IMD SolutionComputing LibraryShop main store

Explainer

Will a remote access gateway work in China

Remote access and virtualization Published 7 min read

Short answer

A remote access gateway works in China in both directions. With the machine in China and the office outside, the managed cloud service detects the gateway's location and applies the China connection server automatically, so no special setting exists. With the office inside China, raise the vendor-requested move to a specific connection server before commissioning; a company OpenVPN server replaces the whole location question with one you run yourself.

On this page
  1. Which side sits in China decides the setup
  2. How Talk2M assigns the connection server
  3. What changes when the gateway is in China
  4. Commissioning a company OpenVPN server instead
  5. Working the path for a machine in Shenzhen and an office in Rotterdam
  6. When the session is up but the machine stays dark
  7. The decision per direction
  8. Questions asked

Yes — in both directions, and the difference between the two is one connection server, not the hardware. A remote access gateway at a machine inside China works when the office is outside China: the Talk2M cloud service detects that the gateway is in China and applies the China connection server on its own, so an Ewon Flexy 205 at a Chinese customer has no China-specific setting to enter. The direction that needs action is an office inside China reaching a machine abroad: the vendor moves the account to a specific connection server on request, and that request belongs before commissioning, not in the middle of a failed startup. This article gives the decision per direction, the server assignment mechanics behind it, the company OpenVPN alternative, and a worked example for a machine in China served from a European office.

Which side sits in China decides the setup #

Three inputs decide the commissioning path: where the gateway sits (machine side), where the engineers connect from (office side), and whether the machine uses the managed Talk2M cloud or a company OpenVPN server. Each input points at a different failure layer, which is why the question has three answers, not one.

Case What happens What you do
Machine in China, office outside China Talk2M detects the gateway's location and applies the China connection server automatically; the vendor describes this as transparent to the user Commission normally — there is no China-specific field to fill
Machine outside China, office inside China The automatically assigned server is not the right one for a China office Request the move to a specific connection server through the vendor's support process, before commissioning
Company OpenVPN server, either direction Talk2M's location handling is out of the picture; the gateway dials your server Place and run endpoints both sites can reach; the server must support OpenVPN

If the choice between the managed cloud and a company server is itself the open question, the guide to choosing a firewall VPN for an industrial remote access router works through that selection. And a router that connected fine at another site proves nothing about this one: at a Chinese site the failing layer is usually the local Internet connection or the site's outbound rules, not the gateway model.

How Talk2M assigns the connection server #

The assignment is fixed once, at account creation: Talk2M attaches a VPN server to the account using the public IP of the computer that created it, which the vendor's support portal documents as VPN server attribution. Machines added later are not pinned to that choice. At connection time the service looks at where the gateway is and applies the location-dependent settings itself, which is why the machine side and the office side stay separate inputs.

The practical consequence for planning: create the account from a network in the region your offices connect from, and let each machine follow its own country. A fleet spread across China and Europe lives on one account without contradiction.

What changes when the gateway is in China #

For the machine side, one thing changes and you never touch it. A gateway located in China must use the China NAP server, which the vendor's address list names as sclient.vpn15.talk2m.com, and the service selects it by location detection — no field in the gateway configuration carries that choice.

Two things you do own. First, the firewall: permit outbound traffic to the service's published addresses and ports, and because endpoint addresses change with notice, keep both the previous and the new address sets open across a change window — the vendor's endpoint notice asks for exactly that. Second, the local diagnosis: the gateway's Summary page shows the Internet connection and VPN connection status at a glance, so sort a WAN failure from a server the site will not reach from a VPN authentication failure before touching anything behind the gateway.

Commissioning a company OpenVPN server instead #

Talk2M is not the only path. The gateway connects to a company server as long as that server supports OpenVPN: you configure the custom setup through System > Setup > Communication > VPN, or load an external OVPN file. A server that speaks some other VPN protocol is not interchangeable, because the client side is OpenVPN and the server has to match it.

The same move is documented for another gateway family in pointing an eWON Cosy at a custom OpenVPN server. What does not transfer is Talk2M's automatic location handling: with your own server, endpoint placement, certificates and routes are design decisions you own, and the China question becomes the question of where you put the server.

The machine side needs a cabinet box that runs the OpenVPN client; when you specify that box, a fanless industrial mini PC is the hardware category built for the role.

Working the path for a machine in Shenzhen and an office in Rotterdam #

Inputs. Machine site in Shenzhen, China — the deployment case behind this question, a European builder serving Chinese customers. Office in Rotterdam, outside China. Service: the managed Talk2M cloud, with the account created from the Rotterdam office network, so the creating computer's public IP is a Dutch one. The China NAP server sclient.vpn15.talk2m.com, applied by detection per the vendor's address list. The firewall permit list holds the current and the previous service address sets — 2 groups across a change window, per the vendor's endpoint notice.

