TIA Portal V12 project will not transfer to an IPC 277D

Operating systems on the plant floor Published 6 min read By IMD Solution engineering team

Short answer

The transfer fails because the runtime version selected in the TIA Portal device configuration does not match the WinCC RT Advanced build in the panel's image. Set the selection to the image's build, or reflash the Embedded Bundle to a V12 image if the project needs V12 features. No TIA Portal downgrade is involved.

On this page
  1. What the transfer compares
  2. Set the version in the device configuration
  3. Why there is no separate V12 SP1 order number
  4. When the project needs V12: update the Embedded Bundle
  5. The decision for each case
  6. Questions asked

A TIA Portal V12 project refuses to transfer to an IPC 277D because the runtime version selected in the device configuration does not match the WinCC RT Advanced build inside the panel's image. Set that selection to the build the image carries and the transfer goes through; if the project needs V12 features the image lacks, update the panel's Embedded Bundle instead. No downgrade of the engineering station is involved: TIA Portal V12 configures both V11 and V12 runtimes, and there is no separate V12 installer to hunt for.

What the transfer compares #

When the transfer dialog opens, TIA Portal compares the runtime version configured on the HMI device against the WinCC RT Advanced build preinstalled in the panel's image, and refuses the download when the two differ. The check runs before any file is written, which is why the message names the version rather than the cable, the switch or the license. The factory image on an IPC 277D is a Windows Embedded Standard 7 build that carries one fixed runtime: on this panel the version arrives inside the image, and the bundle update, not a setup routine, is the supported way to change it.

In the case behind this article, the project was engineered in TIA Portal V12 with the device configuration left at the V12 runtime, while the panel image carried WinCC RT Advanced V11 SP2. The handshake measured 12 against 11 and refused the transfer. Setting the device configuration to V11 cleared the error against that SP2 image, and the same project then transferred over Ethernet with the engineering station untouched.

Worked example — the refusal, computed the way the tool computes it:

  • Project side: configured runtime WinCC RT Advanced V12, major version 12.
  • Panel side: image build WinCC RT Advanced V11 SP2, major version 11, service pack 2.
  • Comparison: 12 does not equal 11, so the handshake fails before a single byte moves.
  • Corrected selection: set the runtime version to the image's build, and 11 = 11 with SP2 = SP2, so the transfer proceeds.

Select the version the panel will run, not the version the project was authored in. On a V12 image you select V12 even for a V11-authored project, because the vendor documents upgrading V11 projects to V12 SP1 with the configuration software — the upgrade path, not the selection, carries older projects forward. The same image-versus-project rule holds across the panel families, and the guide on matching an HMI panel image to its TIA Portal project version walks through that pairing end to end.

Set the version in the device configuration #

Confirm the build before changing anything. If the panel arrived second-hand or its image was rebuilt by someone else, the article on identifying HMI software on a panel PC shows how to pin the installed runtime down before you touch the configuration; a selection made from memory is what produces this fault in the first place.

  1. Open the project and select the IPC 277D in the project tree.
  2. Open the device configuration for that HMI device. The field that matters selects the runtime version; its exact label shifts between TIA Portal service packs, but it is the one list on the device offering the WinCC RT Advanced builds.
  3. Set it to the build the image carries — on this panel, the V11 build with service pack 2.
  4. Recompile the HMI device as a full rebuild so the change reaches the transfer data.
  5. Start the transfer over Ethernet again.

If the transfer now completes, the fault is closed. A missing or capped runtime license is a different fault that shows up at runtime start, not at transfer; what a SCADA runtime license covers beyond running the project is a subject of its own article.

Decision: an image older than the project needs no reflash, no new license and no downgrade — align the selection, recompile, transfer.

Why there is no separate V12 SP1 order number #

The impression that a base V12 does not exist comes from the catalog layout, not from the product line: the order numbers for this runtime do not encode the service pack. The two license packages for the runtime on this panel are:

Order number Package Licensed variables (PowerTags)
6AV2104-0BA02-0AA0 WinCC Runtime Advanced V12 128
6AV2104-0DA02-0AA0 WinCC Runtime Advanced V12 512

PowerTags are the process variables the runtime is licensed to use; 128 and 512 are the two counts sold. Once SP1 was released, these packages shipped with SP1 and the latest updates applied, so no separate order number distinguishes V12 from V12 SP1 — the SP level rides inside the same number.

Decode the pair and the rule shows itself: the two numbers differ by exactly one character, B against D, which moves the licensed count from 128 to 512 variables, and no position in either number holds a service-pack digit. A catalog search that keeps returning SP1 references therefore tells you the delivery is current, not that a base V12 is missing.

