Troubleshooting
AVEVA historian trends stop until a TOP Server restart
Short answer
When historian trends fed from TOP Server freeze and come back only after a restart, the IDAS SuiteLink topic is not detecting the disconnect: Set To No Timeout disables the reconnect attempt and a very large Timeout delays it. Clear the no-timeout selection, set a finite timeout, and treat the EventService relogon failure for FV_Gas_Process as a separate event-tag login problem.
On this page
- Read the live value against the stored samples first
- Confirm the tags acquire through an IDAS SuiteLink topic
- Give the topic a finite timeout
- Set the timeout for a topic that must recover within one minute
- Treat the EventService relogon failure as a separate fault
- Prove the recovery with a controlled interruption
- The changes in order
- Questions asked
When historian trends fed from TOP Server freeze and come back only after the server is restarted, the IDAS SuiteLink topic behind those tags is not detecting the disconnect. Two settings decide that: Set To No Timeout removes the reconnect attempt entirely, and a very large Timeout delays detection by the whole configured interval. Clear the no-timeout selection, give the topic a finite timeout at or below the tolerated recovery time, and restart TOP Server once to clear the stuck session. The EventService relogon failure in the log is a separate event-tag login fault, so fix it on its own. Verify the result by comparing live TOP Server values with the historian's stored samples, not by the trend picture alone.
Read the live value against the stored samples first #
A genuinely constant process value draws a flat line, and a frozen acquisition can look identical. Before changing any setting, establish which side of the historian the interruption sits on.
- Pick an affected tag whose process value really changes, and record its name, the last stored timestamp, and the time the trend stopped moving.
- Read the same item live in TOP Server and record value, quality and timestamp, not the value alone.
- Query the historian directly for that time window and compare the returned samples with what the operator saw.
| Reading | What it means | Next check |
|---|---|---|
| TOP Server values stale or bad quality | The interruption is upstream of the historian | Driver and controller diagnostics on the TOP Server machine |
| TOP Server updates but stored samples stop | The topic connection or storage path failed | The IDAS topic's timeout settings, covered below |
| Historian returns fresh samples but the trend does not | The fault is in the trend client | Binding, time range and refresh behaviour |
Row three is a client-side fault rather than this one, and the guide on historian trend client connection failures walks that path. Rows one and two share one habit with the diagnosis of why PI shows live values but no trend history: separate the live value from the stored trend before touching configuration.
One caution: record these readings before restarting TOP Server, because the restart that recovers the trends also destroys the failed state you need in order to locate the fault.
Confirm the tags acquire through an IDAS SuiteLink topic #
The timeout fix in this article applies to tags that acquire through an IDAS topic connected to TOP Server over SuiteLink. Open one affected tag's acquisition configuration and trace it back: the tag points at a topic, and the topic points at TOP Server.
If several tags stop together while TOP Server still shows their items live, the shared topic connection is the suspect, and the timeout settings in the next two sections are the place to work. If a single tag stops while its neighbours keep logging, check that tag's item mapping and quality first; a wrong item binding is a different fault, and no timeout change will fix it.
If the acquisition path is not SuiteLink — direct OPC, for example — this topic timeout is not in the path, and the guide on how SuiteLink, OPC and PCS IData acquisition paths differ covers those alternatives. If TOP Server's own values have already stopped updating, resolve the driver or controller fault upstream first; a historian timeout setting cannot restore device data that never arrived.
Give the topic a finite timeout #
On a SuiteLink disconnect, the historian detects the dead topic through its timeout: once the timeout elapses on a silent connection, the historian disconnects the topic and attempts to reconnect. The documented default is 60000 milliseconds.
Set To No Timeout removes that check, so a dropped SuiteLink connection is never disconnected and reconnected; the topic sits dead until something outside the historian rebuilds it, which is exactly the restart-dependent behaviour in this fault. A very large finite Timeout produces the same operator symptom more slowly, because detection waits out the whole configured interval first.
Clear Set To No Timeout and enter a finite value. Two boundaries hold it from both sides: too long leaves operators watching stale data for the full interval, and too short triggers repeated disconnect-and-connect cycles when the source is slow to answer. Size it from the recovery requirement, as the worked example below does.
Set the timeout for a topic that must recover within one minute #
Inputs:
- Documented default topic timeout: 60000 ms, from the historian's topic settings documentation.
- Example recovery requirement: fresh samples on the trend within 60 s of a SuiteLink drop. This target is an example chosen for the worked case, not a documented limit.
