Edge computing and IIoT Published 7 min read

Short answer

When groov Manage opens over Wi-Fi but Ignition Edge will not load, the gateway host's firewall is scoped per interface and the wireless interface lacks Ignition's access rules. Enable both firewall controls for that interface in groov Manage, save after each change, and verify by opening the gateway at its HTTPS port from the same wireless client.

On this page
  1. What the symptoms tell you
  2. Why the fault follows the interface
  3. Enable Ignition Edge on the wireless interface
  4. Worked example: one host, two interfaces
  5. Verify the launch from the same client
  6. If the port still does not answer
  7. What the fault is not
  8. The decision for each case
  9. Questions asked

groov Manage opens over the wireless network, but Ignition Edge will not: every browser reports the address unreachable, and the Open Ignition Edge launcher fails the same way. That combination is not Windows Firewall and not an expired trial. It is the gateway host's own firewall, and on a groov EPIC it is scoped per network interface: the permissions that let the launch work over the wired port do not exist on the wireless interface. Enable the two Ignition Edge firewall toggles for the wireless interface, save after each change, and confirm the launch from the same wireless client. The sections below read the symptoms, apply the fix, prove it with numbers and end with the decision for each outcome.

What the symptoms tell you #

Four observations, read together, pin the fault:

Observation What it rules in or out
groov Manage loads from the wireless client The host is up and the wireless path to it passes management traffic
Chrome and Microsoft Edge fail identically at the launch address Not a cache, extension or browser-profile problem
The same address worked over the wired port days earlier The gateway and its license were sound; what changed is the client's path
The connection never opens — a timeout, not a gateway error page The request is discarded before Ignition Edge can answer

Two candidates survive that table: a rule scoped to the interface the client now arrives on, or a block on the network path between the wireless client and the host. The host firewall comes first because groov Manage — served by the same host at the same address — still gets through. Same address, same interface, only the destination service differs.

Why the fault follows the interface #

On a groov EPIC, firewall access is configured per network interface in groov Manage: each interface carries its own set of inbound service toggles, and an access granted on one interface is not inherited by another. Ignition's user manual fixes the gateway's default ports at 8088 for HTTP and 8043 for HTTPS, and the Open Ignition Edge launcher targets the HTTPS port, so the address your browser dials is identical whichever way the packets arrive.

Move the client from the wired network to the wireless one and the same request now lands on an interface whose rule set holds no Ignition entries. The host discards it, and every browser reports an unreachable address. Nothing changed on the gateway: its license, its modules and its wired rules are untouched. What did not follow the client is the set of interfaces permitted to reach the gateway's web service.

The toggles exist precisely so access can differ per interface. That scoping applies to every service the host exposes — an entry enabled on one interface covers only that interface — which is exactly the behavior the symptoms describe.

Enable Ignition Edge on the wireless interface #

The fix lives in groov Manage, reached over the connection that already works:

  1. From the wireless client, open groov Manage at the address that loads.
  2. Open the host's firewall settings and select the wireless interface, the one that client's traffic arrives on.
  3. Enable the first of the two toggles that grant Ignition Edge inbound access on that interface, then save. Labels differ between firmware builds; read them on the interface's own firewall page rather than matching any list written elsewhere.
  4. Enable the second toggle, then save again. The save after each change is part of the documented procedure: one combined save can leave one change uncommitted.
  5. Leave the wired interface's rule set alone. The change is scoped to the wireless interface, which keeps the rest of the network's posture unchanged.

One security note: these toggles open inbound gateway access on a wireless network, so confirm that SSID sits inside the OT segment before enabling them, and record the change the way any firewall change is recorded.

Worked example: one host, two interfaces #

Give the fault numbers. Example addresses: the gateway host's wireless interface at 192.168.1.50 and its wired port at 10.1.20.30; the client sits on the wireless network; the service under test is the gateway's documented HTTPS port.

Client reaches the host on Port dialed Ignition permission on that interface Result
192.168.1.50, wireless groov Manage's own HTTPS address Enabled Page loads
192.168.1.50, wireless 8043 (Ignition HTTPS) None Connection times out
10.1.20.30, wired 8043 (Ignition HTTPS) Enabled Page loads — the state you had days ago

The arithmetic of the drop: same host, same port, one variable. groov Manage answers, so the address and the wireless path are good; the dialed port is the documented one; the only input that differs between the working rows and the failing row is the interface's permission, present on the wired interface and absent on the wireless one. After steps 3 and 4 above, the wireless interface carries both Ignition entries, the permission input flips from absent to present, and the failing row turns into a loaded page. That flip, checked from the same client, is the proof of the repair.

Verify the launch from the same client #

Stay on the wireless client and run both paths. First select Open Ignition Edge in groov Manage and let it open the gateway page. Then type the address in full — https, then the same host address that opened groov Manage, a colon and the HTTPS port, for example 192.168.1.50:8043. If both paths load the gateway, the fault is closed.

A page that opens and then keeps falling over is wireless instability, not this firewall; that is a separate fault with its own fix for holding an Ignition Edge connection up through wireless dropouts.

