Computing Library
Earlier articles
Explainer
When store-and-forward data counts as stored in the historian
InStoreForward = FALSE only clears the buffering indication. The documented transfer check is an empty Store-and-Forward folder, no .dat files, after the connection returns, with the loss flag never TRUE; durable commit into HistoryBlocks is proven separately by querying a known tag across the outage window.
How-to
No Windows 11 LTSC option for your industrial PC: what to do
A missing Windows 11 LTSC entry in a vendor configurator is a procurement gap, not an operating-system fault: Windows 11 IoT Enterprise LTSC 2024 was released October 1, 2024 and is supported until October 11, 2034. Get a written available, planned or unavailable answer for your exact model and region, then qualify factory image, drivers, automation software and recovery separately before you commit a delivery date.
Troubleshooting
Storing HMI recipe data in MySQL on an industrial PC
Yes. Host MySQL on the industrial PC and read recipe rows from the HMI with its SQL Query object, keyed on the barcode's model number. Install MySQL 8.0 with the legacy authentication selection, run the account with all roles and privileges enabled, and gate go-live on a schema load, a simulator test and a field-by-field barcode read.
How-to
Export selected Geo SCADA historian tags to another historian
Pull the selected tags through the documented SQL query interface in measured time windows, and write them to the destination through whatever interface that system's documentation accepts; use a customized transfer application only when the destination's ingestion needs application logic. Never read the historic database folder directly: it is a proprietary binary format held locked by the running server.
Troubleshooting
Linking AVEVA Historian to Omron PLC data through IDAS topics
A topic alone is not the fix. Build the chain: a DeviceSelector and a Device Group in Operations Integration Server Manager against the OMRONFINS device, a Historian topic matching that group for the IDAS and I/O server, then the tag's item address. Prove one test tag end to end before importing the rest.
Troubleshooting
When a firewall blocks SFTP as Psiphon traffic
The Psiphon label is the firewall's classification of the SSH handshake, not installed software, so there is nothing to remove. Excluding the encrypt-then-MAC hmac-sha2-256 MAC from the client's proposal with the -o MACs= option restores the transfer.
Troubleshooting
Citect Historian 2016 slow retrieval as SQL tables grow
Retrieval slow in both the Citect Historian Excel tool and a direct SQL query is a response-time problem in the SQL history tables, which grow with every historized row. Lower over-fast storage rates, purge to your retention, reindex, and start the migration to AVEVA Historian, since end of support for Citect Historian has been announced.
How-to
Disable pre-installed services with update-rc.d
Run update-rc.d with the disable option as root for each pre-installed init script, then reboot. That stops the native services from starting at boot without uninstalling them, so your container stack gets exclusive use of their RAM and ports.
Comparison
WinCC CAS versus PI historian for long-term archiving
WinCC CAS is a Siemens add-on that backs up, collates and archives long-term-relevant WinCC data from lower-level WinCC stations on one central server with RAID storage. PI is a separate plant-wide historian that collects from many source systems and serves many clients. Choose CAS when every record and consumer lives in WinCC; choose PI when several systems share one process history.
Troubleshooting
Fix Node-RED InfluxDB write errors after a network outage
When InfluxDB output nodes throw ECONNRESET after a network outage, Node-RED is usually still holding dead TCP client sessions. Confirm the database is reachable from the Node-RED host, then use the Deploy menu's flow-restart option to rebuild every connection while the runtime stays up.
Troubleshooting
Log paired Torque and Angle values for a live XY chart
The Tag Historian stores Torque and Angle independently, so no record ever pairs them and the XY chart plots mismatched points. Replace that storage for this chart with a SQL Bridge transaction group that samples both tags into one table row with a common timestamp, size its trigger evaluation rate from the shortest feature the curve must resolve, and bind Angle to X and Torque to Y from those rows.
How-to
Get the last N stored records from an Ignition tag history query
A positive returnSize in system.tag.queryTagHistory splits the window into that many time buckets and aggregates each one, so it never yields the newest N stored events. Query raw history with no fixed return size and noInterpolation=True over a bounded window ending at a fixed cutoff, count rows, and step back through earlier windows until you reach N.