IMD SolutionComputing LibraryShop main store

Comparison

WinCC CAS versus SIMATIC IT Historian: which archive fits

Edge computing and IIoT Published 6 min read

Short answer

WinCC CAS is the long-term archive inside one WinCC system: it stores process values, messages and batch data from OS servers and SIMATIC BATCH. SIMATIC IT Historian is a plant-level historian that aggregates raw, compressed, validated and aggregated data from heterogeneous sources and adds KPI calculation and reporting. Choose CAS for a single WinCC installation; choose the Historian when you must consolidate several systems or serve validated, user-facing reports.

On this page
  1. What CAS does
  2. What SIMATIC IT Historian does
  3. Side-by-side
  4. A worked decision
  5. The reporting path is the part engineers leave too late
  6. Where this fits with the rest of the archiving stack
  7. The decision
  8. Questions asked

Neither product logs data from client PCs, and they answer different questions. WinCC Central Archive Server (CAS) is the long-term archive of one WinCC system: it collects process values, messages and batch data from the OS servers and SIMATIC BATCH and stores them time-based. SIMATIC IT Historian is a plant-level historian that aggregates and archives data from different sources - DCS, PLCs, MES, batch systems - and adds KPI calculation and reporting on top. The decision is simple: one WinCC system to archive, take CAS; several automation and MES systems to consolidate, or validated archiving and user-facing reports, take SIMATIC IT Historian.

What CAS does #

CAS is part of the WinCC architecture, not a standalone plant product. It backs up, collates and archives the long-term-relevant data that the WinCC system itself generates: process values, alarms and messages, and batch data coming from the OS servers and SIMATIC BATCH. Storage is time-based, and the archive server can run redundantly on server pairs. It does not ingest a DCS on the other side of the plant, a non-Siemens PLC network, or an MES layer; its input scope is the WinCC system it belongs to.

That makes CAS the default answer whenever the requirement is stated as "archive the data this WinCC system produces for years". You size the server, configure the archive segments, and the data lands in one place. No second platform, no extra connector layer, no separate license for a historian.

What SIMATIC IT Historian does #

SIMATIC IT Historian sits above the automation layer. Its job is to aggregate and archive data from different data sources - DCS, PLCs, MES and batch systems among them - so one repository holds the plant's history instead of one archive per system.

It also stores more than one grade of data. Depending on the requirement it archives raw, compressed, validated and aggregated data. The validated grade is there for regulated plants: a documented use case is archiving quality-relevant process parameters and values in validated form to fulfill FDA requirements.

On top of storage it provides KPI calculations from simple to medium complexity, and reporting and analysis: electronic batch records (EBR), statistical analysis such as top-ten alarm reports, and integration to MES. That reporting layer is the piece CAS does not have; CAS stores, and you extract.

Side-by-side #

Criterion WinCC CAS SIMATIC IT Historian
Scope One WinCC system Plant level, multiple sources
Data sources OS servers, SIMATIC BATCH DCS, PLCs, MES, batch systems
Archiving model Time-based long-term archive of process values, messages, batch data Raw, compressed, validated and aggregated data
Validated archiving for FDA use Not its role Documented use case, quality-relevant parameters in validated form
KPI calculation None built in Simple to medium complexity
Reporting Export from the archive; no built-in user reporting layer EBR, statistical analysis, MES integration
Fits when The requirement is exactly this WinCC system's data Data from several systems must land in one repository and serve reports

A worked decision #

Take a site with one WinCC 7.x SCADA system on two redundant OS servers, SIMATIC BATCH running the reactors, and a requirement to keep five years of process values and batch data for troubleshooting. Every source named in the requirement is inside the WinCC system, so CAS covers it: values, messages and batch data all arrive at the Central Archive Server, time-based, without a second platform to license, patch or validate. The decision for this case is CAS.

Now change two inputs. Add a packaging line on a separate controller family and a batch requirement to produce electronic batch records with statistical alarm analysis per campaign. The controller data is outside the WinCC system, and EBR plus statistical reporting is outside what CAS provides. This case needs the aggregation and reporting layer: SIMATIC IT Historian collecting from both sources, holding validated quality-relevant parameters, and serving the EBR and alarm statistics. The decision for this case is the Historian.

Both decisions follow the same test: list the systems that must appear in the archive, then list what users must do with the data. One system, storage only - CAS. Several systems, or storage plus validated data and reports - the Historian.