If the port still does not answer #

  • Both toggles read enabled after their saves and the port is still dead: the drop is outside the host. Confirm the browser address is exactly the one groov Manage used, then chase the path — routing between VLANs, an access list or an upstream firewall discards that port's packets exactly as a host rule would. The method is the one used to trace remote SCADA access through firewalls and proxies.
  • groov Manage itself stops loading over wireless too: connectivity or addressing is broken, not a firewall rule. Restore the link first, then retest the launch.
  • Gateway pages open but the gateway never becomes usable: the fault has moved inside the host. A gateway stuck starting after a Java trust store corruption is one documented shape of that, and it has its own repair.

What the fault is not #

Windows Firewall plays no part on a groov EPIC: the host's firewall is the device's own, configured in groov Manage, so there is no Windows rule to change. The suspicion is natural on a Windows PC, where the host firewall can also treat networks differently, but in this case the only firewall in the path belongs to the gateway host.

An expired trial does not behave this way either. A trial that runs out announces itself inside the running gateway, in its status and licensing messages, while the web address keeps answering; a browser that cannot open the port at all is a transport failure. If you do meet a trial message, it has its own logic — the 8.3 flash trial can report expired even with a license present, which is why an Ignition 8.3 flash trial shows expired with a license is its own subject.

The decision for each case #

  • groov Manage loads over wireless, every browser fails at the launch address, and it worked over the wired port earlier: enable both Ignition Edge toggles on the wireless interface in groov Manage, saving after each, and judge the repair by the launch opening from that same client. This is the documented fix and it closes the fault.
  • Both toggles confirmed enabled after their saves and the port still dead: stop touching the host and take it to the routing and upstream-firewall checks above.
  • groov Manage gone over wireless as well: fix connectivity and addressing first; no firewall toggle is the answer.
  • Gateway reachable but licensing or runtime errors inside: a different fault family, judged from what the gateway itself reports, not from the firewall.

In the documented case it ends at the first bullet: two toggles, two saves, and a launch that opens from the client that could not reach it minutes before.

Questions asked

Which ports does Ignition Edge use for browser access?

The documented defaults are 8088 for HTTP and 8043 for HTTPS, and the Open Ignition Edge launch points at the HTTPS one. You can move the SSL port to the standard 443 with the Gateway Control Utility, but the firewall toggles still have to be enabled on every interface clients arrive on. The port number is never the fault by itself; the interface rules decide whether it answers.

Why did Ignition Edge work on the wired network but not over Wi-Fi?

Because the gateway host's firewall is configured per interface. The rule set that allowed Ignition Edge on the wired port stays with that port and is not inherited when your client moves to the wireless network, so the same address now arrives on an interface with no Ignition entries and the host drops the request. Enabling the two Ignition toggles on the wireless interface restores the wired behavior.

Does a failed launch mean the free trial expired?

No. An expired trial announces itself inside the running gateway, in its status and licensing messages, while the web address keeps answering. A browser that cannot open the port at all is a transport problem: something between the client and the gateway, most often the host firewall's per-interface rules, is dropping the connection. Fix the firewall first and judge licensing only from what the gateway itself reports.

Do I really have to save between the two firewall changes?

Yes. The documented procedure enables one toggle, saves, enables the second and saves again. The save commits each change to the interface's rule set, so toggling both and saving once risks losing one of them. If the launch still fails afterwards, reopen the firewall page and confirm both entries read as enabled before looking anywhere else.

What if both controls are enabled and the port still does not answer?

Then the block sits outside the host. Confirm the browser address is exactly the one that opens groov Manage, confirm the client is on the same wireless network as that address, and then check the path: routing between VLANs, an access list or an upstream firewall can drop the port's packets just as a host rule would. At that point it is a network-path problem, not a groov Manage setting.

Keep reading

  • Explainer

    Why Kepware to ThingWorx uses AlwaysOn, not the firewall rule

    KEPServerEX and ThingWorx Kepware Server communicate with ThingWorx over the AlwaysOn protocol, and a secure AlwaysOn connection can use a self-signed or a CA-signed certificate. The edge-side Kepware host initiates one outbound TCP session to the port configured in its ThingWorx connection, typically 443, so IT writes a single outbound rule and no inbound rule to the edge.

    Edge computing and IIoT

  • Explainer

    ABB TotalFlow module for Ignition: what exists today

    The ABB TotalFlow entry on the Ignition Edge IIoT page is an entitlement, not a download: the driver is a third-party Cirrus Link module that reached beta after that listing was written. It runs on Ignition Edge and standard Ignition, polls G2 late, G3, G4 and G5 flow computers, and needs MQTT Transmission to publish, because the G5 has no native MQTT client.

    Edge computing and IIoT

  • How-to

    Bridging OPC UA PLC data to MQTT with an edge PC

    Keep the OPC UA server on the PLC side and give MQTT publishing its own role on a separate edge PC that acts as the OPC UA client and MQTT publisher. Commission the two links independently — first a verified tag read, then a verified subscriber message — and only then widen the tag set.

    Edge computing and IIoT