When the project needs V12: update the Embedded Bundle #

If the application uses features the V11 build lacks, stop tuning the selection and move the panel to a V12 image. For the IPC227D and IPC277D that is the Embedded Bundle update, documented in Siemens support entry 79542563: it rewrites the panel's Windows Embedded Standard 7 image with a current WinCC RT Advanced build and, where the machine uses one, carries the WinAC RTX(F) software controller in the same image. The same entry documents moving V11 projects up to V12 SP1 with the configuration software, so the project side keeps pace with the panel side.

  1. Pull the bundle update that matches the panel's exact model from the vendor's support site, filtered by the order number printed on the panel.
  2. Back the panel up with the vendor's panel backup tool (ProSave) before anything else: the image write is destructive, it replaces the project, recipes and logged files stored on the panel, and it leaves the runtime down while it runs, so pick a window when the machine may stand still.
  3. Write the image from the prepared boot medium and let the panel rebuild itself.
  4. Check the runtime license after the rebuild; if the license key lived on the panel's storage rather than on a USB stick, re-apply it with the Automation License Manager before production relies on the panel.
  5. Select V12 in the device configuration, recompile, and transfer.

The pattern is not an oddity of one generation: bundles for the newer E-generation panel IPCs ship with later runtime versions again, so the image remains what sets the version the panel runs. If the same panel still serves an older WinCC flexible 2008 SP3 project instead, the configuration steps differ, and the walkthrough for configuring a SIMATIC IPC 277D with WinCC Flexible 2008 SP3 covers that pairing. Classic WinCC 7 stations are their own line with their own migration route; the two-hop path from WinCC 7.0 SP3 to 7.5 shares nothing with this selection.

The decision for each case #

Image build on the panel Selection in the device configuration Outcome
WinCC RT Advanced V11 SP2 V11 SP2 Transfer succeeds with the V11 feature set; the case in this article
WinCC RT Advanced V11 without a service pack V11 Transfer succeeds with the baseline V11 feature set
WinCC RT Advanced V12 or V12 SP1, after a bundle update V12, one selection with no separate SP1 entry Transfer succeeds with the V12 feature set; upgrade V11 projects to V12 SP1

Decision: read the build off the panel, match the device configuration selection to it, recompile and transfer. Reach for the bundle update only when the feature set genuinely requires V12, keep the engineering station at V12 throughout, and treat the search for a standalone V12 setup as a dead end — the version lives in the image, and the image is what you align or update.

Questions asked

Does TIA Portal V12 handle both V11 and V12 runtime projects?

Yes. The runtime version is a per-device setting, so one engineering station serves a mixed fleet: a panel with a V11 image gets V11 selected in its device configuration, a panel with a V12 image gets V12. No runtime is installed per project and no second engineering installation is needed.

Why does the catalog seem to offer only SP1 of WinCC RT Advanced V12?

Because the order numbers do not encode the service pack. Since SP1 was released, the same license packages ship with the latest service pack and updates already applied, so a catalog search shows SP1 everywhere but there is no separate article number to buy. What arrives is V12 at the current SP level.

How do I confirm which build the panel image carries before changing anything?

Read the version the runtime itself reports on the panel, or match the panel's order number against its bundle delivery documentation. If the unit arrived second-hand or its image was rebuilt by someone else, identify the installed HMI software first, because a selection made from memory is what produces this mismatch.

Will a project engineered for V11 still run on a V12 image?

The supported route is documented: projects with WinCC RT Advanced V11 upgrade to V12 SP1 with the configuration software. Open the project on the V12 engineering station, set the device runtime selection to V12, upgrade and recompile the project, then transfer it to the updated image.

Keep reading

  • Troubleshooting

    Fixing command 66 port error response timeout after a PC swap

    The error means the replaced PC's serial path no longer matches the configured one. Set the host port (COM1 to COM4 or Board) and interrupt level (IRQ 3, 4, 5 or 7) under F6 > F3 System Type and File Loads, keep 9600 8-N-1 on a null-modem cable, and run program transfers from a DOS 6.22 or Windows 9x station.

    Operating systems on the plant floor

  • Troubleshooting

    Box PC disk imaging to USB fails in the boot environment

    USB Legacy in the BIOS serves the pre-boot firmware only; the DOS boot environment Ghost V7 runs from needs its own driver for the USB controller and the enclosure. Prove which environment can see the destination, then change the transfer path — a boot medium with storage support, a network destination, or the disk moved to a bench PC — instead of re-toggling BIOS settings.

    Operating systems on the plant floor

  • How-to

    Configure IP networking on an edge PC with no SSH access

    A new edge PC that leaves the factory with DHCP and static addressing disabled has no IP address, so SSH cannot connect to it. Do the first configuration at a keyboard and monitor: set X1 to DHCP and the plant-side port to the planned static address, restart networking, then confirm both addresses with nmcli device status and ip a before opening SSH or browser management on port 9090.

    Operating systems on the plant floor