IMD SolutionComputing LibraryShop main store

Comparison

PCS 7 CAS versus Process Historian: which archive to deploy

Edge computing and IIoT Published 9 min read

Short answer

Deploy the Process Historian on new and upgraded PCS 7 systems: it ships on the PCS 7 media, licenses by archived value count, and lands OS tags, messages and BATCH data in one SQL database. Keep the Central Archive Server only as a read-only archive for OS generations the current collector cannot read.

On this page
  1. What changes between CAS and the Process Historian
  2. Why the Process Historian is the default
  3. Where the Central Archive Server still fits
  4. Information Server is not the collection path
  5. How the data reaches the historian
  6. Example: counting the archived values that size the Process Historian license
  7. Bringing the historian online
  8. Failures this station class repeats
  9. What proves the archive is central
  10. Questions asked

When a trend on a PCS 7 operator station stops at a date nobody chose, the OS server has answered from its own local archive and nothing carried the query further back. On current PCS 7 releases, the component that carries it is the Process Historian; the Central Archive Server is the component it replaces. Deploy the Process Historian on every new or upgraded system: it ships on the PCS 7 media, licenses by archived value count, and lands OS tag values, OS messages and BATCH data in one SQL database. Keep the Central Archive Server only where a plant area is frozen on an OS generation the current collector cannot read, and run it read-only from the day the historian goes live.

What changes between CAS and the Process Historian #

Both products sit behind the OS servers and hold process values and messages longer than the local OS archives do. They separate on the things that decide a deployment: how they are delivered, what stores the data, what they collect, and how they are licensed.

Criterion Central Archive Server (CAS) Process Historian (PH)
Delivery Separate product, set up as its own PC station Ships with PCS 7, installed on its own station from the same media as the OS and BATCH software
Storage layer StoragePlus stores and serves the archive SQL database the historian manages itself
What it collects Archive segments handed over by the OS servers Tag values, messages and BATCH data from OS and BATCH servers, all in one database
Read access beyond the OS window StoragePlus clients plus OS trend forwarding OS trend and alarm forwarding; Information Server on top for reports, web and Excel
License scope CAS application plus StoragePlus Archived value count, with Information Server added only if reporting is required
Version alignment A second product chain to keep in step with the OS generation One release and one patch level across OS, BATCH and historian

The second row decides most deployments. The Process Historian manages its own database, so there is no second storage product to license, patch and hold at the OS generation's patch level.

Why the Process Historian is the default #

The Process Historian comes out of the PCS 7 setup, so the archive station, the OS servers and the BATCH servers stay on one release and one patch level instead of two product chains drifting apart. OS tag values, OS messages and batch records land in the same database — the only arrangement in which one report can join a batch to the process values recorded while that batch ran. Licensing runs on the archived value count you size, with no second storage product beside it.

Information Server goes on top when reporting, web publication or Excel access is in scope, and stays off when they are not. It never changes what is collected.

Where the Central Archive Server still fits #

Keep CAS where a plant section is frozen on an OS generation the current collector cannot read. CAS is its own product on its own version line — 7.0 SP3 is a released version with a documented upgrade path from it — so a frozen section runs it without dragging the rest of the project along. Its documented job is a central long-term archive for any amount of process data and messages from different data sources, which is exactly what a frozen section needs: a passive store that keeps serving what it already holds. Set it read-only on the day the historian goes live: no new data sources, and the station retires when the section does.

Read-only still means the OS clients need to know where to hand a query older than the local window, and the walkthrough on configuring a PCS 7 OS client to read CAS-archived process values covers that configuration step by step. If the comparison on your table is instead CAS against an external PI system for long-term archiving, that is a different decision with its own article: the WinCC CAS versus PI historian comparison.

Information Server is not the collection path #

One mix-up wastes a server, so it is worth stating bluntly: Information Server is not the collection path. Data moves from the OS and BATCH stations into the Process Historian database on its own. Information Server sits on top of that database and turns it into reports, web pages and Excel extracts. If the archive is empty, adding Information Server changes nothing — the fault is upstream, at a collector or at the forwarding configuration.

The vendor documents Process Historian and Information Server together, in one installation, operation and maintenance manual for long-term archiving in a PCS 7 environment. That manual is the sizing and commissioning reference for the pair.

How the data reaches the historian #

Each OS server writes tag values and messages into its local segmented archives first — archives sized for continuous operation, not for plant lifetime. A collector component installed with the OS station forwards values and messages to the historian station, and a BATCH server forwards batch data the same way. If the terminal bus link drops or the historian is down for maintenance, the collector buffers locally and backfills once the link returns, so the series closes instead of showing a hole.

On the read side, nothing changes for the operator. The OS client asks its OS server for a time range; when the range falls outside the local window, the server forwards the query to the central archive and merges the answer. That forwarding lives in the OS project configuration and is downloaded to the servers — skip it and you get a healthy historian collecting data nobody can see from a faceplate. When tag values never arrive at a Process Historian 2014 station while every OS screen looks healthy, the fault is on this path, and why WinCC tag data never reaches Process Historian 2014 walks it end to end.

Example: counting the archived values that size the Process Historian license #

Inputs, each from the example project — a mid-size continuous unit; count your own from the OS tag list:

  • Two OS servers, archiving 5,000 process values each.
  • Cyclic logging at a 1 s cycle.
  • A record-retention target of 3 years.
  • 24 h × 60 min × 60 s = 86,400 s in a day.

The rule: the historian license scope is sized on archived values, so the count multiplies values per server by cycles per day, by servers, by years kept.

The arithmetic:

  • Per OS server per day: 5,000 values × 86,400 s/day = 432,000,000 values/day.
  • Both servers: 432,000,000 × 2 = 864,000,000 values/day.
  • Per year: 864,000,000 values/day × 365 days = 315,360,000,000 values/year.
  • Held at the end of the retention target: 315,360,000,000 values/year × 3 years = 946,080,000,000 values.