- Documented mechanism: the reconnect attempt begins only after the timeout expires on the silent connection.
Rule in words: the timeout plus the reconnect handshake must fit inside the tolerated recovery window. The handshake duration is site-specific and undocumented here, so reserve half the budget for it.
Arithmetic: half the 60 s budget goes to the handshake reserve, so the timeout setting is 60000 ms ÷ 2 = 30000 ms, that is 60 s ÷ 2 = 30 s.
Result: enter 30000 in the topic's Timeout field with Set To No Timeout cleared.
Decision: if the trend must have fresh samples within one minute of a drop, the computed value meets it with margin for the handshake; if a full minute of stale trend is tolerable, keep the default; and a topic that must recover on its own never gets Set To No Timeout.
Treat the EventService relogon failure as a separate fault #
The log line Main EventService: Action failure ABANDONING the attempt to relogon FV_Gas_Process comes from the historian's event system, not from the sample path that feeds trends. Read it as: an event tag or an action tied to the name FV_Gas_Process tried to re-logon, the attempt failed, and the event system gave up. The message does not say a SuiteLink topic stopped acquiring, and the timeout change will not make it go away.
Work it as its own fault:
- Search the event tag and action configuration for FV_Gas_Process and identify the action attached to that name.
- Identify the connection the action uses — a database or another external system — and check the configured login, credentials and access rights at that destination.
- Test that login directly with the same account the action uses.
- Compare the failure time with the last stored sample; matching times usually mean both failures followed the same restart, not that one caused the other.
The two faults can share a clock and still be independent. Judging event messages separately from stored samples is the same discipline behind diagnosing slow historian trends by separating events from samples. Fix the event login until the action runs, fix the timeout until the topic reconnects, and test each path against its own success.
Prove the recovery with a controlled interruption #
After the settings change, prove the behaviour instead of waiting for a real outage. Schedule a short maintenance window, then break the SuiteLink path deliberately: stop and restart the SuiteLink service on the TOP Server machine, or block the network path between the two computers for a few minutes.
- Watch the topic status: detection should appear within the configured timeout, followed by the disconnect-and-reconnect.
- When the source returns, confirm new stored samples arrive within roughly the timeout plus the handshake.
- Run the test on a topic that does not feed an operator decision on a running process; a maintenance window or a bench machine is the right place.
If the topic stays down after the timeout expires, look at what changed at the machine boundary — firewall or switch changes are the usual suspects — and confirm TOP Server still serves fresh values from its driver and controller. If samples resume in the historian but the client still draws stale data, check that client's time range and refresh behaviour; the InTouch trend option named Reconnect as soon as possible and do not mark disconnects, for example, controls how a trend draws across a communication gap, and it changes the drawing, not the acquisition.
The changes in order #
- Record the affected tags, the last stored timestamps and the live TOP Server readings before touching anything.
- Confirm the tags acquire through an IDAS SuiteLink topic and that TOP Server itself serves live values.
- Clear Set To No Timeout on the topic and set a finite Timeout sized to the recovery requirement.
- Restart TOP Server once to clear the stuck session.
- Fix the FV_Gas_Process event action's login separately and prove the action runs.
- Verify with a controlled interruption: detection inside the timeout, stored samples resuming, the trend drawing again.
Questions asked
Is restarting TOP Server a fix for the frozen trends?
A restart forces a new SuiteLink session, so trends return immediately, but it changes no settings. The next disconnect freezes them again if the topic still has no finite timeout. Restart once to recover the current gap, then clear Set To No Timeout and set a finite timeout so recovery happens without anyone walking to the server.
What value should the topic timeout be set to?
Use the documented default of 60000 ms, which detects a drop and reconnects without tuning. Shorten it only when the trend must recover faster, as in the worked example above, and avoid very small values, because a source that is slow to answer would trigger repeated disconnect and connect cycles.
What is FV_Gas_Process in the EventService message?
It is the target the historian's event system was trying to re-logon to when it gave up, not one of your trend tags. Search the historian's event tag and action configuration for that name, then check the login and credentials of the connection behind the action. If nothing matches, the name may belong to a script or an external connection configured elsewhere.
The topic still will not reconnect after the timeout expires. What then?
Work through SuiteLink basics on both machines: confirm TCP/IP is operational, confirm the SuiteLink service is running and start it again if it has stopped, and check that each computer's node name is 15 characters or fewer. Firewall or switch changes during the outage are the other common suspects.