Ewon Flexy reboots when Ethernet is connected during VPN startup
Short answer
On firmware 13.x with a static IP on the WAN interface, a known NTP-related issue can make a Flexy reboot each time it tries to establish the VPN while Ethernet is connected. Disable NTP or upgrade to firmware 14, then start the tunnel over the 3G link with Ethernet connected to confirm the loop is gone.

On this page
A Flexy that reboots again and again while the VPN tries to come up with the Ethernet cable connected is not a failing 3G card or a broken tunnel service: on firmware 13.x with a static IP on the WAN interface, it matches a known NTP-related issue. Disable the NTP client, or upgrade to firmware 14, then prove the fix by bringing the tunnel up over the cellular link with Ethernet connected. The signature is specific: with the cable in place the tunnel never completes and the unit restarts; with the cable out the same tunnel connects; with the cable back in after the tunnel is up, Modbus TCP acquisition runs normally. That pattern ties the fault to connection establishment, so work through the checks below in order and apply one of the two fixes once your unit matches.
Reproduce the loop before changing anything #
Run three observations and write the results down; together they rule out the usual suspects before you touch any setting.
| Test | Result that matches this fault | What it rules out |
|---|---|---|
| Ethernet connected during VPN startup | Tunnel never completes, Flexy restarts, cycle repeats | A one-off tunnel failure |
| Ethernet unplugged during startup | Tunnel connects over the 3G card | A dead SIM, blocked VPN service or coverage fault |
| Ethernet reconnected after the tunnel is up | Modbus TCP acquisition runs normally | A bad cable, port or switch |
Also read the firmware version from the unit's web administration pages before moving on, because the diagnosis in the next section depends on it. If your unit reboots with the cable out, or the tunnel fails without a restart, the pattern no longer matches this fault: troubleshoot the tunnel and the cellular path first, because an NTP change will not fix those.
Match the firmware 13.x condition #
The reboot loop alone does not prove the NTP issue. The reported condition needs two things at the same time:
- firmware in the 13.x branch — 13s2 is the version reported on units showing this exact loop;
- a static IP address configured on the WAN interface.
Read both on your unit. With both present, treat the NTP-related issue as the working diagnosis and go to the first fix. With the affected firmware and a dynamic WAN address, the evidence does not tie the loop to NTP, so keep the WAN configuration and the cellular path as your first suspects. A unit that still loops after the upgrade no longer matches this fault either; its cause sits elsewhere.
Worked check: a Flexy 202 on firmware 13s2 with a static WAN IP #
The inputs, and where each comes from: a Flexy 202 with a 3G GSM card and Ethernet used for Modbus TCP acquisition (the reported case); firmware 13s2, read from the unit's administration pages; a static IP on the WAN interface, read from the WAN settings; and the three-part loop signature from the table above.
The rule in words: the fault applies when the firmware belongs to the 13.x branch and the WAN uses a static address; NTP is the reported mechanism, so removing NTP or leaving that branch removes the fault.
The check, written out: condition 1 — 13s2 sits in the 13.x branch, so condition 1 is met. Condition 2 — the WAN address is static, so condition 2 is met. Two conditions defined, two met: the NTP-related issue is the working diagnosis.
Decision and threshold: at 2 of 2 conditions met, apply fix one — disable the NTP client — and rerun the startup test. If the unit still loops with NTP off, apply fix two — the upgrade — and rerun the same test. A loop that survives both no longer meets either condition; that unit has a different fault, and the tunnel, power supply and SIM are the suspects to work through.
Fix one: disable the NTP client #
- Back up the Flexy configuration first, so the change can be reversed without rebuilding the unit.
- In the Flexy's web interface, open the settings group that handles time synchronization and switch the NTP client off. The manufacturer documents NTP client, server and relay modes for the Flexy in one article; it shows where each mode is set. For the WAN settings and the NTP relay settings side by side, the walkthrough in configuring WAN access and the NTP relay on a Flexy 205 covers both.
- Save the change and restart the Flexy.
- Leave the Ethernet cable connected and start the VPN tunnel over the cellular card.
- Confirm the tunnel completes with no restart, then power-cycle the unit once more and let it boot with Ethernet in place from the start.
If the tunnel now establishes with the cable connected, the NTP condition was the cause. Two side notes before you close the ticket: if other devices on the LAN take their time from the Flexy's NTP relay, give them another time source before switching the client off; and keep NTP disabled only while the unit stays on the affected firmware — the change that lets you run time synchronization again is the upgrade, not re-enabling NTP with the static WAN address still set.
Fix two: upgrade to firmware 14 #
Moving off the affected branch clears the condition and lets you turn time synchronization back on afterwards. Flexy firmware ships as an update file that you apply with the manufacturer's Ebuddy utility, push over FTP, or load from a USB or SD card. Take the file from the manufacturer's own download pages, match it to the exact model, and check the vendor's product list for the newest firmware available for that unit before you plan the work; some older models can no longer take current firmware, and that list says which.
Treat the upgrade itself as a bench task: do it with someone at the cabinet and in a window when the line can tolerate the tunnel being down. A gateway that is reachable only over its cellular link, and that reboots or sits mid-update, can leave the site unreachable exactly when you need to intervene. After the upgrade, re-enable NTP, restart, and rerun the verification below with the Ethernet cable connected.
Prove the fix on the cellular link #
- Cold-start the unit with the Ethernet cable connected and let the VPN come up over the 3G card; the tunnel must establish with no restart.
- Confirm Modbus TCP acquisition over Ethernet still polls its devices.
- Power-cycle and repeat the cold start once more. Two consecutive clean startups show the loop is cleared; a single pass can be luck.
- Each reboot in the old loop also dropped the acquisition sessions. If a MELSEC controller will not re-establish its TCP connection after the Flexy comes back, the checks in troubleshooting MELSEC TCP after Flexy 205 reboots cover that recovery.
One further failure can appear afterwards: the tunnel comes up and the Flexy holds a VPN address, but nothing answers a ping. That is a routing and client fault with its own checks, covered in why a VPN-connected Flexy gets an address but cannot be pinged.
Questions asked
Will the Flexy keep correct time with the NTP client disabled?
No. With NTP off, the unit runs on its internal clock, and logs, scheduled actions and time-stamped records depend on it. That is acceptable for a short test on this firmware, but for continuous running, re-enable time synchronization after the upgrade to firmware 14, once the static-WAN condition no longer applies.
What changes about NTP beyond firmware 14?
From firmware 15.0 on the Flexy and Cosy 131, the NTP server is disabled by default, and a unit that must serve time to the LAN as an NTP relay needs that server enabled manually in the system setup pages. The reboot-loop evidence itself stops at 14, so a looping unit already on 15.0 does not match this fault.
Is pulling the Ethernet cable a permanent workaround?
No. It works, and it is what the reported case did, but it leaves the NTP-related condition in place: the next reboot, power cut or tunnel drop puts the unit back into the loop with the cable present. Treat cable-pulling as a same-shift workaround and apply one of the two fixes.
What if the model cannot take current firmware?
The manufacturer publishes a product list pairing each Cosy and Flexy model with its newest available firmware, and notes that some older models can no longer move to current firmware because of cybersecurity requirements. If the list bars the upgrade, keep the NTP client disabled on that unit and use the unplug-Ethernet-until-the-tunnel-is-up routine, or plan a replacement with a current model.