WinCC CAS versus PI historian for long-term archiving

Edge computing and IIoT Published 7 min read

Short answer

WinCC CAS is a Siemens add-on that backs up, collates and archives long-term-relevant WinCC data from lower-level WinCC stations on one central server with RAID storage. PI is a separate plant-wide historian that collects from many source systems and serves many clients. Choose CAS when every record and consumer lives in WinCC; choose PI when several systems share one process history.

On this page
  1. What WinCC Central Archive Server is
  2. What the PI historian is
  3. The decision at a glance
  4. Record fidelity when WinCC history must reach PI
  5. Sizing CAS storage for a WinCC station at 400 MB per day over a 3-year retention
  6. The decision by case
  7. Questions asked

WinCC CAS and the PI historian answer different questions. WinCC Central Archive Server is a WinCC add-on that backs up, collates and archives long-term-relevant data from lower-level WinCC stations onto one central server, so WinCC archive data outlives the station's local disks. PI is a standalone plant historian: every source system connects through its own collection interface, and any client you wire up reads the shared history. Choose CAS when every record and every consumer lives inside WinCC; choose PI when several systems need one shared process history. Storage follows the same arithmetic either way, measured archive growth times retention days, and the worked example below runs the numbers. If you are still weighing a central store against the archives WinCC keeps at runtime, start with WinCC runtime archives versus a central process historian.

What WinCC Central Archive Server is #

CAS is the add-on application that backs up, collates and archives the data you mark as long-term-relevant, and Siemens documents it as a separate Windows host rather than a service inside a WinCC station. It collects process values and alarms in real time from lower-level WinCC systems across the plant, and any number of those systems can feed the same central store. That is the whole architectural idea: the stations keep their local short-term archives, and the long-term-relevant records get one central home with retention measured in years instead of in local disk space.

Storage sits on that host, and RAID volumes are a supported arrangement for CAS data. Read RAID narrowly: it protects against individual disk failure, not against deletion, corruption or loss of the whole storage system, so archive backups on separate media and a tested restore stay on the acceptance list as their own items.

WinCC V7 can compress process values inside long-term archives, so measure station archive growth with compression enabled before you size anything; the compressed figure is the one that fills the CAS volume.

The CAS host itself is specified once, like any 24/7 server; in a cabinet that usually means a fanless mini PC. The configuration work of host, storage layout and archive cycle is set up once and then left alone, the same discipline the CAS server configuration guide for long-term archiving in PCS 7 walks through.

What the PI historian is #

PI is a historian platform that belongs to no HMI family. Each source system, whether a WinCC station, a PLC, a lab feed or an ERP feed, needs its own supported collection connection, and the historian stores what that connection delivers: for each archived element, the original value with its source time and all status bits, with smoothing available as a scheduled option rather than a default. Point naming and engineering units are configured per point, so map them to how the consuming applications will actually read the data.

Consumers read through the historian's own clients and interfaces instead of through WinCC, and each client points at a specific archive server. Check which archive a client targets before you design retrieval, because PI Vision connects to only one PI Data Archive, and that constraint shapes how a multi-archive plant reaches its history. This separation is the point of the platform: process history becomes a plant-wide service that outlives any single HMI or SCADA layer.

The decision at a glance #

The product follows from five answers: where records originate, who reads them, what retention the site requires, which retrieval paths must work, and how much storage the growth arithmetic produces.

Requirement WinCC CAS fits PI historian fits
Record origin All required records are WinCC archive data Records come from several source systems
Consumers WinCC users reading through WinCC clients Clients outside WinCC: analytics, cross-line reports, other HMI families
Retention Longer central retention of WinCC archives A shared historian service sized for the plant
Alarms and events Collected in real time with process data from the WinCC stations Each source needs a supported collection path, checked separately
Retrieval WinCC archive access to the central archives Historian clients and interfaces, designed per application
Storage CAS host volume set; RAID supported Historian server storage sized to point count and write rate
Typical trap Sizing from local disk space instead of measured growth Treating a transferred time series as the complete archive

Record fidelity when WinCC history must reach PI #

A time series moved from a WinCC archive into PI is not automatically the original archive. Verify it on a record read back through the intended retrieval path, because that record is what the consuming application will live on.

  • Record types: process values and alarm or event history each need a supported path end to end; a value whose alarm trail stops at the transfer is a gap you find years later.
  • Timestamps: the source time travels with every sample; confirm the receiving application reads the same convention.
  • Quality: status bits keep an invalid measurement distinguishable from a valid one; if the mapping drops them, a bad value looks good.
  • Stored versus interpolated: know which retrievals return actual recorded samples and which calculate values between them.

CAS skips this mapping work for WinCC-native records, because the archives stay inside the WinCC access path; the trade is that CAS serves WinCC consumers, not the rest of the plant.

