes Time sync on both servers
Installer refuses to proceed on the Application Server host Layout A attempted Move the Historian to its own server

When the trend is empty and the network is not the reason, start from why System Platform tags do not reach Historian.

If a 2014 R2 historian already holds your history #

Layout C applies: the Historian Server 2023 technology matrix lists System Platform 2014 R2 as compatible, so the existing historian can be migrated rather than abandoned. Follow the vendor's documented migration guide for the historian move, and keep the 2023 R2 server on separate hardware from the 2014 R2 stack throughout.

Two further boundaries sit outside that matrix row. Licenses: AVEVA Historian license backward compatibility decides whether your existing entitlements run the 2023 R2 server. Clients: validating Historian Client 2017 against a 2023 R2 SP1 server is the kind of test every client version needs before rollout.

The decision, case by case #

  • The platform stays on 2014 R2 and you need a current historian: layout B. Separate server, Galaxy pointed at it by node name, Store Forward on, outage test passed.
  • A 2014 R2 historian holds data you must keep: layout B plus C. Migrate the history per the vendor guide, verify retrieval of known tags and timestamps on the new server, then retire the old box.
  • Any design that installs both products on one machine: rejected. The technology matrix does not support it, temporarily or otherwise.
  • Asked whether the 2014 R2 node serves as the collector: no. The platform sends its own historized values over the network, and Store Forward is the backfill.

Questions asked

Can System Platform 2014 R2 act as the data collector for Historian 2023 R2?

Not in the sense the question usually means. In the split-server layout the Application Server node does not run the Historian's acquisition role: it sends its own historized attribute values to the 2023 R2 server over the network, and Store Forward on that node buffers and backfills. Confirm the exact Store Forward behavior for your 2014 R2 patch level in the technology matrix before quoting a backfill window to operations.

What happens if Historian 2023 R2 is installed on the Application Server machine anyway?

The layout is unsupported: two different versions of Application Server and Historian cannot be installed on the same machine, and the restriction sits at installation level rather than behind a setting. Treat it as a dead end even as a temporary step during a migration, and plan the separate server from the start so the project never rests on an unsupported stack.

Can data in an existing 2014 R2 historian move to the 2023 R2 server?

Yes. The Historian Server 2023 technology matrix lists System Platform 2014 R2 as compatible, and the vendor's documented migration guide covers moving the historian. Keep the 2023 R2 server on separate hardware from the 2014 R2 stack, and verify retrieval of known tags and timestamps on the new server before retiring the old one.

How long can Store Forward cover a network outage?

As long as the buffer has room. Multiply sample rate by outage duration: at 200 samples per second, a two-hour outage needs 1,440,000 buffered samples and an eight-hour one needs 5,760,000. The disk they consume depends on your measured per-sample footprint, so size the buffer for the longest outage you accept and prove it with a deliberate outage test.

Does the split change which clients and licenses the 2023 R2 server accepts?

It raises two separate checks. Client software carries its own compatibility rows in the same matrix, so validate each client version against the 2023 R2 server before rollout. Licenses are decided by different documents again: confirm your entitlements actually run the 2023 R2 server before planning the cutover.

Keep reading

  • Checklist

    Validate Historian Client 2017 against a 2023 R2 SP1 server

    Yes on licensing by mechanism: a Historian client takes its entitlement from the license server named in its client-node configurator, not from the historian connection, so server-held licenses reach a 2017 Update 3 client once that setting points at the right host. The data path is proven, not assumed: one pilot client must return a known tag over a past time range from the 2023 R2 SP1 server. Pass pairing, pilot query and license setting, and the installed-base upgrade can follow in its own window.

    Edge computing and IIoT

  • Explainer

    AVEVA Historian 2023 R2 license backward compatibility explained

    Yes. AVEVA knowledge base 000033942 lists Historian among the 2023 products whose licenses are backward compatible to their 2017 versions, and one field test reports a 2023 R2 license running Historian 2020 R2. That clears the license layer only: Citect 2016 connectivity must be proven through the Plant SCADA Connector and CtAPI path.

    Edge computing and IIoT

  • Selection guide

    Plant SCADA 2023 R2 AEL license tiers and included historian tags

    Plant SCADA 2023 R2 (v8.5) AEL server licenses bundle a Historian 2023 R2 Server (Standard) and a Reports for Operations 2023 R2 Server: 500 historian tags and 500 reporting tags at the 1,000- and 2,500-tag tiers, and 5,000 of each from the 10,000-tag tier through Unlimited. Existing enterprise licenses pick the entitlements up with a sync rather than a repurchase; legacy USB keys exchange through the distributor; and Flex shows existing enterprise customers only the 100,000-tag and Unlimited packages.