What a SCADA runtime license covers beyond running the project
Short answer
A runtime license is permission to run a configured project; OPC UA is a data transport and SQL or ODBC is a query path into stored history. Triad's published feature list shows the VTScada ODBC Server and OPC Server on runtime license tiers, but you must confirm the exact interface role for your installed version before building a thin client or external query around it.
On this page
A SCADA runtime license answers one question: may this machine run the configured project? It does not by itself answer whether an external client may read live values over OPC UA, whether reporting software may query stored history through SQL, or where that history lives. Those are three different decisions — entitlement, transport and storage — and mixing them up is how a trial project quietly becomes an unsupported production design.
For VTScada specifically, the vendor's published feature list shows the ODBC Server and OPC Server included on its runtime license tiers, alongside features such as email, SMS and voice. That is a strong documented signal, but it is the published list for named tiers, not a guarantee for your installed build: confirm the entry for your exact version before you architect around it.
The three things people confuse #
Separate the question into entitlement, transport and storage before you touch any configuration screen.
Entitlement is the license. It decides whether the machine may run a project at all, whether you may edit that project, and which interfaces the vendor includes at that tier. You read it in the vendor's license documentation, never by observing what a running system happens to do.
Transport is the protocol path. OPC UA moves live values between a server and a client over standardized, security-capable protocols; an ODBC connection moves query results over SQL. A working connection proves the transport — nothing about the license and nothing about the data.
Storage is where history lives. VTScada stores tag history in its own historian, whether or not any external client ever connects. Configuring an OPC UA endpoint or an ODBC Server does not move that history; it only opens a window onto it. If you are deciding where history should live for a new host, the trade-offs are laid out in the article on choosing a site historian for a PC-based SCADA host.
OPC UA: which side is the server? #
The role matters more than the protocol name. VTScada can act as an OPC UA server, exposing tags to external clients, and it can act as an OPC client, consuming data from PLCs and RTUs through its driver set. Configuring one direction does not enable the other, and the license documentation may treat the roles differently.
If an external application needs current values, decide first which side serves: your SCADA host exposing tags, or the host acting as a client to another server. Then check the license entry for that role. When a SCADA node or gateway sits in front of a historian and external consumers, also decide deliberately which tags it exposes — the article on exposing only approved Ignition tags to an external historian makes the same point for a different platform: an open gateway hands out whatever you did not filter, not whatever you meant to share. And if the same gateway accepts anonymous reads, the article on what anonymous OPC UA gateway access exposes from a historian shows how much a historian can leak through an unauthenticated path.
If the sentence you are working on is about reading variables from a controller without standing up an OPC UA server at all, the article on reading ctrlX CORE variables without an OPC UA server covers that alternative approach.
SQL and ODBC: query access is not history storage #
VTScada's ODBC Server is a documented reporting interface: standard reporting software — Crystal Reports, Microsoft Access, Excel and similar tools — extracts data from a running system using SQL and the VTScada ODBC driver. The vendor positions this as the path for reporting tools that run alongside the SCADA system without a development license, which is exactly the pattern the reporting-tool rumor rests on.
But read the direction carefully. An ODBC Server on the SCADA host lets outside tools query data the system already holds. It is not the same feature as configuring the project to write tag history into a separate external database. Before you build, write down which of these you need:
- A reporting tool querying history the VTScada historian already stores — ODBC Server access, covered on runtime tiers per the published feature list.
- A thin client displaying history to operators — client access to the running server, subject to the client licensing terms.
- Tag history written into an external SQL database as the store of record — a project-side configuration, a different feature with different license implications, and one that changes where your data ownership sits.
A successful login to the database, or a successful connection from the reporting tool, proves transport only. Confirm a known tag, value and timestamp end to end before you call the path proven.
What the demo key does to all of this #
You are working in the 90-day trial with the Water and Wastewater Demo, so the demo-key rule applies to everything you build now. Trihedral documents that an application created or edited using a demo key must be run once under a development license before it can be used on a workstation with a runtime license.
That rule is easy to trip over in a small plant. If you configure the ODBC Server tags, the OPC UA exposure and the thin-client layout entirely under the trial key, then drop the project onto a runtime-licensed production machine, the project is not legitimate there until it has run once under a development license. Budget that step — a development license on an engineering workstation — into the deployment plan rather than discovering it at commissioning.