The reporting path is the part engineers leave too late #

Storage is the easy half; access is where projects stall. A common situation: the process department had simple Excel-plugin access to a PI archive at a previous site, and on the new system the only path out of the CAS archive is the WinCC archive export function, which they find neither flexible nor user-friendly. The archive is fine; the reporting path was never specified.

Decide the reporting route during selection, not after commissioning. If process users need their own queries, trends and batch records against the archive, that requirement alone pushes the decision toward SIMATIC IT Historian, whose reporting and analysis layer exists for exactly that. If engineers doing exports from WinCC tools is acceptable, CAS keeps the architecture minimal. Also check what the numbers must look like afterward: where aggregation is involved, the raw values must reach the historian in chronological order for the aggregates to be calculated correctly, so plan the data flow, not just the endpoint.

Where this fits with the rest of the archiving stack #

CAS is not the only central archive in the Siemens portfolio, and the comparison changes with the SCADA host. For PCS 7 systems the equivalent question is CAS versus Process Historian, which is covered in the article on PCS 7 CAS versus Process Historian. When the alternative on the table is a PI system rather than SIMATIC IT Historian, the article on WinCC CAS versus PI historian for long-term archiving works through the same decision with PI's strengths in user access. And if data already flows to a central historian but never arrives, the WinCC-side causes are laid out in the article on why WinCC tag data never reaches Process Historian 2014.

The decision #

  • Archive one WinCC system's process values, messages and batch data, no reports beyond exports: WinCC CAS. It is the system's own long-term archive; adding a plant historian for a single-source requirement buys nothing.
  • Consolidate DCS, PLC, MES and batch data into one repository: SIMATIC IT Historian. Aggregation across heterogeneous sources is its defining function; CAS cannot ingest them.
  • Need validated archiving for FDA-relevant parameters, KPI calculations, EBR or statistical reporting: SIMATIC IT Historian, because the validated data grade and the reporting layer exist only there.
  • Both needs at once: run CAS as the WinCC system's archive and the Historian at plant level; they occupy different layers and are not substitutes for each other in a mixed site.

Questions asked

Does WinCC CAS log data from the client computers?

No. CAS archives the long-term process values, messages and batch data produced by the OS servers and SIMATIC BATCH of a WinCC system, not the activity of the engineering or runtime client PCs. If you need data from machines that are not part of the WinCC system, a plant-level historian that aggregates other sources is the layer that collects it.

Which product consolidates data from a DCS, PLCs and MES into one archive?

SIMATIC IT Historian. It is built to aggregate and archive data from different data sources, including DCS, PLC, MES and batch systems, and it can hold raw, compressed, validated and aggregated data in the same repository. WinCC CAS stays inside its own WinCC system and does not ingest external historians or MES data.

Which historian supports validated archiving for FDA-regulated processes?

SIMATIC IT Historian is the one with a documented use case for this: it archives quality-relevant process parameters and values in validated form, alongside raw, compressed and aggregated data, to support FDA requirements. CAS is a system archive for WinCC data and does not carry that validated-archiving role.

Can end users query the archives from Excel?

A CAS archive is usually exported through the archive export functions of the WinCC system, which engineers find workable but limited for process departments. SIMATIC IT Historian adds its own reporting and analysis layer, including statistical views such as top-ten alarm reports and electronic batch records, so process users query the historian instead of exporting raw archives. Match the reporting tool to whichever archive you deploy before rollout.

Keep reading

  • Comparison

    WinCC CAS versus PI historian for long-term archiving

    WinCC CAS is a Siemens add-on that backs up, collates and archives long-term-relevant WinCC data from lower-level WinCC stations on one central server with RAID storage. PI is a separate plant-wide historian that collects from many source systems and serves many clients. Choose CAS when every record and consumer lives in WinCC; choose PI when several systems share one process history.

    Edge computing and IIoT

  • Comparison

    PCS 7 CAS versus Process Historian: which archive to deploy

    Deploy the Process Historian on new and upgraded PCS 7 systems: it ships on the PCS 7 media, licenses by archived value count, and lands OS tags, messages and BATCH data in one SQL database. Keep the Central Archive Server only as a read-only archive for OS generations the current collector cannot read.

    Edge computing and IIoT

  • Explainer

    WinCC runtime archives versus a central process historian

    Each WinCC server archives its own tags at runtime; SIMATIC Process Historian is a separate central tier that collects the long-term-relevant tags and messages from multiple WinCC servers into its own SQL Server database. Keep runtime archiving on, keep archives on each server, and point long-term and cross-server queries at the historian.

    Edge computing and IIoT