Rule. The gateway's country selects the connection server it dials, and Talk2M applies that selection automatically. The office's country triggers an action only when the office sits inside China, and that action is the vendor-requested move to a specific server.

Arithmetic. Direction cases: 2 machine locations × 2 office locations = 4 commissioning cases. The vendor-requested move attaches to one trigger, an office inside China. For this deployment: 0 China-specific settings to enter, 1 automatic server selection (the China NAP server), 2 permit-list groups to hold open.

Result. Rotterdam sits outside China, so the trigger is absent: the Shenzhen machine commissions through the standard registration path and lands on the China NAP server without input.

Decision. Office outside China: register normally and expect 0 settings to enter and 2 permit-list groups to hold. Office inside China: the pre-commissioning action count changes from 0 to 1 — raise the server-move request first. The threshold is the office's country, never the machine's.

When the session is up but the machine stays dark #

A connected VPN is a transport path, nothing more. If the gateway reports the VPN up and the controller still will not talk, work the layers in order: the machine-side subnet first, because an office LAN using the same address range pulls traffic away from the tunnel; then the routes and access permissions on the gateway; then the controller's own protocol access.

Losing device visibility right after an OpenVPN session comes up is a pattern with its own checklist, written up in troubleshooting visibility loss after an OpenVPN session connects. When the tunnel is fine but the engineering software will not go online to the controller, that is the PLC layer, and why a PLC agent will not go online remotely walks it from the gateway side. Changing an HMI tag or a driver setting will not repair a tunnel that is down, and re-establishing the tunnel will not fix a wrong subnet.

One rule sits above all of it: remote access is for engineering work, and a machine that can move keeps its local emergency stop and local controls independent of any remote connection.

The decision per direction #

  • Machine in China, office outside China: yes — standard Talk2M commissioning, no China-specific settings, and the service selects the China NAP server by detection.
  • Machine outside China, office inside China: yes, after the vendor-requested move to a specific connection server — make that request step one of commissioning.
  • Company OpenVPN server instead: yes wherever your endpoints are reachable; the server must support OpenVPN, and placement, certificates and routes are yours.

In every case the China dependency is the connection server and the site's outbound rules — not the gateway hardware.

Questions asked

Where should the Talk2M account be created from?

Create it from the network your service offices normally use. The cloud service fixes the account's connection server from the public IP of the computer that creates the account, so the office side gets a server it can reach well. The machines are not pinned to that choice, because the gateway side is adjusted by location detection, including to the China server.

Can one account serve machines in several countries?

Yes. The connection server is a property of the account, not of any one machine, and each gateway dials it with the location-dependent settings applied for its own country. A fleet with machines in China and in Europe can share one account. The constraint to watch is the office side: once an office sits inside China, plan the vendor-requested server move into the deployment and confirm the resulting server serves the whole fleet.

What do I hand the site network administrator in China?

The vendor's current address and port list for the service, a request to permit outbound traffic to it from the gateway, working DNS resolution on the machine network, and written confirmation that the site allows the connection. Keep the previous and the new address sets both in the permit list across an endpoint change, so the administrator can approve the path without guessing ports.

If I run my own OpenVPN server instead, where should it sit?

Where both sides can reach it under their local rules — the placement the managed service would otherwise decide for you. Name endpoints the Chinese site can dial out to and your offices can reach, and test both directions from the real networks, because a lab bench in either country proves the other one nothing.

Keep reading

  • Selection guide

    Choose a firewall VPN for an industrial remote access router

    The Ewon tunnel is OpenVPN, initiated outbound. For Ewon-client-to-firewall-server mode, buy a firewall with an OpenVPN server role; IPsec or PPTP support is irrelevant. If you only use Talk2M, the firewall needs no VPN role at all, just outbound rules for *.talk2m.com on the ports in KB-0209, which requires hostname and wildcard address objects.

    Remote access and virtualization

  • Troubleshooting

    Ping works but PLC program download fails over remote access

    ICMP success proves only the routed IP path, not the programming session. A download opens separate query and download connections on documented TCP and UDP ports, and broadcast discovery does not cross a routed VPN. Point the controller's default gateway at the remote-access router LAN address, permit both programming ports to the controller LAN IP, and add the controller manually by IP.

    Remote access and virtualization

  • Troubleshooting

    Troubleshooting a PLC agent that will not go online remotely

    A green remote session proves only that you reached the gateway. Prove the programming connection locally first, then the agent's target address and subnet, then the agent type and protocol, then the client — one boundary at a time. Most of these faults are a mistyped target address or an agent type that carries the wrong protocol.

    Remote access and virtualization