Working through a thin-client history query on a runtime license #
Take the case in question: you want a thin client to connect to the server and query tag history, with the project running on a runtime license.
The inputs: the project runs on a runtime license; the history lives in the VTScada historian on that server; the consumer is a thin client, not an editing session; the query path is the server's own history interface or the ODBC Server; the work so far was done under the demo key within its 90-day window.
The rule, stated as a check rather than a formula: for each role in the design — runtime execution, client access, reporting interface, project editing — find the explicit entry in the vendor's license documentation for your version. A role with a documented entry on the runtime tier is covered; a role with no documented entry is unconfirmed, and an unconfirmed role cannot carry a production design.
Working it through: runtime execution of the configured project — documented as the runtime license's purpose — covered. Thin client reading history from the running server — client access, documented separately from development rights — covered at the tier's client terms. Reporting software querying through the ODBC Server — listed on runtime tiers in the published feature list — covered, pending a version check. Editing the project from that machine — not covered, and not needed here. The demo-key project — requires one run under a development license before the runtime workstation may use it — a required step, not yet done.
The result: the design as stated is license-consistent, with two conditions attached. The result also shows the threshold that moves it: the moment the thin client or reporting tool needs live data through OPC UA as well, that role joins the check list, and if your version's documentation does not name the OPC UA server function on your tier, that piece stays unbuilt until the vendor confirms it.
The decision: build the thin-client history access on the runtime license after running the project once under a development license and confirming the ODBC Server entry for your installed version. Do not add the OPC UA exposure until its role is confirmed the same way.
Prove the path before the plant relies on it #
License coverage, transport and correct data are three tests, and only the last one protects the operators.
- Record the license state of the target machine and the exact version. Confirm each interface role — OPC UA server or client, ODBC Server, thin-client access — in the license documentation for that version. Anything unnamed stays unconfirmed.
- Bring the project onto the runtime machine by the documented route: one run under a development license if it was built under the demo key.
- Pick one known tag. Read its live value on the SCADA screen, then read it through the external path — the OPC UA client or the SQL query — and compare, including quality and timestamp.
- Run a bounded history query over a period you can check by hand, and compare the returned records against the historian's own trend for that tag.
- Repeat under the production license and the production client arrangement. A result proven only on the trial key proves the trial, not the plant.
If a value comes back wrong or stale, trace it backward before blaming the license: screen tag, binding, interface, endpoint, source. A failed read is a transport or configuration fault far more often than an entitlement one, and the license documentation — not the error message — is what settles that branch.
The one-line answer to the original question: yes, the published VTScada feature list puts the ODBC Server and OPC Server on runtime tiers, so a runtime-only deployment with a thin client querying history is the supported pattern — provided you confirm the entries for your installed version, run the demo-built project once under a development license, and keep the historian as the store of record rather than assuming a connection moved it.
Questions asked
Can a third-party reporting tool query VTScada history with only a runtime license?
Trihedral's published feature list puts the VTScada ODBC Server on its runtime license tiers, and that interface is what lets standard reporting software read data from a running system using SQL and the VTScada ODBC driver. Confirm the entry for your exact version and tier in the current license documentation, because tier contents change between releases.
Does the 90-day trial license become a runtime license when it expires?
No. The trial is a time-limited evaluation key, and work done under it carries a documented condition: an application created or edited with a demo key must be run once under a development license before a workstation with a runtime license can use it. Plan that development-license step into the deployment, or rebuild the project on a properly licensed machine.
If my client connects to the OPC UA server, does that prove the license covers it?
No. A connected client proves only that the network path, endpoint address and security policy are right. License coverage is a separate question answered by the vendor's documentation for your version, and correct history is a third question answered by comparing a known tag, value and timestamp against the source.
Should I point every external consumer at the SCADA server, or at a historian?
Keep the historian as the store of record and give bulk or reporting consumers a query path into it, reserving the OPC UA path for consumers that need live values. Before exposing anything outside the OT network, review what the interface exposes, because anonymous or unfiltered gateway access can hand over more tag data than you intend.