Edge computing and IIoT Published 6 min read

Short answer

Missing DDATA with Node Info and Control populated is not an unsupported-datatype fault: MQTT Modules releases 4.0.13 and later carry String and DateTime arrays, and 4.0.14 and later carry Sparkplug v3.0.0 compliance. Record both module builds, update MQTT Transmission and MQTT Engine to 4.0.18, retest with the arrays enabled, and escalate with Ignition logs if DDATA stays absent.

On this page
  1. Why does MQTT Engine show Node Info and Control but no DDATA?
  2. Which module release supports Sparkplug 3.0 and String or DateTime arrays?
  3. Why is version support not the whole answer in the reported case?
  4. What do you record before updating the modules?
  5. How do you update and retest both modules?
  6. How do you prove the retest exercised the arrays?
  7. What goes to the vendor when DDATA still does not appear?
  8. When do you update and when do you escalate?
  9. Questions asked

If MQTT Engine populates Node Info and Control but the DDATA metrics never reach the tag browser while String and DateTime arrays ride in the payload, do not treat the datatypes as unsupported: both capabilities shipped before the builds in the reported case, so the fault sits in the module pairing or the modules themselves, not in the data. Record the release and build identifier of MQTT Transmission on the publisher and MQTT Engine on the consumer, update both modules to release 4.0.18, and retest with the arrays enabled; a rebirth followed by a deliberate value change proves the retest actually exercised them. If DDATA is still absent on matching current releases, download the Ignition logs from both servers and open a ticket with the module vendor. The sections below give the version floors, the arithmetic that closes the datatype question, and the decision for each case.

Why does MQTT Engine show Node Info and Control but no DDATA? #

Because the receiving side holds them back: in the reported case, MQTT Engine received the node births and populated Node Info and Control, but no DDATA metric appeared in the tag browser while String or DateTime arrays were present in the transmitted payload.

That split — births arrive, data does not — localizes the fault to the Engine side of the link or to the content of the data messages, because a publisher connection problem would starve the births too. The same birth-without-data shape exists one layer down when a Sparkplug-aware collector logs DBIRTH but ignores DDATA; that variant has its own causes and fix in why an MQTT collector logs DBIRTH but ignores DDATA.

Which module release supports Sparkplug 3.0 and String or DateTime arrays? #

String and DateTime arrays are supported from MQTT Modules release 4.0.13, and Sparkplug v3.0.0 compliance from release 4.0.14, so any module at 4.0.14 or later carries both capabilities.

Capability First MQTT Modules release that carries it
String arrays and DateTime arrays as transmitted metrics 4.0.13
Sparkplug v3.0.0 compliance 4.0.14

Sparkplug 3.0 is the Eclipse specification that fixes the birth-and-data contract this fault lives in: an edge node announces every metric it will send in one birth message and then sends later values for those metrics as data messages. A consumer that builds the node tree but swallows the data messages is breaking its half of that contract, not missing a datatype the publisher invented.

Why is version support not the whole answer in the reported case? #

Because both reported builds already clear both floors — Transmission 4.0.16 and Engine 4.0.14 against floors of 4.0.13 for the arrays and 4.0.14 for compliance — the unsupported-datatype theory cannot stand, and the mixed revisions move to the top of the suspect list.

Worked check on the reported pair: MQTT Transmission 4.0.16, build b2023041422, publishing to MQTT Engine 4.0.14, build b2022121422.

  • Array floor 4.0.13: 4.0.16 is above it and 4.0.14 is above it, so both sides support String and DateTime arrays.
  • Compliance floor 4.0.14: 4.0.16 is above it and 4.0.14 sits exactly on it, so both sides are Sparkplug 3.0 compliant.
  • Observed result: DDATA appeared only after every String and DateTime array was filtered out of the payload.

Both checks pass and the fault still follows the arrays, which leaves a mixed-revision interaction, a module defect, a configuration setting or the message content itself as the remaining explanations. The arithmetic closes the datatype theory; only a same-release retest and the logs separate the rest.

What do you record before updating the modules? #

Capture the exact release and build identifier of MQTT Transmission and MQTT Engine on both servers, and keep a copy of the failing configuration that carries the String and DateTime arrays, because the support investigation will ask for every one of those items.

The Ignition gateway lists each installed module with its version and build identifier, so copy both numbers for Transmission on the publishing server and Engine on the receiving server exactly as printed. Export or snapshot the Transmission configuration that defines the arrays, because the clean retest after the update needs the identical payload. With those two numbers and the payload description, a colleague can reproduce the fault without guessing.

How do you update and retest both modules? #

Update MQTT Transmission and MQTT Engine to release 4.0.18, the version the module vendor recommended for this reported behavior, then restore the arrays and watch the Engine tag browser for the DDATA metrics to populate.

  1. Pick a window first: a module update restarts the Ignition gateway, and the Engine's live tags drop until it comes back.
  2. Update MQTT Transmission on the publishing server and MQTT Engine on the receiving server to the target release, and keep both on the same release level.
  3. Restore the recorded configuration so the String and DateTime arrays are back in the transmitted payload.
  4. Trigger a rebirth from the edge node so its birth message re-announces every metric, arrays included.
  5. Change one value inside an array and confirm the data message reaches Engine and the array metrics land in the tag browser under the node.