Sizing CAS storage for a WinCC station at 400 MB per day over a 3-year retention #

Inputs for this worked example:

  • Archive growth: 400 MB per day, the illustrative measured value for this example. Measure yours by sizing the station's archive folders after one full production month, with compression enabled.
  • Retention: 3 years, which is 1,095 days, this example's record-keeping requirement. Use the period your site or its regulations set.
  • Margin: 30 percent, this example's allowance for segments not yet closed, index and filesystem overhead, and growth. It is a design choice, not a vendor rule.

The rule: storage equals daily archive growth times retention days, multiplied by one plus the margin.

The arithmetic: 400 MB/day times 1,095 days = 438,000 MB; 438,000 MB divided by 1,000 = 438 GB, in decimal gigabytes; 438 GB times 1.30 = 569.4 GB. Provision a 600 GB volume for that one station.

The decision: one station at this growth fits a single CAS volume, and two stations at the same rate double the figure to about 1.2 TB provisioned. The threshold that moves the answer: when measured growth times retention days times one plus the margin, summed over every station, exceeds the storage you can give the CAS host, either shorten the retention or let the plant historian carry that history on its own budget. The arithmetic makes that call, and the final figure is worth checking against the platform's own sizing guidance before anything is ordered. Where a regulation or contract sets the retention period, treat it as a floor and prove readback across the whole span, the same discipline as verifying HMI historical trend retention before committing.

The decision by case #

Choose CAS when every required record originates in a WinCC station and every consumer works in WinCC. The project is then bounded and small: enable collection of the long-term-relevant values and alarms, size the host volume with the arithmetic above, and accept the system with a restore test that reads a known record from a known date through a WinCC client.

Choose PI when two or more source systems must share one history, or when consumers sit outside WinCC. The project is then a collection connection per source, point mapping that uses the consumers' names and units, storage sized to point count and write rate, and a retrieval test per application.

Before either, check the premise: if the only requirement is occasional report values, settle first whether you need a historian or just an OPC tag server.

The two products are not rivals for one slot. A plant can run CAS for WinCC-native retention while PI serves wider consumers, each with its own sizing and its own restore test. What neither archive delivers by itself is MES context such as production orders, batches and equipment states, so any MES or production-reporting requirement is a separate integration project on top of whichever platform holds the history.

Questions asked

Can WinCC CAS and a PI historian run at the same time?

Yes, and the split is clean: CAS keeps the WinCC-native long-term archives for WinCC users, while the PI historian serves consumers that sit outside WinCC or need several source systems in one shared history. Treat them as two storage systems with two sizing calculations and two restore tests, and decide per record type which platform is that record's system of record.

Does CAS remove the archives from each WinCC station?

No. The station keeps its local short-term archives, and CAS receives the long-term-relevant data onto a separate server for central retention. Old records are then read back through the CAS path, so confirm a full archive cycle before sign-off: one record written by the station, present centrally, and readable again from the central store.

How do I measure my WinCC archive growth per day?

Size the archive folders on each station, wait one full production month that includes your longest campaign, and divide the growth by the days elapsed. Repeat the measurement once to confirm it is steady, and measure with compression enabled if you use it, because compression changes the daily figure materially.

Does CAS storage on RAID remove the need for backups?

No. RAID on the CAS host covers individual disk failure only. Deletion, file corruption and loss of the whole storage system pass straight through a RAID array. Keep archive backups on separate media and test recovery by reading a known record from a known date through the intended client; a finished copy job alone proves nothing about readability.

Is a PI historian an MES?

No. A historian stores and serves time-stamped process data; an MES ties that history to production orders, batches, material lots and equipment states. Archive retention on either platform supplies none of that context by itself, so treat MES reporting as its own integration project with its own data model, separate from the storage decision.

Keep reading

  • How-to

    Backfilling PI from an existing plant historian

    Split the historian-to-PI backfill into four independent stages — extract, intermediate store, external compression, destination load — and qualify throughput with a measured pilot. Rows divided by elapsed seconds, not tag count, sets the schedule: 12,000 tags from 2020 at 500 rows/s is about 203 days. Check the native Historian 2023 replication route before writing pipeline code.

    Edge computing and IIoT

  • Explainer

    WinCC runtime archives versus a central process historian

    Each WinCC server archives its own tags at runtime; SIMATIC Process Historian is a separate central tier that collects the long-term-relevant tags and messages from multiple WinCC servers into its own SQL Server database. Keep runtime archiving on, keep archives on each server, and point long-term and cross-server queries at the historian.

    Edge computing and IIoT

  • How-to

    Connecting a Yokogawa ExaOPC server to Canary Historian

    Yes. Canary Historian's OPC client collector reads tags straight from ExaOPC, Yokogawa's OPC server for CENTUM, over DA or UA with no custom driver. Run the DA collector on the ExaOPC host or a same-domain host: cross-host DCOM is where these links break.

    Edge computing and IIoT