Computing Library
Earlier articles
Troubleshooting
Why gateway scripts stop when the Ignition Edge Designer closes
If handshake or reset logic on an Ignition Edge gateway only runs while a Designer or Perspective session is open, the logic lives in session-scoped objects, which stop when nothing hosts a view. Move it to a Gateway Event timer or a tag event script keyed off the tag timestamp, then verify with zero sessions connected.
How-to
Migrate a TagHistoryProvider to Ignition 8.3.3
Ignition 8.3.3 removed the default getStorageEngine() from TagHistoryProvider, so a custom historian module that compiled before now fails to build. Keep the same historian-gateway SDK artifact and package imports: either extend LegacyTagHistoryProviderAdapter, which supplies the storage engine for Store and Forward, or add an explicit getStorageEngine() override returning your StorageEngine. Rebuild against 8.3.3 or later and confirm a known value round-trips through the provider.
How-to
Edge gateway commissioning sequence for plant data
Commission an edge gateway in a fixed order: mount and power it, prove each Ethernet and serial path at the interface level, configure one point, and verify that value against a trusted measurement before adding the rest. A link light or a successful ping proves transport only — never that the engineering value is right.
Troubleshooting
Why configured DCS tags are missing from historian records
Matching History Collection Configuration proves nothing until the Continuous Historian has been downloaded after those settings were defined. Check license acceptance next: a license sized at 1250 DST disables enough tags to run within entitlement once the configured count exceeds it. Then confirm the tag's live value and quality at the collection interface.
Troubleshooting
Remove DeltaV Continuous Historian points when Delete is grayed out
The Delete button is grayed out because the history point is defined in the module class, not at the instance: only instance-added points can be deleted in DeltaV Explorer. Class-owned points come out by editing the class or shrinking the historian's area assignment, and the blocked download clears once the licensed parameter count drops.
Troubleshooting
Why a historian report template lacks identification fields
The Historian Analysis templates in Report Engine v10 expose four columns: variable, timestamp, value and status flags. Neither they nor the Historian Trend Analysis template offer Identification or Resource Labels, and no template setting adds them. Pull that metadata through the archive's documented data-access layer into a custom report, or escalate to the vendor with the exact version and field list.
Selection guide
Backfilling Wonderware Historian data into PI: connector or RDBMS
For outages and gaps on tags the connector already serves, keep the PI Connector for Wonderware Historian: recovery runs from each tag's last known good timestamp and, before release 1.3.0.2, reaches at most four days back. For older history and migrations, use the PI Interface for RDBMS; there is no OPC HDA route into Wonderware Historian.
Explainer
Log one-second trends and one-minute reports in one historian
Yes. One historian archive serves both rates: keep the one-second acquisition for trends and add either a second one-minute logging schedule on the same tag or a one-minute aggregate computed from the one-second records. Choose the aggregate for sums and averages, the second schedule only when the report must acquire its own minute value; one-second logging stores 60 times the records.
Explainer
Why Historian replaces a client-set ReceivedTime
Yes, it is expected: Historian assigns ReceivedTime itself, as a UTC receipt stamp, when the server accepts the event, and no option preserves a client value. EventTime is the field your application owns — set it to the occurrence time, drop the ReceivedTime assignment, and carry any third timestamp as a custom property.
Troubleshooting
Why only Historian Trend follows a redundant partner
Only Historian Trend, in the Client Desktop package, follows the partner of a redundant Historian pair; Historian Query and Historian Client Web stay bound to the failed primary until you repoint them or move a network alias. Trend then stays on the partner by design until its connection drops or a new connection attempt starts.
Troubleshooting
Historian gaps after copying history blocks between servers
When every tag loses the same whole 24-hour intervals after a block copy, the data is almost always present and the destination index is stale. Count the destination's blocks against the days covered; if the count matches, rebuild the historian index per the documented procedure before you drop and recreate the database.
How-to
Inhibit historian logging of one tag with a Boolean gate
There is no per-tag inhibit command. $HistoricalLogging is global: writing 0 to it stops InTouch historical logging for the whole application. Instead, log a memory Real tag that copies the process tag only while a Boolean permits, keep the live tag updating for display and alarms, and force one catch-up copy when the inhibit clears.