Steps 4 and 5 are the test; an update alone changes nothing the tag browser can show until a birth and a change of value have both happened.

How do you prove the retest exercised the arrays? #

Force a rebirth and then change an array value: the rebirth makes the edge node re-send its complete birth with every metric, and DDATA publishes only when a value changes, so a retest without both steps proves nothing about the arrays.

Rebirth is the lever for the first half, and when to use the Sparkplug rebirth tag on an edge node covers the tag and its timing. The change-of-value half exists because Sparkplug B sends DBIRTH once and DDATA only on change, which why Sparkplug B sends DBIRTH once and DDATA only on change explains in detail. Read the browser after both halves: Node Info and Control should stay populated and the array metrics should arrive with the data.

What goes to the vendor when DDATA still does not appear? #

Download the Ignition logs from both servers and open a support ticket with the module vendor, Cirrus Link, including the two module releases with their build identifiers, the affected array types, and the test results with and without the arrays.

Put these in the ticket:

  • Both module releases with their build identifiers, copied exactly from the gateway module list.
  • The affected array types and where they originate, for example a string array bridged from an OPC UA server on a PLC.
  • The result matrix: arrays present and DDATA absent, arrays filtered and DDATA present, and the outcome after the module update.
  • The log bundles from both servers covering a window in which a data message should have arrived but did not.

State up front that both builds clear the documented floors for the arrays and for Sparkplug 3.0 compliance; that one sentence removes the first round of version questions from the exchange.

When do you update and when do you escalate? #

Update before anything else when either module sits below the array-support floor, update both to the current release when a compliant pair still drops DDATA, and escalate with logs when the current release on both sides still fails.

  • Either module below 4.0.13: String and DateTime arrays are not supported on that release, so update first, and flatten or string-join the arrays in the bridge only as a stopgap until the update lands.
  • Both modules at 4.0.14 or later with arrays enabled and DDATA missing: the datatype question is closed; update both to 4.0.18 and rerun the rebirth-and-change test from the steps above.
  • Both modules on 4.0.18 with arrays enabled and DDATA still missing: stop changing configuration, collect the logs from both servers, and open the ticket with the result matrix — the fault now belongs to the vendor's investigation.

Questions asked

Is Sparkplug 3.0 an official standard?

Yes. The Eclipse Foundation announced on 7 November 2023 that the Sparkplug 3.0 specification had been published as an international standard, so the compliance floor is a published requirement rather than a vendor label. The MQTT modules for Ignition reached v3.0.0 compliance before that announcement, which is why the version check in this article uses the module release, not the standard's publication date.

Do the MQTT modules need MQTT 5.0 for these arrays?

No. The MQTT modules for Ignition are Sparkplug compatible and run over both MQTT 3.1.1 and MQTT 5.0, so the broker protocol is not what gates String or DateTime arrays or DDATA delivery. Keep protocol choice out of the first troubleshooting pass and work the module releases and payload content instead.

Can MQTT Transmission and MQTT Engine stay on different releases?

They can run that way, but a mixed pair makes the cause hard to assign because either side can hold the behavior. The reported case paired Transmission 4.0.16 with Engine 4.0.14 and never isolated which side suppressed the data. Keep both modules on one release level, 4.0.18 for example, so a retest changes a single variable.

Does filtering out the arrays prove the datatypes are unsupported?

No. A filtered run that brings DDATA back is an isolation result: it establishes only that the failure depends on the arrays being present in the payload. It does not tell you whether a module defect, the mixed revisions, a configuration setting or the message content is responsible, so do not close the investigation on it.

Which Ignition tag types do the bridged arrays map to?

String arrays and DateTime arrays are standard entries in the Ignition tag data type table, so an OPC UA value of those types needs no conversion to exist as an Ignition tag. The failure described here happens after the tag model, in what the modules transmit and how the receiving Engine handles it.

Keep reading

  • Troubleshooting

    Why MQTT Engine shows online status after an edge node drops

    An Info/Online tag that stays true with Good quality is not proof the edge node is alive: Engine's online state comes from the node's Sparkplug death certificate, and earlier Engine versions marked tags stale only on Engine shutdown. Read Info/Online, tag quality and Store & Forward stored metrics as three separate indicators, retest on Engine 4.0.8 with Ignition 8.0.16 or later, and compare against a node that reports correctly before escalating.

    Edge computing and IIoT

  • Troubleshooting

    MQTT Transmission connected but missing from the node list

    A connected badge only certifies the broker session; the gateway node list fills from the node's birth message and subscriptions. The compatibility matrix lists module 4.0.13 as supported on Ignition 8.1.21, so the fault sits in subscription behavior or MQTT Server ACLs. Read three logs from one attempt, repair the specific grants, and roll the new edge back to Ignition 8.1.18 with module 4.0.8 if production waits.

    Edge computing and IIoT

  • Troubleshooting

    Sparkplug node stuck on Connecting while MQTT connects

    The node-red-contrib-sparkplug node takes its broker string literally and adds no transport scheme, so a bare IP:port is rejected before any connection attempt and the node sits on Connecting with no error. Write the broker as a full URI — tcp://192.168.1.50:1883 for plaintext or ssl://host:8883 for TLS — deploy, and it connects where the default MQTT node already did.

    Edge computing and IIoT