Troubleshooting
Why a remote access router goes offline after one hour
Short answer
The hourly offline cycle comes from the router's Max outgoing call duration, which defaults to 60 minutes and closes the Talk2M session on schedule even though the internet link itself is fine. Set it to 0 for an unlimited session, or to a longer site-approved value, then confirm the fix with separate WAN and gateway tests.

On this page
- Why does an eWON Flexy go offline after exactly one hour on Talk2M?
- How do I prove the timer, not the internet link, is failing?
- What is Max outgoing call duration and where do I change it?
- What value should the Max outgoing call duration get?
- Why do devices behind the eWON keep internet access while Talk2M shows offline?
- What if the unit still drops offline after the change?
- What goes into the support file when the cycle continues?
- Questions asked
An eWON Flexy that turns offline in eCatcher on a fixed schedule has not lost its internet link; the Talk2M session is being closed by the unit's own outgoing-call timer. The Max outgoing call duration parameter defaults to 60 minutes on a cellular unit, so the session ends on schedule and returns only when the next connection attempt succeeds. Set the duration to 0 for an unlimited session, or to a longer site-approved value, then confirm the fix with separate WAN and gateway tests.
Why does an eWON Flexy go offline after exactly one hour on Talk2M? #
The documented default of the Max outgoing call duration parameter is 60 minutes, so a cellular unit ends its Talk2M call when that time is up and stays offline until its next outgoing call succeeds.
HMS's Talk2M and Internet connection documentation and its support notes on changing MaxCallDur define the parameter as the maximum amount of time of the outgoing call with the operator's network; when that amount of time is reached, the unit stops the call. eCatcher shows the unit offline from that moment because the remote-access session no longer exists, while the WAN link itself is untouched.
The precision of the drop is the fingerprint. A failing link, a carrier outage or a firewall that kills the tunnel cuts sessions at irregular times, because none of them counts from the moment the call began. Drops at 59, 61 or 87 minutes point elsewhere; a drop on the hour, every hour, points at the timer.
How do I prove the timer, not the internet link, is failing? #
Record the eCatcher online and offline timestamps across two full cycles while leaving the WAN, firewall and cellular service untouched; a fixed interval that repeats on schedule identifies the timer, because a failing link drops at irregular times.
- Power-cycle the unit or start a fresh Talk2M session, and write down the time eCatcher first reports it online.
- Change nothing on the WAN, the firewall in front of the unit, or the cellular service while you observe.
- Note the time eCatcher reports the unit offline and the time it reports online again.
- In parallel, test internet access from a device on the same WAN network and from a device that uses the unit as its gateway.
- Repeat for a second cycle and compare the two online spans.
Worked example: eCatcher reports the unit online at 06:12. The first drop lands at 07:12, because 06:12 plus 60 minutes is 07:12. The unit returns at 08:42 after 90 minutes of retrying, and the next drop lands at 09:42, the same interval again counted from the new session start. Two online spans of identical length, each timed from its own reconnect, are the signature of the duration limit; a WAN fault cannot reproduce that pattern twice by coincidence.
If the parallel internet tests stay green through the drop, the WAN path is healthy and the session layer is at fault. If they fail too, repair the upstream path first, because the timer diagnosis only holds while the link itself is up.
What is Max outgoing call duration and where do I change it? #
The parameter caps how long one outgoing call over the cellular network may run; HMS documents it as the Max outgoing call duration, with MaxCallDur as the underlying parameter name, and you edit it in the unit's configuration among the outgoing Internet connection settings.
Open the unit's web configuration, find the setting among the outgoing connection parameters, and record the value it shows before changing anything. A stored value that matches the observed session length closes the diagnosis. Note what the timer does not touch: firewall rules, the SIM contract and the LAN side all stay as they are, so this change needs no coordinated window.
What value should the Max outgoing call duration get? #
Enter 0 to remove the limit entirely; the vendor's guidance for hourly disconnects says to increase the value or set it to 0 to disable it, and 0 is the right choice when the Talk2M session must stay up continuously for remote support and data collection.
If plant or carrier policy still requires periodic re-registration, choose the duration from the operating requirement instead of from the observed offline gap, and size it above the longest planned remote session: 480 minutes covers an 8-hour shift, and 600 adds two hours of margin. Apply the change, leave the settings page, reopen it and confirm the saved value stuck, then hold a session open across the old boundary to verify the scheduled drop is gone.