The result: cyclic logging at that cycle writes 864 million archived values a day and holds about 946 billion values at year three.

The decision: size the license scope to the counted total, not to the 10,000-line tag list — the tag list understates the total by the cycle factor. If the plant logs on change, re-run the count with the share of cycles that actually carry a new value, measured from the OS archives. If the counted total overshoots the largest archived-value class the release documents, cut the stored resolution on stable tags and on old data before enlarging the license — reducing stored historian data older than six months is that move written out. Verify the active license scope on the deployed station before sign-off.

Bringing the historian online #

  1. Size the machine before anything else: count archived tags and their cycles, add message rate and batch volume, and split the disks — database on its own volume, transaction log and segment backup destination separated from it. The archive station runs around the clock; when you specify the machine, a fanless industrial mini PC is the usual cabinet format for a historian box.
  2. Put the station in the same domain or workgroup naming scheme as the OS and BATCH servers, and prove name resolution works in both directions before installing anything.
  3. Install from the PCS 7 media so the database engine, the historian and the station software come from one release, then hold every station at that patch level.
  4. Apply the historian license for the counted archived value scope, and keep the count with the project documentation so the next upgrade inherits it.
  5. Install the collector component on every OS and BATCH server and point it at the historian station name.
  6. In the historian management console, confirm each data source appears and reaches an active state, set segmentation and retention, and define where segments are backed up.
  7. Configure long-term trend and message forwarding in the OS project so queries beyond the local window reach the central archive, then download and activate it.
  8. Add Information Server only when reporting is in scope, connected to the historian database as its data source.
  9. Set every station — historian included — to the same plant time master before the first segment fills.

Failures this station class repeats #

Stations of this class fail repetitively, and almost none of the failures announce themselves on an OS screen.

Symptom Cause Where to look
Data source drops to inactive after a restart Historian station name not resolvable from the OS station Name resolution in both directions; the station entry in the collector configuration
Gap in the trend across a known outage Collector service stopped, or the local buffer volume filled Collector service state on the OS station; free space on the buffer volume
Timestamps drift between OS archive and historian Station not following the plant time master The synchronization path from the master to the historian station
Archiving stops silently, no new segments Database volume full, or the segment backup destination unreachable Free space on the database volume; the backup path and its access
Query beyond the OS window returns empty while the historian fills Long-term forwarding not configured, or not downloaded The OS project configuration, then a re-download
Queries crawl while the database CPU runs pegged Antivirus scanning database and backup files Scanner exclusions for the database and segment directories

What proves the archive is central #

Run the acceptance in this order:

  • In the historian management console: every OS and BATCH source connected, and the segment count increasing.
  • On an operator client: open a trend and request a window earlier than the local OS retention — the curve must continue, not restart.
  • On the alarm list: filter on a date beyond the local message window and confirm messages return.
  • On BATCH: retrieve a completed batch record older than the local window and confirm it comes back joined to the process values recorded while it ran.

The decision, case by case. A new or upgraded PCS 7 system: deploy the Process Historian, license it on the counted archived values, and verify the scope on the deployed station. A frozen plant section the current collector cannot read: keep CAS, read-only, until the section retires. Reporting, web or Excel access in scope: add Information Server on top of the historian database — never as the collector. Everything else is configuration.

Questions asked

Does the Process Historian need StoragePlus as well?

No. StoragePlus is the storage and serving layer of the Central Archive Server route, so that pairing stays with CAS. The Process Historian manages its own SQL database and stores and serves the archive itself. Information Server is a separate optional add-on, used only when reporting, web publication or Excel access is in scope.

What happens to the trend when a redundant OS pair switches over?

A redundant OS server pair is registered with the Process Historian as one data source, so a partner switchover continues the same series instead of splitting it into two. If a step appears in the trend at every switchover, look for the pair registered twice, or the collector service stopped on one partner.

What does an undersized historian license look like in operation?

Not an error on the operator screen. The historian stops accepting a data source, so a server drops to inactive in the historian management console while the OS station itself looks healthy. Check source state and license scope on the historian station, never at the client, and compare the scope against the counted archived values rather than the tag count.

How far back does an OS trend reach without a central archive?

Only to the oldest local archive segment still on the OS server. Local archives are sized for continuous operation, not for plant lifetime, and the depth moves with segment size and free disk on the OS server. Anything older has to come from the central archive, which is why long-term query forwarding is configured in the OS project and downloaded.

Keep reading

  • Comparison

    WinCC CAS versus PI historian for long-term archiving

    WinCC CAS is a Siemens add-on that backs up, collates and archives long-term-relevant WinCC data from lower-level WinCC stations on one central server with RAID storage. PI is a separate plant-wide historian that collects from many source systems and serves many clients. Choose CAS when every record and consumer lives in WinCC; choose PI when several systems share one process history.

    Edge computing and IIoT

  • Explainer

    WinCC runtime archives versus a central process historian

    Each WinCC server archives its own tags at runtime; SIMATIC Process Historian is a separate central tier that collects the long-term-relevant tags and messages from multiple WinCC servers into its own SQL Server database. Keep runtime archiving on, keep archives on each server, and point long-term and cross-server queries at the historian.

    Edge computing and IIoT

  • Explainer

    AVEVA Historian 2023 R2 license backward compatibility explained

    Yes. AVEVA knowledge base 000033942 lists Historian among the 2023 products whose licenses are backward compatible to their 2017 versions, and one field test reports a 2023 R2 license running Historian 2020 R2. That clears the license layer only: Citect 2016 connectivity must be proven through the Plant SCADA Connector and CtAPI path.

    Edge computing and IIoT