One caution for live work: a call ended by this timer cannot be extended from the remote side, so keep local staff or a local access path available whenever a remote session is used on running equipment.
Decision: continuous remote access with no policy against it — enter 0. A policy-mandated cap — enter that cap, sized above the longest session you plan.
Why do devices behind the eWON keep internet access while Talk2M shows offline? #
Because the WAN interface, the gateway forwarding and the Talk2M client are separate functions; the timer closes only the remote-access call, so downstream equipment keeps routing through the unit while eCatcher already reports it offline.
That is why the reported installation keeps its internet access on both sides of the drop: packet forwarding runs independently of the remote-access session. It also means a green internet test never certifies the session, so record the two results separately every time. Treat the offline gap between calls as reconnect behavior rather than a property of the link. The same separation explains the sibling fault where a VPN-connected Flexy gets an address but cannot be pinged: session state and IP path each need their own test.
What if the unit still drops offline after the change? #
Then stop raising the limit and test the reconnect path instead: match the session close in the unit's event records to the configured duration, and split the offline gap into the time before the first new attempt and the time spent on failed attempts.
- A long silence before any new attempt points at the unit's own connection scheduling or at the interface state, not at the network.
- Repeated failed attempts point at the WAN path, the operator's service, or the firewall and router in front of the unit; the guide on choosing a firewall VPN for an industrial remote access router covers that side of the setup.
- A firewall that passes an established session can still refuse a new one, so check the outbound rules against a fresh session, not against the one that already worked.
- On a cellular installation, confirm the modem still has a data path while Talk2M is down; the timer ends the call and says nothing about the SIM or the service behind it.
- Change one thing in each test cycle so the cause-and-effect record stays readable.
What goes into the support file when the cycle continues? #
Send a full backup with support files when the saved duration is correct but the cycle persists, when drops land at irregular times, or when reconnection attempts fail; export it while the disconnect window and its timestamps are still known.
Package it with the details that steer the analysis:
- Unit model and expansion card, for example the reported Flexy 201 with its FLX3101 cellular card.
- Firmware revision, 11.2s2 in the reported case.
- The saved value of the duration parameter.
- eCatcher online and offline timestamps for at least two cycles.
- WAN and gateway-client test results captured during a drop.
- Whether the pattern reproduces after a clean power-up.
Send it through the unit's official support channel or the local distributor, and put the timing in one line of notes: a drop pinned to the configured duration reads as a deliberate limit, while irregular losses read as transport, reconnect or filtering trouble. The decision splits the same way. A drop that matches the configured duration is a configuration item, and the change above ends it; anything irregular belongs to the reconnect path and goes out with the file.
Questions asked
Does the hourly disconnect also affect a unit connected by Ethernet instead of a cellular card?
The documented behavior covers cellular units, whose internet connection is an outgoing call to the operator's network; the cap on that call is the 60-minute default. A unit that reaches the internet over Ethernet has no operator call to time out, so an hourly drop there is a different fault - trace the firewall and session logs instead of the duration parameter.
Devices behind the eWON also lose internet at the same time - is it still the timer?
No. When gateway clients lose their internet path at the same time the unit goes offline in eCatcher, the fault is upstream of the Talk2M session: the WAN link, the router or firewall in front of the unit, or the operator's service. Restore a stable internet path first, because the duration setting does not touch packet forwarding.
The unit stays offline for 1 to 1.5 hours before it returns. Should that gap be entered as the new duration?
No. The gap is not a configured value; it is whatever the unit's own retry behavior needs to place the next outgoing call successfully. Read it from the event records as three timestamps: the session close, the next attempt, and the first successful registration. In the reported case the gap ran 1 to 1.5 hours, but it moves with the operator's network and the service state, so never copy an observed gap into the duration field.
Does the fix depend on the Flexy 201, the FLX3101 card and firmware 11.2s2?
No. The outgoing-call timer and its default are documented for the family's cellular connections, not for one firmware build, and the reported symptom on that exact combination matches the documented default. Before editing, open the unit's configuration, confirm the Max outgoing call duration parameter is present, record the value your firmware shows, then apply the change and re-check that it saved.